Pro1 Technologies T855iSH Installation Manual Download Page 8

30

31

32

29

Technician Setup Menu

Technician Setup Menu

Tech Setup Steps

Adjustment Options

Default

LCD Will Show

You can configure the D terminal 

as Normally-Open or 

Normally-Closed. 

NO = Normally Open

NC = Normally Closed 

 

Summer Away Mode protects the 

home in unoccupied long periods 

of time, during hot and humid 

weather.  This is done by main-

taining programmed and desired 

humidity and temperature set-

tings.  Summer Away Mode will 

show in the text field and allows 

the thermostat to put the pro-

grammed set point and humidity 

level in a permanent HOLD when 

this setting is enabled (HOLD will 

have  to  be  manually  removed).                                                                                                                            

Dehumidity tech setting must be 

ON for this feature to be available.  

Cycle Minimizer is turned ON 

when Summer Away Mode is ac-

tivated by the user (usually cycle 

minimizer is based on Unoccupied 

and Leave time periods).

Adds another Tech Setting: 

following this one

Dehumidify 

Relay 

(Only shows if 

dehumidify is set 

to “ON”)

Use the or key to select NO 

or NC. If NO is selected D will 

energize to dehumidify. 

If NC is selected D will be 

normally energized. D will 

de-energize to dehumidify. 

 

 

DHM RELAY O/C

Use the        and         

buttons  to  select  ON/OFF.                                                                                 

When ON is selected, 

Summer Away Mode is 

activated by pressing and 

holding the “HOLD” key on 

the thermostat screen, for 3 

seconds.

OFF

OF

NO

SUMMER AWAY

This feature will adjust the 

indoor humidity as the outdoor 

temperature changes.  When 

OFF is selected, the humidity 

will constantly stay at the same 

percentage.  When ON is selected, 

the indoor humidity will fluctuate 

based on outdoor temperature.

 

Use the         and         buttons 

to  select  OFF,  ON  1  or  ON  2.                                                          

When ON 1 or ON 2 is 

selected and humidity level 

is adjusted, the thermostat 

will revert to the original 

humidity level after four

hours. See Automatic 

Humidity Adjusting chart for 

humidity ranges.

Please see revious page for 

chart.  

OFF

OF

Automatic 

Humidity 

Adjusting

(Only displayed 

if remote sensor 

setting is set to 2 

and humidity is 

turned “ON”)

AUTO HUMIDITY

Summer

Away Mode

(Only displayed 

if dehumidity is 

turned “ON”)

Tech Setup Steps

Adjustment Options

Default

LCD Will Show

The amount of over cooling 

allowed when using A/C to 

remove humidity. This screen is 

only shown when ON is selected 

in the Dehumidify with AC tech 

setup step. 

 

Over Cool 

Limit

 

(Only displayed if 

Dehumidify with 

AC is turned “ON”)

Use the and left and right 

arrows to select the 

maximum number of 

degrees of over cool. 

Options are: 2,3,4,5 

3

OVER COOL LMT

Options for how the HUM 

terminal energizes.

See chart below 

HUM

Terminal

(Only shows if 

humidify is set to 

“ON”)

Use the left and right arrows to 

select one of the four options.

View the HUM terminal chart 

below for an explanation of 

these options. 

1

HUM TERMINAL

1

3

Options for how the DHM 

terminal energizes.

See chart below 

 

Use the left and right arrows 

to select one of the four 

options.

View the DHM M terminal 

chart below for an 

explanation of these 

options. 

1

1

DUM

Terminal

(Only shows if 

dehumidify is 

set to “ON”)

DUM TERMINAL

HUM Terminal

DHM Terminal

OPTIONS

1

2

3

4

HUM terminal energizes when the ambient 

humidity is...

Below the humidity setpoint and heat or 

fan is energized.

Below the humidity setpoint and heat is 

energized.

Below the humidity setpoint. It will also 

energize the fan during a call for humidity. 

Below the humidity setpoint.

OPTIONS

1

2

3

4

DUM terminal energizes when the ambient 

humidity is...

Above the humidity setpoint and cool or fan 

is energized.

Above the humidity setpoint. It will also 

energize the fan during a call for dehumidity.

Above the humidity setpoint. 

Above the humidity setpoint and the 

compressor is not running.

Technician Setup Menu

Automatic Humidity Adjusting Index

When The Outdoor Temperature Is: 

On 2

> +40˚F

+30˚F to 40˚F

 

+20˚F to 29˚F

50%

On 1

45%

+10˚F to 19˚F

0˚F to 9˚F

-1˚F to -10˚F

-11˚F to -20˚F

<-20

45%

40%

40%

35%

35%

30%

30%

25%

25%

20%

20%

15%

15%

10%

This table references different humidity levels the thermostat will 

conform to, based on the outdoor temperature measurements.  

When the Automatic Humidity Adjusting tech setting selection 

is ON1 or ON2, the thermostat humidity will stay adjusted to 

the humidity level that correspond to the outdoor temperature 

based on the chart index below.

Technician Setup Menu

Tech Setup Steps

Adjustment Options

Default

LCD Will Show

This feature adds humidity when 

system key is in HEAT. 

Humidify

Use the          and           key to 

turn on or off. If ON is selected 

the humidity will be displayed 

on the main screen and HUM 

terminal will energize when 

humidity setpoint is above 

ambient humidity in Heat 

mode. 

OFF

HUMIDIFY

OF

This feature removes humidity 

when system key is in COOL. 

Dehumidify

Use the          and           key to 

turn on or off. If ON is selected 

the humidity will be displayed 

on the main screen and DUM 

terminal will energize when 

humidity setpoint is below 

ambient humidity in Cool 

mode. 

DEHUMIDIFY

OF

OFF

This feature forces the A/C to run 

longer to remove humidity when 

needed. The A/C will “over cool” 

the room a few degrees until 

humidity reaches the desired 

setpoint. The numbers below 

are the maximum number of 

degrees the thermostat will 

overcool to satisfy humidity.  For 

example, If temperature set point 

is 70 and humidity set point is 

50 and swing is 1 degree and 

“Dehumidify with AC” is set to 

3 and the ambient is 68 and 

indoor humidity is 60 … the 

thermostat will continue to run 

air conditioning until 67 degree 

to try to satisfy the humidity set 

point of 50

Dehumidify

With AC 

(Only shows if 

dehumidify is set 

to “ON”)

DEHUMIDIFY AC

0F

0FF

Use the         and         buttons 

to select Off, 2, 3, 4, 5 

If selected a number is 

selected the thermostat will 

use the air condition to “over 

cool” to control humidity in 

Cool mode. If Off is selected 

the system will not use over 

cooling. 

This feature allows the installer 

to change the calibration of the 

ambient humidity displayed. 

Humidity 

Calibration

(Only shows 

if Humidify or 

Dehumidify is set 

to “ON”)

Use the left and right arrows 

to adjust the calib/-3.  

Each one unit of adjustment 

amounts to approximately 5%. 

 

O

HUMIDITY CAL

OF

Summary of Contents for T855iSH

Page 1: ...all 4 Wires should be pushed into the wall Installation Tips The thermostat should be installed approximately 4 to 5 feet above the floor Select an area with average temperature and good air circulati...

Page 2: ...e the bevel on lower ridge Day of theWeek Setpoint Indicator Displays the user selectable setpoint temperature Energy Efficient Globe Indicates the setpoint temperature chosen is a efficient choice In...

Page 3: ...gency heat relay a jumper can be installed between E and W2 to turn thermostat into a single stage control for Emergency Heat Operation 9 10 11 12 Wiring Diagrams Wiring Diagrams Typical2H 2CSystem 1T...

Page 4: ...nd stage will turn on at 2x the swing setting The second stage will turn off when 1x the swing is reached For example if the swing setting is 5 degrees for heating and the thermostat is set at 70 F th...

Page 5: ...pump applications OF DUAL FUEL Use the and buttons to select ON OFF SET STAGES 2H2C PROGRAM 7d 4 TIME PERIODS PRO RECOVERY This setting maximizes efficiency and equipment longevity by increasing the h...

Page 6: ...iods is set to 2C or 4C Use the and buttons to adjust Pre Occupancy Fan Youcanselectthe pre occupancyfanfromOFF 1 2 or3hours If1 2 or3 isselected thefanwillturn onthatmanyhourspriorto thescheduledoccu...

Page 7: ...lect OFF 10 15 20 25 30 35 40 45 50 degrees OFF BALANCE POINT OF Balance point with electric auxiliary will optimize heat pump usage When the outdoor temperature is above the AUX CUT OUT selection the...

Page 8: ...an explanation of these options 1 1 DUM Terminal Onlyshowsif dehumidifyis setto ON DUM TERMINAL HUM Terminal DHM Terminal OPTIONS 1 2 3 4 HUM terminal energizes when the ambient humidity is Below the...

Page 9: ...64 6 65 4 66 4 67 4 68 2 68 2 68 9 69 2 65 3 66 2 67 2 68 2 69 1 69 1 70 70 1 66 67 68 69 70 70 71 71 67 2 68 2 69 1 70 1 71 1 71 4 72 4 72 6 68 3 69 3 70 3 71 3 72 3 72 8 73 8 74 3 69 7 70 7 71 7 72...

Page 10: ...ng 1 Select HEAT or COOL with the SYSTEM key Note You have to program heat and cool each separately 2 Press the MENU button If menu does not appear first press RUN SCHED 3 Press SET SCHED Note Monday...

Page 11: ...F 17 C 70 F 21 C 62 F 17 C 78 F 24 C 85 F 28 C 78 F 24 C 82 F 26 C 78 F 24 C 85 F 28 C 78 F 24 C 82 F 26 C 78 F 24 C 85 F 28 C 78 F 24 C 82 F 26 C Programming Factory Default Program for 2 Time Period...

Page 12: ...g 802 11 B G N Standards 45 46 Specifications Remote Sensor Operation Option 1 Indoor Local Temperature Sensor ON 1 The displayed room temperature will display the average temperature of the thermosta...

Reviews: