2.4 Transfer cable
To transfer screen data to GP-4301T/TW, use a USB transfer cable or Ethernet.
The USB cables that can be used for GP-4301T/TW are as follows:
Model
Connector Type
Connector on GP
Options
CA3-USBCB-01
USB (Type A)
ZC9USCBMB1
USB (Type mini B)
Commercial Item
-
Please note that the cables (GPW-CB02, GPW-CB03, GP430-CU02-M) for GP-2300
series cannot be used for GP-4301T/TW.
2.5 Interface
2.5.1 Serial Interface
The pin assignment and the shape of plug/socket connector of GP-2300 series are
different from those of GP-4301T/TW.
To know the details about them, see [
4.2 Shapes of COM ports
] and [
4.3 Signals of
COM ports
].
Because of it, the existing PLC connection cables cannot be used as they are. If you
use the existing connection cables for GP-4301T/TW, see [
4.6 Cable Diagram at
the time of replacement
].
And even though the both COM1 and COM2 ports on GP-2300T/S/L are used with
RS-232C setting, only the COM1 port can be used for GP-4301T/TW. In this case,
please contact our sales office in your region.
(
http://www.pro-face.com/customer/contact.html
)