Function:

The IUC-7X-WTX is a new & improved model of its prior
version.

It uses a microprocessor to compute

instantaneous voltage and current values which it then
uses to produce one of four different outputs. These
are: 1) Watt, 2) VA, 3) VAR and 4) Power Factor.

An optional Watt Hour counter output is also available to
count watt hours consumed. The IUC-7X-WTX comes
in single (-WT1) or double (-WT2) element versions for
1, 2 or 3 phase systems.

Watts = V

x I

VA = V

x I

VAR =

VA - Watt

Power Factor =

Calibration:

No calibration is required on these watts transducers.
There is a zero and span adjustment for the output
signal for output calibration. Standard calibrations are
for 500 Watts (WT1) and 1000 Watts (WT2).

Standard Features:

Selectable Output for Watt, VA, VAR or Power Factor

High Input-Output-Power Isolation (1500VAC Test)

Single or Double Element for 1 and 3 Phase Circuits

Industry Standard Output: 4-20 mA, 1-5 VDC, more

Optional Watt Hour Counter & Watt Display

Microprocessor Controlled for High Accuracy even
with Distorted Waveforms (SCR switching etc.)

Less than 1VA Burden on Voltage and Current Coils

0-5 AAC Current, 0-150 VAC Voltage Input

Standard Calibrations: 500 Watts (WT1),

1000 Watts (WT2)

Easy Field Adjustable Output Calibration

Power: 117 VAC 50/60 Hz

High Noise Rejection

CSA and NRTL Approved (LR 51078)

Specifications:

Isolation: Input to Output to Power 1500 VAC (test)
Maximum Coil Ratings: Current: 15A Continuous

100A 3 sec/Hr.

Voltage: 150% of Rated Voltage

Accuracy/Lin/- 0.4% max., +/- 0.2% typ.
Operating Temperature: -40 Deg.C. to +50 Deg.C.
Temperature Effects: +/-0.5% max., +/-0.2% typ.

(for 40 Deg.C. change)

Page A22

Model: IUC-7X-WTX

Isolated Watts Transducer

NRTL/C

R

New

and

Improved

2

2

Instantaneous

Instantaneous

RMS

RMS

Watts

VA

New

New

New

New

Manufacturers of Process

Controls and Instrumentation