Electrical connection
3L2
1L1
5L3
4T2
2T1
6T3
(N) 8T4
(N) 7L4
L1
L2
L3
N Grnd
1.
2.
3.
4.
Figure 5. ExitOxy switch panel
The ExitOxy needs a supply of ± 400V AC + N 16A
Before the ExitOxy can be supplied, the following points must be checked:
-
Is there a correct main power cable supplied?
The ExitOxy is delivered without its own power cable. It is therefore desirable the an authorized electrician provides
a correct main power supply cable to the location of the ExitOxy.
-
Is the supplied power cable voltage-free?
Use a fitting voltmeter or multi-meter to check if the cable is voltage-free. Is there a voltage? Let an authorized
electrician shut off the power.
-
Is the head switch in the ‘OFF’ position?
(Figure 5. No. 1 & Figure 6)
Put this, if needed, in the desired position.
If the above points are met, the supply can be safely connected.
I ON
O
O
FF
Figure 6. Main switch
Step 1. Insert the supplied power cable into the ExitOxy switch panel.
Finish the cable with a suitable cable tray or PVC pipe.
Step 2. Connect the phases 1, 2 and 3 to the contacts 2T1, 4T2 and 6T3 of the main switch (Figure 5).
Step 3. Connect the neutral wire to the contact (N)8T4 of the main switch (Figure 5).
Step 4. Connect the green/yellow wire to the first ground terminal of the terminal strip. (Figure 5. No. 2).