To avoid the possibility of an electric shock, be sure the Power Cord is unplugged
from the power outlet prior to connecting the power cord's power terminals to the
GLC.
•
The GLC300-TC41-24V can only use DC24V input. Any other input voltage can
damage the GLC and its power supply.
•
Since the GLC has no power switch, be sure to use a breaker type switch.
•
To prevent a short from occurring when the ring terminals
become loose, be sure to use sleeved ring terminals.
•
When the FG terminal is connected, be sure the wire is
grounded. Not grounding the GLC unit will result in excess
noise and vibration.
•
Wherever possible, use thick wires (max. 2 mm
2
) for power
terminals, and twist the wire ends before attaching the ring terminals.
•
Be sure to use the following size Ring Terminals.
7
Wiring
Under
6.0 mm
Over
φ
3.2 mm
WARNING
*
1
Ring Terminal to use: V2-MS3 (made by JST)
Rear side
-
+
FG
+ - FG
Ring Terminals *1
Power Input
Terminal Block
Connect the power cable following the steps below.
1. Check to make sure the Power is Off.
2. With a plus screwdriver, remove the cover on the Power Input Terminal Block.
3. Disconnect the screws from the 3 terminals to be used, align the wire rings and
re-insert the screws.
(Please make sure the connection of the wires are correct.)
•
The torque necessary for fastening the screws is between 0.5-0.6N
•
m.