5.

Return Therma-Fuser diffusers to operating
condition by pushing the balancing lever down until
it latches.

6.

Return the remainder of the system to operating
condition.

ADJUSTING MINIMUM FLOW 

Turn dial until desired minimum flow on the scale 
intersects with the lower metal piece. See Fig. 5

ADJUSTING TEMPERATURE 

SETPOINTS 

The STR Therma-Fuser diffuser is factory set at 
74°F/23°C. Because heat loads in various rooms diff er 
and individual occupants prefer different temperatures, 
it is recommended that the thermostat not be adjusted 
until after a few days of operation. 

Room temperature setpoints for heating and cooling 
are separately adjusted by turning the heating and 
cooling thumbwheels. Align the outside of each 
thumbwheel with its respective temperature scale. See 
Fig. 6. Each setpoint can be anywhere between 70° 
and 78°F/21° and 25°C. Both are factory set at 
74°F/23°C. (The model STR-C has only one 
thumbwheel). 

If the cooling thumbwheel is tight when the room is 
cool, continue to turn the thumbwheel and pull the 
changeover close rod outward to relieve the tightness. 
See Fig. 6

RECOMMENDED ADJUSTMENTS FOR VARIOUS 
CONDITIONS 

Room 

Temp. 

Disc 

Position 

Recommended 

Action 

Open 

Adjust cooling for higher room 
temperature set point. (Turn cooling 
thumbwheel out.) 

Too 

Cold 

Closed 

Therma-Fuser diffuser is correct. 
Check if cooling is still required, and if 
not, turn cooling unit off. 

Open 

Therma-Fuser diffuser is correct. 
Check for lack of air or for too warm 
air temperature. 

Cooling 

Mode 

STR-C 

STR-HC 

Too 

Warm 

Closed 

Adjust cooling for lower room 
temperature set point. (Turn cooling 
thumbwheel in.) 

Open 

Therma-Fuser diffuser is correct. 
Check for lack of air or too low air 
temperature. 

Too 

Cold 

Closed 

Adjust heating for higher room 
temperature set point. (Turn heating 
thumbwheel out.) 

Open 

Adjust heating for lower room 
temperature set point. (Turn heating 
thumbwheel in.) 

Heating 

Mode 

STR-HC 

Too 

Warm 

Closed 

Therma-Fuser diffuser is correct. 
Check if heating is still required, and if 
not, turn it off. 

Too 

Noisy 

STR-C 

STR-HC 

Any 

Any 

Reduce static pressure. 
Recommended static pres- 
sure is .05 to .25 wg / 10 to 62 Pa at 
the inlet of the diffuser. If lower noise 
level does not result from lower static 
pressure, check for and correct noise 
generating restrictions in the duct up 
stream such as large pressure drops 
over dampers, heaters, etc. 

MAINTENANCE 

The moving parts of the STR Therma-Fuser diffuser 
have no maintenance or lubrication requirements. We 
are often asked to recommend periodic maintenance 
procedures and a spare parts stock. Recommended 
maintenance is to clean the outer surfaces of the 
Therma-Fuser diffuser—nothing else. We do not 
recommend stocking any spare parts. Our customers 
also confirm that stocking is unnecessary. 

CONTROLLING THE SYSTEM 

References: 

System Design, STR brochure, Form 046.101.

Chapters 2.2, 3.1 and 3.2, pp 6, 7 and 8, Designing
Modular VAV Systems Form 5.2.