USER GUIDE

FLTA

8 (9) 

 

Produal Oy 

Keltakalliontie 18, 48770 Kotka FINLAND 

Tel: +358 10 219 9100 / Fax: +358 5 230 9210 

[email protected] 

www.produal.com 

Information is subject to change without prior notice. 

Register 

Parameter description 

Data type 

Values 

Range 

300

52

 

SID 2, AO1 

Signed 16 

0…100 

0,0…10,0 V 

300

53

 

SID 2, AO2 

Signed 16 

0…100 

0,0…10,0 V 

… … 

 

 

 

30

244

 

SID 98, AO1 

Signed 16 

0…100 

0,0…10,0 V 

30

245

 

SID 98, AO2 

Signed 16 

0…100 

0,0…10,0 V 

30

246

 

SID 99, AO1 

Signed 16 

0…100 

0,0…10,0 V 

30

247

 

SID 99, AO2 

Signed 16 

0…100 

0,0…10,0 V 

30

248

 

SID 1, TE 

Signed 16 

 

See note 2 

30

249

 

SID 1, SP 

Signed 16 

 

See note 3 

30

250

 

SID 1, RH 

Signed 16 

 

See note 4 

30

251

 

SID 1, FAN 

Signed 16 

 

See note 5 

30

252

 

SID 2, TE 

Signed 16 

 

See note 2 

30

253

 

SID 2, SP 

Signed 16 

 

See note 3 

30

254

 

SID 2, RH 

Signed 16 

 

See note 4 

30

255

 

SID 2, FAN 

Signed 16 

 

See note 5 

… … 

 

 

 

30

636

 

SID 98, TE 

Signed 16 

 

See note 2 

30

637

 

SID 98, SP 

Signed 16 

 

See note 3 

30

638

 

SID 98, RH 

Signed 16 

 

See note 4 

30

639

 

SID 98, FAN 

Signed 16 

 

See note 5 

30

640

 

SID 99, TE 

Signed 16 

 

See note 2 

30

641

 

SID 99, SP 

Signed 16 

 

See note 3 

30

642

 

SID 99, RH 

Signed 16 

 

See note 4 

30

643

 

SID 99, FAN 

Signed 16 

 

See note 5 

Holding registers 

Register 

Parameter description 

Data type 

Values 

Range 

400

34

 

Coils 16 - 01 

16 bit 

 

 

400

35

 

Coils 32 - 17 

16 bit 

 

 

… … 

 

 

 

400

45

 

Coils 192 - 177 

16 bit 

 

 

400

46

 

Coils 208 - 193 

16 bit 

 

 

400

47

 

Not in use 

16 bit 

 

 

400

48

 

Not in use 

16 bit 

 

 

400

49

 

Not in use 

16 bit 

 

 

400

50

 

SID 1, AO1 

Signed 16 

0…100 

0,0…10,0 V 

400

51

 

SID 1, AO2 

Signed 16 

0…100 

0,0…10,0 V 

… … 

 

 

 

40

246

 

SID 99, AO1 

Signed 16 

0…100 

0,0…10,0 V 

40

247

 

SID 99, AO2 

Signed 16 

0…100 

0,0…10,0 V 

 

Summary of Contents for FLTA

Page 1: ...e transmitters and I O modules can be connected to the base station by using the FLSER commissioning tool See the commissioning instructions for transmitters and I O modules from the documentation of...

Page 2: ...l switch to the RSSI position On CARE text appears on FLTA display and RX indicator light flashes rapidly 2 Take the FLSER commissioning tool to the planned installation places and check the signal st...

Page 3: ...1 10 V TEUFL Temperature 50 150 C Analogue input 0 10 V TEUFL DI Temperature 0 50 C Digital input 0 0 V 1 10 V KLUFL LUX 11 Temperature 50 150 C Humidity 0 100 rH Luminosity 0 2000 lx HDHFL RH Temper...

Page 4: ...tter or low battery approx 5 of capacity remaining There are two types of alarms depending on the Modbus usage If the Modbus is used the alarms can only be read via Modbus For example a transmitter wi...

Page 5: ...osition 6 Push the and buttons to select OFF for the transmitter sensor ID SID 7 Push the OK button Wait message starts to flash on the FLSER tool display You have now approximately 30 seconds to comp...

Page 6: ...ut Registers 0x05 Write Single Coil 0x06 Write Single Register 0x0F Write Multiple Coils 0x10 Write Multiple Registers 0x16 Mask write Register NOTE The Modbus commands must have at least 500 ms inter...

Page 7: ...f 1 On 10202 SID 2 PIR Bit 0 1 0 Off 1 On 10298 SID 98 PIR Bit 0 1 0 Off 1 On 10299 SID 99 PIR Bit 0 1 0 Off 1 On 10301 SID 1 DI1 Bit 0 1 0 Off 1 On 10302 SID 2 DI1 Bit 0 1 0 Off 1 On 10398 SID 98 DI1...

Page 8: ...2 SID 2 TE Signed 16 See note 2 30253 SID 2 SP Signed 16 See note 3 30254 SID 2 RH Signed 16 See note 4 30255 SID 2 FAN Signed 16 See note 5 30636 SID 98 TE Signed 16 See note 2 30637 SID 98 SP Signed...

Page 9: ...nd KLUFL TE Signed 16 500 1500 50 0 150 0 C RYFL AI1 Signed 16 0 100 0 0 10 0 V PAFL single pulse counting Signed 16 0 999 0 999 Note 3 TEFL SP Signed 16 175 245 17 5 24 5 C TEUFL Uin Signed 16 0 270...