Pro1 Technologies T855iSH Installation Manual Download Page 4

Technician Setup Menu

Technician Setup Menu

14

15

16

13

This feature allows the installer 

to change the calibration of the 

room temperature display. For 

example, if the thermostat reads 

70˚ and you would like it to read 

72˚ then 2.

OFF

This feature will flash a reminder 

after the elapsed run time to 

remind the user to change the 

filter. A setting of  “OFF” will 

disable this feature.

Filter Change

Reminder

You can adjust the filter 

change reminder from “OFF” 

to 2000 hours of runtime in 

50 hour increments.

Tech Setup Steps

Room

Temperature

Calibration

0˚F

You can adjust the room 

temperature display to read 

up to 4˚above or below the 

factory calibrated reading.

Adjustment Options

Default

LCD Will Show

FILTER

OF

0

This thermostat has a technician setup menu for easy installer 

configuration. To set up the thermostat for your particular application:

1.  Press the 

MENU

 button.

2.  Press and hold the  

TECH SET

 button for 3 seconds. This 3 

     second delay is designed so that homeowners do not accidentally 

     access the  installer settings.

3. Configure the installer options as desired using the table below.

     Use the             or              keys to change settings and the 

NEXT 

     

or 

PREV

 key to move from one step to another.  

     

Note:

 Only press the 

DONE

 key when you want to exit the 

     Technician Setup options.

4. Press the 

DONE

 key to exit.

Tech Setup Steps

Adjustment Options

Default

LCD Will Show

This setting will select the 

terminal for medium fan speed 

operations.  The selected terminal 

cannot be used for reversing valve 

operations when heat pump is 

enabled. 

Use the         and         buttons to 

select O/B terminals.

0

0

The swing setting often called 

“cycle rate”, “differential” or

“anticipation” is adjustable. A 

smaller swing setting will cause 

more frequent cycles and a larger 

swing setting will cause fewer 

cycles.

Cooling 

Swing

The cooling swing setting 

is adjustable from 0.2˚ to 

2˚. For example: A swing 

setting of 0.5˚ will turn the 

cooling on at approximately 

0.5˚ above the setpoint 

and turn the cooling off at 

approximately 0.5˚ below 

the setpoint.

The swing setting often called 

“cycle rate”, “differential”, or 

“anticipation” is adjustable. A 

smaller swing setting will cause 

more frequent cycles and a larger 

swing setting will cause fewer 

cycles.

Heating 

Swing

0.5

0.5˚

The heating swing setting is 

adjustable from 0.2˚ to 2˚. 

For example: A swing setting 

of 0.5˚ will turn the heating 

on at approximately 0.5˚ 

below the setpoint and turn 

the heating off at 0.5˚ above 

the setpoint.

0.4˚

0.4

Swing Setting Tip

The second stage will turn on at 2x the swing setting.  The second stage will 

turn off when 1x the swing is reached. For example, if the swing setting is .5 

degrees for heating and the thermostat is set at 70

˚

F, the first stage will turn 

on at approximately 69.5

˚

F.  The second stage will turn on at 69

˚

F. The second 

stage will turn off at 69.5

˚

F and the first will turn off at 70.5

˚

F.  If the third 

stage is used, it will turn on at 68.5

˚

F and turn off at approximately 69

˚

F.

COOL SWING

HEAT SWING

MED FAN TERM

CALIBRATE

PTAC Mode

This setting allows the thermostat 

to operate a PTAC. This will allow 

for multiple fan speeds selectable 

in the next two tech settings.

Use the         and         buttons to 

select ON/OFF.

OFF

OF

PTAC MODE

This setting allows you to choose 

the number of fan speeds the 

thermostat will control.  

G = Low Speed Fan

B/O = Medieum Speed Fan

Y2 = High Speed Fan

PTAC Fan

Speeds

(Only displayed 

if PTAC mode is 

“ON”) 

2

2

FAN SPEEDS

When turned on the thermostat 

will operate a heat pump.  EM. 

Heat will show as an option in the 

system switch tech setting.  

Use the         and         button to 

adjust.  

Heat Pump

OFF configures the 

thermostat for conventional 

systems. 

ON configures the 

thermostat for heat pump 

systems.

OFF

OF

HEAT PUMP

Use the         and         buttons to 

select , 2 or 3.

1. Speeds: ON, Auto

2. Speeds: Low, High, Auto

3. Speeds: Low, Med, High, 

Auto

Default Heat Heat Options Cool Default

Cool Options

PTAC (conventional)

PTAC (Heat Pump)

Heat Pump

Conventional

System Mode

1

2

2

2

1

2, 1

5, 4, 3, 2, 1

2, 1

1

1

2

2

1

1

3, 2, 1 

3, 2, 1 

Typical 2H/2C system with 24 VAC Humidifier

Typical 2H/2C system with Dehumidify Terminal

L2

L1

(HOT)

C

R

RC
RH

Y
C

G

W/E

W2

Y2

H

COMPRESSOR

RELAY

HUMIDIFIER

HEAT RELAY

FAN RELAY

HEAT RELAY 2

COMPRESSOR

RELAY 2

RC

RH

Y
C

W/E

G

W2

Y2

D

COMPRESSOR

RELAY

HEAT RELAY

FAN RELAY

HEAT RELAY 2

COMPRESSOR

RELAY 2

DEHUMIDIFIER 

RELAY

L2

L1

(HOT)

C

R

Typical 2H/2C system with Dry Contact Humidifier

RC

RH

Y
C

W/E

G

W2

Y2

H

COMPRESSOR

RELAY

24V RELAY

NORMALLY-OPEN

TERMINALS

HEAT RELAY

FAN RELAY

HEAT RELAY 2

COMPRESSOR

RELAY 2

L2

L1

(HOT)

C

R

DRY CONTACT

HUMIDIFIER

HUM

HUM

Wiring Diagrams

Wiring Diagrams

Power supply

Factory - installed jumper. Remove only when installing on 2 transformer systems.

Use either O or B terminals for changeover valve.

A 24 VAC common connection is required with this thermostat.

If DEHUM relay requires a normally-energized input, set Dehumidify relay to NC 

in Technician Setup.

Typical 5H/3C Heat Pump System

RC
RH

Y
C

W/E

G

W2

Y2

COMPRESSOR

RELAY 1

FAN RELAY

AUXILIARY

HEAT 2

COMPRESSOR

RELAY 2

AUXILIARY

HEAT 1

C

R

L2

L1

(HOT)

O
B

COOL 

CHANGEOVER OR 

COMPRESSOR 3

HEAT 

CHANGEOVER OR 

COMPRESSOR 3

PTAC Medium 

Fan Speed 

Terminal 

(Only displayed 

if PTAC mode is 

ON and PTAC fan 

speeds is set to 3)

Summary of Contents for T855iSH

Page 1: ...all 4 Wires should be pushed into the wall Installation Tips The thermostat should be installed approximately 4 to 5 feet above the floor Select an area with average temperature and good air circulati...

Page 2: ...e the bevel on lower ridge Day of theWeek Setpoint Indicator Displays the user selectable setpoint temperature Energy Efficient Globe Indicates the setpoint temperature chosen is a efficient choice In...

Page 3: ...gency heat relay a jumper can be installed between E and W2 to turn thermostat into a single stage control for Emergency Heat Operation 9 10 11 12 Wiring Diagrams Wiring Diagrams Typical2H 2CSystem 1T...

Page 4: ...nd stage will turn on at 2x the swing setting The second stage will turn off when 1x the swing is reached For example if the swing setting is 5 degrees for heating and the thermostat is set at 70 F th...

Page 5: ...pump applications OF DUAL FUEL Use the and buttons to select ON OFF SET STAGES 2H2C PROGRAM 7d 4 TIME PERIODS PRO RECOVERY This setting maximizes efficiency and equipment longevity by increasing the h...

Page 6: ...iods is set to 2C or 4C Use the and buttons to adjust Pre Occupancy Fan Youcanselectthe pre occupancyfanfromOFF 1 2 or3hours If1 2 or3 isselected thefanwillturn onthatmanyhourspriorto thescheduledoccu...

Page 7: ...lect OFF 10 15 20 25 30 35 40 45 50 degrees OFF BALANCE POINT OF Balance point with electric auxiliary will optimize heat pump usage When the outdoor temperature is above the AUX CUT OUT selection the...

Page 8: ...an explanation of these options 1 1 DUM Terminal Onlyshowsif dehumidifyis setto ON DUM TERMINAL HUM Terminal DHM Terminal OPTIONS 1 2 3 4 HUM terminal energizes when the ambient humidity is Below the...

Page 9: ...64 6 65 4 66 4 67 4 68 2 68 2 68 9 69 2 65 3 66 2 67 2 68 2 69 1 69 1 70 70 1 66 67 68 69 70 70 71 71 67 2 68 2 69 1 70 1 71 1 71 4 72 4 72 6 68 3 69 3 70 3 71 3 72 3 72 8 73 8 74 3 69 7 70 7 71 7 72...

Page 10: ...ng 1 Select HEAT or COOL with the SYSTEM key Note You have to program heat and cool each separately 2 Press the MENU button If menu does not appear first press RUN SCHED 3 Press SET SCHED Note Monday...

Page 11: ...F 17 C 70 F 21 C 62 F 17 C 78 F 24 C 85 F 28 C 78 F 24 C 82 F 26 C 78 F 24 C 85 F 28 C 78 F 24 C 82 F 26 C 78 F 24 C 85 F 28 C 78 F 24 C 82 F 26 C Programming Factory Default Program for 2 Time Period...

Page 12: ...g 802 11 B G N Standards 45 46 Specifications Remote Sensor Operation Option 1 Indoor Local Temperature Sensor ON 1 The displayed room temperature will display the average temperature of the thermosta...

Reviews: