The GLC2500-TC41-24V, GLC2600-TC41-24V are UL/c-UL listed
products.(UL File No.E182139)
GLC2500-TC41-24V (UL Registration Model : 3280036-03)
GLC2600-TC41-24V (UL Registration Model : 3080021-01)
These products conform to the following standards:
UL508
Industrial Control Equipment
UL1604
Electrical Equipment for Use in Class I and II Division 2 and Class III
Hazardous(Classified) locations
CAN/CSA-C22.2,No.1010-1 (c-UL Approval)
Safety Requirements for Electrical Equipment for Measurement, Control and
Laboratory use
<Cautions>
Be aware of the following items when building the GLC into an end-use prod-
uct:
• The GLC unit’s rear face is not approved as an enclosure. When building the
GLC unit into an end-use product, be sure to use an enclosure that satisfies
standards as the end-use product’s overall enclosure.
• The GLC unit must be used indoors only.
• Install and operate the GLC with its front panel facing outwards.
• If the GLC is mounted so as to cool itself naturally, be sure to install it in a
vertical panel. Also, insure that the GLC is mounted at least 100 mm away
from any other adjacent structures or machine parts. If these conditions are
not met, the heat generated by the GLC unit’s internal components may cause
it to fail to meet UL standards.
UL1604 Conditions of Acceptability and Handling Cautions:
1. Power, input and output (I/O) wiring must all be in accordance with Class I,
Division 2 wiring methods, Article 501-4 (b) of the National Electrical Code,
NFPA 70, or as specified in Section 18-152 of the Canadian Electrical Code
for units installed within Canada, and in accordance with that location's au-
thority.
2. Suitable for use in Class I, Division 2, Groups A, B, C and D hazardous loca-
tion, or nonhazardous locations only.
3. WARNING: Explosion hazard - substitution of components may impair suit-
ability for Class I, Division 2.
4. WARNING: Explosion hazard - do not disconnect equipment unless power
has been switched off or the area is known to be nonhazardous.
5. WARNING: Explosion hazard - when in hazardous locations, turn off power
before replacing or wiring modules.