INSTALLATION
Figure 10 - Gas Connection
Figure 9 - Gas Regulator Location and
Gas Line Access Into Stove Cabinet
* Purchase the optional CSA design-certified equipment
shutoff valve from your dealer (see
Accessories
, page 24).
For propane/LP installations, apply pipe
joint sealant lightly to male threads. This will
prevent excess sealant from going into pipe.
Excess sealant in pipe could result in clogged
heater valves.
The installer must supply an external regula-
tor. The external regulator will reduce incom-
ing gas pressure. You must reduce incoming
gas pressure to between 11" and 14" of w.c.
If you do not reduce incoming gas pressure,
heater regulator damage could occur. Install
external regulator with the vent pointing down
as shown in Figure 11. Pointing the vent down
protects it from freezing rain or sleet.
Install sediment trap in supply line as shown
in Figure 10. Place sediment trap where it is
within reach for cleaning. Place sediment trap
where trapped matter is not likely to freeze.
A sediment trap traps moisture and contami-
nants. This keeps them from going into heater
controls. If sediment trap is not installed or is
installed wrong, heater may not run properly.
Figure 11 - External Regulator
with Vent Pointing Down
External
Regulator with
Vent Pointing
Down
Gas Inlet Regulator
Connection
Propane/LP
Supply Tank
Equipment
Shutoff Valve
Ground
Joint Union
3/8" NPT
Pipe Nipple
Tee Joint
Reducer
Bushing to
1/8" NPT
1/8" NPT
Plug Tap
Test Gauge
Connection*
Sediment
Trap
Tee Joint
Pipe Nipple
Gap
3" Minimum
Natural Gas
From Gas Meter
(5" W.C.** to
10.5" W.C.
Pressure)
Propane/LP
From External
Regulator
(11" W.C.**
to 14" W.C.
Pressure)
WARNING: Test all gas piping
and connections for leaks after
installing or servicing. Correct
all leaks at once (see page 13).