background image

..\Manuals\RCI-200-RFM rev.B.doc 

                                                                                                          Page 7 of 8 

Next, set the 

number of channels of the host

 using SW2-3, -4.  

An RCI-200 can at most have 2 channels.  This is the number of 
channels that will be exchanged between the host and each 
remote. 
 

Remote Configuration:

 

 
To make an RCI-200 operate as a REMOTE unit, make sure that SW2-8 is flipped up. 
 
Next, set the 

number of channels on this remote

 using SW2-1, 

-2.  One channel is considered 1 analog input/output plus 1 
contact input/output. Hence an RCI-200 can have at most 2 
channels. 

 
 
Received Signal Strength Indicator (RSSI) : (Repeater Mode Only)

 

 

The Signal Strength indicator is active in the Repeater Mode only. 

 
The radio communications board has a signal strength indicator to show the level 
of the signal that was received from another radio.  The indicator is a 10 segment 
LED bar graph as shown on the left.  Each segment represents 10% of received 
signal.   At least 50% of signal is required for proper operation of the radios.   
 
The radios have an automatic power adjustment for optimal transmission.  As a 
result the signal strength meter may never reach a full 10-segment count even 
when the two radios are right next to each other. 
 
 
 

SW2-3 

SW2-4 

Channels on Host 

UP UP 

DOWN UP 

SW2-1 

SW2-2 

Channels on Remote 

UP UP 

DOWN UP 

Summary of Contents for Model: RCI-200-RF2

Page 1: ...00 XXX If special or required 24 VDC 2 Dry Contacts and 2 Analog Inputs Input Remote Control Signal Interface XXX SER RS 232 485 Output 2 Form C Contacts and 2 Analog Outputs 117VAC 50 60Hz XXX RF9 90...

Page 2: ...ducts or all non standard products may not be returned for restocking Pribusin Inc warrants equipment of its own manufacture to be free from defects in material and workmanship under normal conditions...

Page 3: ...pread Spectrum Radio Technology Provides Reliable Communication 2 Dry Contact and 2 Analog Inputs 2 C Relay Contacts and 2 Analog Outputs Point to Point or Host to Multipoint Topologies No Calibration...

Page 4: ...ct OR Master Remote 1 2 Analog 2 Contact 2 Analog 2 Contact Remote 2 Remote 3 Master to Multi Remote 2 Analog 2 Contact 2 Analog 2 Contact 2 Analog 2 Contact 2 Analog 2 Contact Page J10 any system 11...

Page 5: ......

Page 6: ......

Page 7: ...a 500mA SLOBLO fuse It can be wired for 240VAC operation by removing de soldering power jumpers J1 J2 and installing soldering jumper J3 When changing the RCI 200 to 240VAC power make sure to change t...

Page 8: ...inputs are connected to the RCI 200 in two fashions 1 Normal 3 wire connection or 2 two wire connection On a 3 wire connected input an external power supply or the 24V power output terminal of the RCI...

Page 9: ...or from the inputs Care must be taken when connecting the outputs to different devices so that no inadvertent ground loops are established Output Calibration Input Testing The outputs on the RCI 200 a...

Page 10: ...communications failure occurs If H1 3 IN then analog output 1 will ramp to the setting of K1 and analog output 2 will ramp to the setting of K2 Both outputs will change at a rate determined by the set...

Page 11: ...In addition there are two types of Topologies that can be configured 1 Point to Point and 2 Host to Multipoint In a Point to Point topology one host communicates with one remote The two exchange all t...

Page 12: ...the Standard mode of operation unless a repeater is required in your system Host Configuration To make an RCI 200 operate as a host unit make sure that SW2 8 is flipped down Next set the number of re...

Page 13: ...al Strength Indicator RSSI Repeater Mode Only The Signal Strength indicator is active in the Repeater Mode only The radio communications board has a signal strength indicator to show the level of the...

Page 14: ...n This means that there are no obstructions between the host antenna and each of the remote antennas This may require the antenna to be raised on a mast with some low loss coaxial cable being installe...