Cut a hole in the panel, and install the GLC into the panel's front face.
Attach the Installation Fasteners from the inside of the panel.
Tighten all installation fasteners with a screwdriver.
To create a waterproof seal, a force of 0.5-0.6N•m is required.
Panel
GLC unit
6
7
Under 4-R3
1.6 mm to 5 mm
Panel thickness
Unit: mm
Tightening the screws with too much force can damage the GLC.
156
123.5
Rear of GLC
Gasket
Before installing the GLC, be sure that the moisture resistant
gasket is attached securely to the unit.
4
Installation
Be sure to connect this unit’s SG/GND (Signal Ground) terminal
to the other unit’s Signal Ground terminal. If necessary, you may
also need to connect the FG terminal to the other unit’s FG ter-
minal depending on the type of the other unit you use.
This unit’s RS-485(RS-422) Port is not isolated, therefore, it is
crucial that you connect the SG/GND (Signal Ground) terminals.
If this is not done, the RS-485(RS-422) circuit may be damaged.
+ 1
- 0
+1 -0