INSTALLATION

Installation and Gas Connection

1.  Place  the  burner  pan  assembly  in  the 

center  of  the  fireplace  floor.  Make  sure 

the front of pan faces forward.

2.  Thread the gas supply fitting to the fire

-

place gas supply pipe. Use thread sealant.

3.  Install adapter fitting onto the burner inlet 

fitting using thread sealant on male threads 

of burner inlet fitting (see Figure 4).

4.  Install the gas connector tube to the gas 

supply fitting. Carefully shape tube to at

-

tach to adapter fitting.

Figure 4 - Connecting Gas to Appliance

Burner Pan Assembly 

(Facing Front of 

Fireplace)

Adapter Fitting

Gas 

Connector 

Tube

CONNECTION TO GAS SUPPLY

  WARNING: A  qualified  ser-

vice person must connect log 

set to gas supply. Follow all 

local codes.

Installation Items Needed

Before installing log set, make sure you have 

the items listed below.
•  piping (check local codes)
•  sealant (resistant to natural gas)
•  equipment shutoff valve
•  test gauge connection
•  adjustable (crescent) wrench or pliers
•  sediment trap
•  tee joint
•  pipe wrench

 CAUTION: Only use a new, 

black  iron  or  steel  pipe.  Inter-

nally-tinned copper tubing may 

be used in certain areas. Check 

your local codes. Use pipe of 

1/2" diameter or greater to allow 

proper gas volume to log set. If 

pipe is too small, loss of pres-

sure will occur.

Installation must include an equipment shut

-

off valve, union, and plugged 1/8" NPT tap. 

Locate NPT tap within reach for test gauge 

hook up. NPT tap must be upstream from log 

set (see Figure 5).

IMPORTANT:

 Install equipment shutoff valve 

in  an  accessible  location.  The  equipment 

shutoff valve is for turning on or shutting off 

the gas to the appliance.

Apply pipe joint sealant lightly to male threads. 

This will prevent excess sealant from going 

into pipe. Excess sealant in pipe could result 

in a clogged burner injector.
Install sediment trap in supply line as shown 

in Figure 5. Locate sediment trap where it is 

within  reach  for  cleaning.  Locate  sediment 

trap  where  trapped  matter  is  not  likely  to 

freeze. A sediment trap traps moisture and 

contaminants. This  keeps  them  from  going 

into log set controls. If sediment trap is not 

installed or is installed incorrectly, log set may 

not run properly.

Figure 5 - Gas Connection

Approved Flexible Gas Hose 

(if allowed by local codes)

CSA Design - Certified 

Equipment Shutoff Valve 

with 1/8" NPT Tap*

3" Minimum

From Gas Meter 

(5" W. C.**

to 10.5" W. C.) 

pressure

Sediment Trap

Cap  Pipe  Tee

 

Nipple  Joint

* Purchase the optional 

CSA  design-certified 

equipment shutoff valve 

from dealer. See 

Acces-

sories

 page 12.

**  Minimum  inlet  pres

-

sure for purpose of input 

adjustment.

Summary of Contents for WAN18N-2

Page 1: ...and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immed...

Page 2: ...ntenance can cause injury or property damage Refer to this manual for correct in stallation and operational procedures For assistance or additional information consult a qualified installer service ag...

Page 3: ...um 13 W C Add 4 when using ON OFF safety pilot valve kit For use if unit is converted to Propane LP gas SAFETY IMPORTANT Read this owner s manualcarefullyandcompletely before trying to assemble op era...

Page 4: ...ing and the burning of manufacturing residues You may wish to add more ventilation by opening a window SAFETY 7 To reduce the creation of soot follow the instructions in Care and Maintenance page 15 8...

Page 5: ...llation must be made by a licensed plumber or gas fitter in the Commonwealth of Mas sachusetts Sellers of unvented propane or natural gas fired supplemental room heaters shall provide to each purchase...

Page 6: ...ied chimney cleaner Creosote will ignite if highly heated Adirtychimneyfluemay createanddistributesootwithin the house Inspect chimney flue for damage NOTICE Installation service and repair of this ap...

Page 7: ...s Supply page 8 Gas line is on the left side If your gas line will be coming into the fireplace from the left side continue with step 2 2 Using a screwdriver remove cover plate on left side of burner...

Page 8: ...ter or greater to allow proper gas volume to log set If pipe is too small loss of pres sure will occur Installation must include an equipment shut off valve union and plugged 1 8 NPT tap Locate NPT ta...

Page 9: ...d 3 Pressurize supply piping system by either using compressed air or opening gas sup ply tank valve 4 Check all joints of gas supply piping sys tem Apply a noncorrosive leak detection fluid to gas jo...

Page 10: ...NING Failure to posi tion the parts in accordance with these diagrams or failure to use only parts specifically approved with this heater may result in property damage or personal injury It is very im...

Page 11: ...uctions If you cannot reach your gas supplier call the fire department C Use only your hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand don t t...

Page 12: ...curing of the logs Ignite a 2 flame and maintain it for 1 hour Burn the logs in consecutive 1 hour periods raising the flame an additional 2 to full flame height for a total of three hours CARE AND M...

Page 13: ...ective Action Log set is smoking soot ing excessively Note It is natural and unavoidable for vented gas log sets to produce moderate levels of car bon soot where flames contact the logs 1 Poor fuel qu...

Page 14: ...alve Gas odor during com bustion 1 Gas leak See Warning statement at top of page 16 1 Locate and correct all leaks see Checking Gas Connec tions page 9 TROUBLESHOOTING REPLACEMENT PARTS Contact author...

Page 15: ...rs 1 WAN300B Hardware Package 1 WAL08 02 1 2 Female x 5 8 Flare Adapter 1 WAL13 01 Damper Clamp 1 ITEM PART DESCRIPTION QTY 1 BL050 01 3 8 Female x 5 8 Flare Adapter 1 2 WAL06 01 Injector Mounting 1 3...

Page 16: ...ller in accordance with all local codes and instructions furnished with the unit WHAT IS NOT COVERED This warranty does not apply to parts that are not in original condition because of normal wear and...

Reviews: