When connecting the GP2000H Series units to a Serial I/F, DC24V I/F, or External
I/F, be sure to use the Digital Electronics Corporation's GP2000H Series option
cables.

9

Wiring

 To avoid an electric shock, prior to connecting the GP's power cord

terminals to the power terminal block, confirm that the GP's power
supply is completely turned OFF, via a breaker, or similar unit.

 The GP2000H Series units are designed to use only DC24V input.

Any other power level can damage both the GP and the power
supply.

 Since there is no power switch on the GP unit, be sure to attach a

breaker-type switch to its power cord.

        

WARNINGS

Digital's option cables are as follows.

Cable Name

Model Number

RS-232C DSUB Connector 3m Cable

GP2000H-D232-3M

RS-232C DSUB Connector 10m Cable GP2000H-D232-10M
RS-232C 3m Cable

GP2000H-C232-3M

RS-232C 10m Cable

GP2000H-C232-10M

RS-422 DSUB Connector 3m Cable

GP2000H-D422-3M

RS-422 DSUB Connector 10m Cable

GP2000H-D422-10M

RS-422 3m Cable

GP2000H-C422-3M

RS-422 10m Cable

GP2000H-C422-10M

8

Emergency Switch Guard

Emergency Switch Guard

„

„

„

„

„

 Emergency Switch Guard

This guard is used to prevent the accidental pressing of the Emergency Stop Switch
when the GP2000H unit is placed face down on a table, or is accidentally dropped.
This unit is factory equipped with two (2) Emergency Switch Guard Hole Covers
(Seals).

For guard attachment details, refer to

 GP2000H Series User Manual

Summary of Contents for GP2301H-LG41-24V

Page 1: ...esignsshouldbeusedtoensuretheproperdegreeofreliability andsafety AftertheGP sbacklightburnsout unliketheGP s StandbyMode thetouchpanelisstillactive If theoperatorfailstonoticethatthebacklightisburnedoutandtouchesthepanel apotentially dangerousmachinemiss operationcanoccur Therefore donotuseGPtouchswitchesforthe controlofanyequipmentsafetymechanisms suchasEmergencyStopswitches etc thatprotect human...

Page 2: ...thetouchpanelwithahardorpointedobject orpressonthetouchpanelwith toomuchforce sinceitmaydamagethetouchpanelorthedisplay DonotinstalltheGPwheretheambienttemperaturecanexceedtheallowedrange Doingso maycausetheGPto malfunctionorshortenitsoperationlife DonotrestrictorlimittheGP snaturallyoccurringrear faceventilation orstoringorusingthe GPinanenvironmentthatistoohot Donotusethisunitinareaswherelarge s...

Page 3: ...Approval The GP2301H LG41 24V GP2301H SC41 24V GP2401H TC41 24V are UL c UL CSA listed products UL File No E171486 UL60950 The GP components conform to the following standards UL60950 Third Edition Safety of Information Technology Equipment CAN CSA C22 2 No 60950 00 Safety of Information Technology Equipment GP2301H LG41 24V UL Registration Model 3080028 03 GP2301H SC41 24V UL Registration Model 3...

Page 4: ...hould you find anything damaged or missing please contact your local GP distributor immediately GP Unit 1 GP2301H LG41 24V GP2301H SC41 24V Installation Guide 1 This Guide Package Contents Hand Strap 1 Emergency Switch Guard 1 GP2401H TC41 24V CF Card Interface Guard 1 GP2301H LG41 24V GP2301H SC41 24V GP2401H TC41 24V Emergency Switch Guard Attachment Screws 2 CF Card Interface Guard Attachment S...

Page 5: ... C Status LED 1 Part Names LED GP Status Not Lit Power is OFF Green Normal operation Orange Backlight is not functioning Refer to 13 Changing the Backlight I L Rear Face A B C Front Face GP 2401H with CF Card Cover open D H F Q J M K E LED GP Status Green Indicates the Operation Switch or the 3 Position Enable Switch are ON 1 Not Lit If the unit status is other than the above conditions and GP H70...

Page 6: ...ols CF Card access Reserved ON Allows CF Card access OFF Does not allow CF Card access Dip Switches Factory Settings Before removing the CF Card confirm that the CF Card Ac cess Switch is turned OFF and the CF Card Access LED is not lit If the switch is ON or the LED is lit removal of the CF Card may result in data loss The CF Card Access Switches are located inside the rear face CF Card Cover on ...

Page 7: ...up Switches The CF Card Startup Switches are located inside the rear face CF Card Cover just below the CF Card insertion slot Termination Resistance Switch When you need to set the GP unit s termination resistance this dip switch is used It is located next to the External Output Interface Connector Setting it to ON will insert 100Ω of resistance The factory setting is OFF DC24V I F Connector Seria...

Page 8: ...is for DC24V input Since Pin 7 s VCC DC5V output is unprotected be sure to keep the output current within the rated range This unit s serial port is not isolated therefore it is important that you connect the SG 8 terminals If this is not done the RS422 circuit may be damaged This interface is used to connect the GP to the host PLC via an RS 232C or RS 422 cable The connector is located inside the...

Page 9: ...3 Position Enable switch 0A A contact Rated DC24V 300mA min applicable load DC24V 4mA 17 ENB1B 3 Position Enable switch 1B A contact 18 ENB1A 3 Position Enable switch 1A A contact Rated DC24V 300mA min applicable load DC24V 4mA External Output I F 7 DOUT GND is common for 2 DOUT0 C 4 DOUT1 C and 8 BUZZ OUT When using GP H70 compatible mode 17 ENB1B and 18 ENB1A cannot be used CF Card Interface Thi...

Page 10: ...Mounting Interface physical specification designed by VESA for attachment of a display to either an arm or stand 7 CF Card Interface Guard CF Card Interface Guard When the GP unit s CF Card Interface Guard is attached to the GP unit the GP meets NEMA 250 TYPE4X 12 environment requirements Even if the CF Card Interface Guard is not attached if the CF Card Cover is closed the unit s protection level...

Page 11: ...power cord WARNINGS Digital s option cables are as follows Cable Name Model Number RS 232C DSUB Connector 3m Cable GP2000H D232 3M RS 232C DSUB Connector 10m Cable GP2000H D232 10M RS 232C 3m Cable GP2000H C232 3M RS 232C 10m Cable GP2000H C232 10M RS 422 DSUB Connector 3m Cable GP2000H D422 3M RS 422 DSUB Connector 10m Cable GP2000H D422 10M RS 422 3m Cable GP2000H C422 3M RS 422 10m Cable GP2000...

Page 12: ...e GP unit Connect a surge absorber to handle power surges To reduce noise make the power cord as short as possible 1 Use a grounding resistance of 100Ω a wire of 2mm2 or thicker or your country s applicable standard All GP Input and Output signal lines must be separated from all operating circuit power cables If this is not possible use a shielded cable and ground the shield 13 Backlight Replacmen...

Reviews: