• From the FG terminal at the rear side of GLC unit, be sure to use exclu-
sive type grounding (resistance of less than 100
Ω
).
• GLC input and Output signal lines must be separated from the power
control cables used for any and all operation circuits.
• If this is not possible, use a shielded, grounded cable.
• Before changing the Backlight, be sure the power cord has been discon-
nected from the power supply
• While the unit is still hot, be sure to use gloves to prevent burns.
• Do not touch the backlight area while the unit is still ON, since high voltage
runs through that area.
• When the GLC's power cord has just been unplugged, the unit is still very
hot. Be careful not to be burned.
• Check that you have the proper Backlight for your specific GLC-
100 model.
• When attaching an option unit to the GLC, be sure to follow the option
unit's operation instructions.
GLC
Backlight Model
GLC100-LG**
GLC100-SC**
GP370-BL00-MS
When changing the backlight, be sure to wear gloves and use the fol-
lowing steps.
1. Unplug the GLC's power cord from the power supply.
2. Detach the power cord from the GLC. (A)
3. With a screwdriver, unfasten the two screws on the top face of the
unit. Press down the top center section to confirm that the cover's
catch is released. (B)
4. Insert a screwdriver into the hole at the side of the unit.Then, hold the
GLC with one hand and turn the screwdriver to open up the unit from the
top. (C)
5. Unplug the Backlight's connector. Do not shift or remove the GLC's inter-
nal pad while pulling out the backlight. (D,E)
6
Grounding Precautions
7
Input/Output Signal Line Precautions
8
Replacing the Backlight
WARNING