background image

Recommended

Action

Adjust cooling for higher room temperature set point. 

(Turn cooling thumbwheel out.)
Therma-Fuser diffuser is correct. Check if cooling is 

still required, and if not, turn cooling unit off.
Therma-Fuser diffuser is correct. Check for lack of 

air or for too warm air temperature.
Adjust cooling for lower room temperature set point. 

(Turn cooling thumbwheel in.)
Therma-Fuser diffuser is correct. Check for lack of 

air or too low air temperature.
Adjust heating for higher room temperature set point. 

(Turn heating thumbwheel out.)
Adjust heating for lower room temperature set point. 

(Turn heating thumbwheel in.)
Therma-Fuser diffuser is correct. Check if heating is 

still required, and if not, turn it off.
Reduce static pressure. Recommended static pres-

sure is .05 to .25 wg / 10 to 62 Pa at the inlet of the 

diffuser. If lower noise level does not result from 

lower static pressure, check for and correct noise 

generating restrictions in the duct up stream such as 

large pressure drops over dampers, heaters, etc. 

Disc

Position

Open

Closed

Open

Closed

Open

Closed

Open

Closed

Any

Room

Temp.

Too

Cold

Too

Warm

Too

Cold

Too

Warm

Any

Cooling

Mode

ST-C

ST-HC

Heating

Mode

ST-HC

Too

Noisy

ST-C

ST-HC

Page 3

MAINTENANCE

The moving parts of the ST Therma-Fuser diffuser have no 

maintenance or lubrication requirements. We are often asked 

to recommend periodic maintenance procedures and a spare 

parts stock. Recommended maintenance is to clean the outer 

surfaces of the Therma-Fuser diffuser—nothing else. We do 

not recommend stocking any spare parts. Our customers 

also confirm that stocking is unnecessary.

CONTROLLING THE SYSTEM

References:
• System Design, p 4, ST brochure, Form 10.1.
• Chapters 2.2, 3.1 and 3.2, pp 6, 7 and 8, Designing Modu-

lar VAV Systems, Form 5.2.

• Air Handling and Fan Coil Units Subzoned with Therma-

Fuser VAV modules, Form 6.7.

• DX Equipment Zoned with Therma-Fuser VAV Modules,

Form 6.5.

SUPPLY AIR TEMPERATURE

The sources of cooling and heating are controlled from 

supply air temperature. As with all VAV systems, the goals 

are to achieve a constant supply air temperature (may be 

reset to another 

constant

 supply air temperature) and to limit 

the supply air temperature. Limits for supply air temperature 

should be between 50°F/10°C and 68°F/20°C when cooling 

and between 80°F/26.5°C and 120°F/49°C when heating. The 

heating temperature limit should be as low as possible. These 

objectives are best achieved by modulating chilled water 

valves, hot water valves and other variable equipment from 

supply air temperature. On/off equipment such as DX 

compressors and electric heat are cycled from supply air 

temperature. Use a discharge air sensor for the supply air 

temperature signal.
Mode change between heating, recirculation and cooling is 

controlled from room temperature. Signals from one or more 

room temperature sensors may be used for mode change. 

When using more than one sensor, either a “majority rules” or 

a “cooling dominant” approach is recommended.

STATIC PRESSURE

As with all VAV systems, the fan must run continuously dur-

ing occupied times. Goals of static pressure control are to 

provide enough static pressure to obtain the required air vol-

ume especially at the diffuser farthest from the fan, to avoid 

diffuser noise by limiting static pressure at both full flow and 

turndown and to provide pressure independence or consistent 

operation as the system flow changes.
These objectives can be achieved with the usual methods of 

automatic static pressure control: bypass dampers, discharge 

dampers, zone dampers, and fan control (variable speed 

drives, inlet dampers, etc.). Locate the static pressure sensor 

as far down the duct as possible—at least 2/3 down the duct 

from the first takeoff.

ADJUSTING TEMPERATURE 

SETPOINTS

The ST Therma-Fuser diffuser is factory set at 74°F/23°C. 

Because heat loads in various rooms differ and individual 

occupants prefer different temperatures, it is recommended 

that the thermostat not be adjusted until after a few days of 

operation.
Room temperature setpoints for heating and cooling are sep-

arately adjusted by turning the heating and cooling thumb-

wheels. Align the outside of each thumbwheel with its 

respective termperature scale. See

 Fig. 6.

 Each setpoint can 

be anywhere betwee 70° and 78°F/21° and 25°C. 

See Fig. 6.

 

Both are factory set at 74°F/23°C. (The model ST-C has only 

one thumbwheel).
If the cooling thumbwheel is tight when the room is cool, con-

tinue to turn the thumbwheel and pull the changeover close 

rod outward to relieve the tightness. 

See Fig. 6.

Fig. 6 Adjusting Temperature

RECOMMENDED ADJUSTMENTS FOR 

VARIOUS CONDITIONS

21

23

25

21

23 25

°

C

78

74

70

78

74

°

F

70

Cooling (Blue)

Thumbwheel

°C Temperature

Scale

Heating (Red)

Thumbwheel

Changeover

Close Rod

°F Temperature

Scale

Continued on next page

Reviews: