OPERATIONS (Continued):
Mode Parameter Settings:
The Futuredesign FDC-L91 temperature controller has been programmed prior to
shipment, so no programming will be necessary. The table below shows the various
controller settings for this unit when properly configured to operate the TYTAN inline
heater.
Parameter
Description Default
Setting
HSP1
Hi Limit Set Point
120 C / 248 F
LSP1
Low Limit Set Point
82 C / 180 F
SP2
Set Point 2 value, for Output 2
10 C / 18 F above”SP0” of the
E5CN Temperature Controller
INPT
Input Type Selection
J_tC
UNIT
Process Unit
C / F
RESO Display
Resolution
NodP
IN.LO
Low Scale for Linear Input
0
IN.HI
High Scale for Linear Input
100 C / 212 F
SHlF
PV Shift (offset) Value
0
FILT
PV Filter Time Constant
2
OUT1
Output 1 Function
HI
O1.HY
Output Hysteresis Value
0.1
HSP.L
Lower Limit of HSP1
0
HSP.H
Upper Limit of HSP1
150 C / 302 F
LSP.L
Lower Limit of LSP1
0
LSP.H
Upper Limit of LSP1
120 C / 248 F
OUT2
Output 2 Function
ALA
ADDR
Address Assgnmnt of Digital Com
Not used
BAUD
Baud Rate of Digital Com
Not Used
PARI
Parity Bit of Digital Com
Not Used
AL.FN Alarm
Function
PYLA
AL.MD Alarm
Mode
Norm
AL.HY Alarm
Hysteresis
0.1
AL.FT
Alarm Failure Transfer
ON
EIFN
Event Input Function
0
DISP
Normal Display Format
PV
Table 8: Future Design L91 Parameters
M-45-02
TYTAN Manual
Revision - Date: 01 – 11/16/07
40