5
Wiring
*1
Suggested Ring Terminal: V2-MS3 (made by JST Co.)
• When connecting a wire to the GP's FG terminal, be sure the wire
is grounded. Not grounding the wire will result in excessive
noise.
• To avoid a short caused by loose ring terminals, be sure to use
ring terminals with an insulating sleeve.
• Wherever possible, use thick wires (max. 2 mm
2
) for power terminals, and twist
the wire ends before attaching the ring terminals.
• Be sure to use the following size ring terminals.
*1
Under
6.0mm (0.24in.)
Over
φ
φ
φ
φ
φ
3.2mm (0.13in.)
Rear of GP
Ring Terminals
*1
Power Input
Terminal Block
+ - FG
F G
-
+
• To avoid an electric shock, check first that the GP's power
supply is completely turned OFF, via a breaker, or similar unit
when connecting the GP power cord terminals to the power
terminal block.
• GP-37W2B Series units are designed to use only DC24V in-
put. Any other power level can damage both the GP and the
power supply.
• The GP-37W2B is not equipped with a power switch, there-
fore, you need to use a breaker switch.
WARNINGS
WARNINGS