1.

Installation Requirements

• For easier maintenance, operation, and 

improved ventilation, be sure to install the 
ST at least 100 mm [3.94 in.] away from 
adjacent structures and other equipment.

• Be sure that the ambient operation temper-

ature and the ambient humidity are within 
their designated ranges. (Ambient opera-
tion temperature: 0 to 50°C, Ambient 
humidity: 10 to 90%RH, Wet bulb temper-
ature: 39°C max.)

 

When installing the ST on the panel of a cab-
inet or enclosure, “Ambient operation tem-
perature” indicates both the panel face and 
cabinet or enclosure’s internal temperature.

• Be sure that heat from surrounding equip-

ment does not cause the ST to exceed its 
standard operating temperature.

2.

ST Installation

(1) Create a Panel Cut following the dimen-

sions in the table below.

(2) Confirm that the installation gasket is 

attached to the ST unit and then place the 
ST unit into the Panel from the front.

• It is strongly recommended that you 

use the installation gasket, since it 
absorbs vibration in addition to repel-
ling water.

 

For the procedure for replacing the 
installation gasket, refer to “ST3000 
Series Hardware Manual”.

(3) The following figures show the four (4) 

fastener insertion slot locations. Insert 
each fastener’s hook into the slot and 
tighten it with a screwdriver. Insert the 
installation fasteners securely into the 
insertion slot recess.

100
[3.94]

100
[3.94]

100
[3.94]

100
[3.94]

Unit:mm[in.]

100
[3.94]

100
[3.94]

100
[3.94]

Panel Face

Inside Cabinet

X

Y

Panel thickness

118.5 

[4.67

]

92.5 

[3.64

]

1.6[0.06] 

 

to 

 

5.0[0.20]

Unit: mm [in.]

X

Under

 

4-R3[0.12]

Panel 
thickness

ST

Y

+1

-0

+0.04
-0

+1

-0

+0.04
-0

Left Side

Insertion 

Slots

Right Side

Summary of Contents for ST3200 Series

Page 1: ...fully packed with special attention to quality However should you find anything damaged or missing please contact your local ST distributor immediately About the Manual For the detailed information on ST3000 series refer to the following manual ST3000 Series Hardware Manual Maintenance Troubleshooting ST3000 Series Hardware Manual can be selected from the help menu of GP Pro EX or downloaded from ...

Page 2: ...lug type RS232C is supported E Serial Interface COM2 AST3201 A1 D24 has Dsub 9 pin plug type and supports RS422 RS485 1 AST3211 A1 D24 has Dsub 9 pin socket type and supports RS485 MPI only 1 RS485 is compliant with AST 3201A units with revision code C or later Revision page 11 Front A Rear E D B C Bottom LED ST Status Green lit Normal operation power is ON or OFFLINE operation Orange blinking Dur...

Page 3: ...sulation Resistance DC500V 10MΩ min between charging and FG terminals Physical Surrounding Air Temperature 0 to 50 C 1 1 When using in an environment where the temperature becomes or exceeds 40 C for an extended period of time the screen contrast level may decrease from its original level of brightness Storage Temperature 20 to 60 C Ambient Humidity 10 to 90 RH Wet bulb temperature 39 C max no con...

Page 4: ... isolation unit CA3 ISO232 01 on COM1 COM1 Recommended Cable Connector XM2D 0901 made by OMRON Corp Recommended Jack Screw XM2Z 0073 made by OMRON Corp Recommended Cable Cover XM2S 0913 made by OMRON Corp Interfit Bracket 4 40 inch screws are used Pin RS232C Signal Name Meaning 1 CD Carrier Detect 2 RD RXD Receive Data 3 SD TXD Send Data 4 ER DTR Data Terminal Ready 5 SG Signal Ground 6 DR DSR Dat...

Page 5: ...ame Meaning 1 RDA Receive Data A NC 2 RDB Receive Data B NC 3 SDA Send Data A LINE Line 4 ERA Data Terminal Ready A RS RTS Request to Send 5 SG Signal Ground SG Signal Ground 2 2 In COM2 on the AST3211 A1 D24 the SG and FG terminals are isolated 6 CSB Clear to Send B 5V 5V External Output 3 4 3 The 5V output for Pin 6 is not protected against overcurrent To prevent damage or unit malfunctions use ...

Page 6: ...lation 1 Create a Panel Cut following the dimen sions in the table below 2 Confirm that the installation gasket is attached to the ST unit and then place the ST unit into the Panel from the front It is strongly recommended that you use the installation gasket since it absorbs vibration in addition to repel ling water For the procedure for replacing the installation gasket refer to ST3000 Series Ha...

Page 7: ...nected be sure the wire is grounded 1 Wiring the DC type power supply cable Power Cord Specifications Use copper conductors only Power Connector Plug Specifications The power connector plug is CA5 DCCNM 01 made by Pro face or MSTB2 5 3 ST 5 08 made by Phoenix Contact Insertion Slot Recess Hook the fastener on the Recess Panel Installation Fastener ST Hook and secure the fastener on the panel with ...

Page 8: ...bundled with or kept close to main circuit lines high voltage high current or input output signal lines To reduce noise make the power cord as short as possible If the supplied voltage exceeds the ST unit s range connect a voltage transformer Between the line and the ground be sure to use a low noise power supply If there is an excess amount of noise connect a noise reducing transformer The temper...

Page 9: ...long grounding wire replace the thin wire with a thicker wire and place it in a duct 4 Input Output Signal Line Cautions All ST Input and Output signal lines must be separated from all operating circuit power cables If this is not possible use a shielded cable and ground the shield To prevent the USB cable from coming off Attaching the USB Holder 1 Before starting the procedure lift up the tab on ...

Page 10: ... aware of the following items when building the ST into an end use product The ST unit s rear face is not approved as an enclosure When building the ST unit into an end use product be sure to use an enclosure that satisfies standards as the end use product s overall enclosure The ST unit must be used indoors only Install and operate the ST with its front panel facing outwards If the ST is mounted ...

Page 11: ...n 8 2 52 Nanko higashi Suminoe ku Osaka 559 0031 JAPAN TEL 81 0 6 6613 3116 FAX 81 0 6 6613 5888 http www pro face com Copyright 2006 Digital Electronics Corporation All rights reserved 085886B AST3200 MT01E BTH 2007 7 SS F Inquiry Do you have any questions about difficulties with this product Please access our site anytime that you need help with a solution http www pro face com otasuke Please be...