At a glance

The Pressac Sensing CO

2

 Sensor is a fully wireless, solar powered room sensor,  designed to measure and 

report levels of Carbon Dioxide, ambient temperature and relative humidity in an internal environment. During 
normal operation, the sensor is powered from ambient room light: in prolonged low light environments the 

security  of  battery  back-up  ensures  continued  operation  for  over  10*  years  of  maintenance  free  operation. 

The sensor supports the open EnOcean

®

 standard (ISO/IEC 14543-3-10) facilitating seamless connection with 

building management systems.

Product Description

1. Selection of Sampling Rate

This can be set by confi guring DIP switch 1 as below.

2. Calibration

              CALIBRATION IS ESSENTIAL

 To ensure accurate CO

2

 reporting It is essential to perform a manual  

 

              calibration prior to commissioning this sensor. See section 2 of Product Operation.

Manual Calibration

To recalibrate the default level of 500ppm, set DIP Switch 3 (manual calibration) and DIP switch 4 (battery 
backup) to ON and press the learn button for 5 seconds. The unit’s LED will fl ash once per second for 
approximately 4 minutes. During this time, take the unit to an unoccupied environment (the ambient CO

2

 level 

here should be approximately 500ppm). After the 4 minute period, the unit’s LED will fl ash quickly for a further 
2 minutes while the recalibration process takes place. Once the LED has stopped fl ashing the unit’s base CO

2

 

level has been reset to 500PPM. Return DIP Switch 3 to the off  position. Dip switch 4 can be left in the ON 
position if the battery backup function is required. Moving Dip switch 3 back to the OFF position during the 

procedure will abort the calibration process.

Operating Mode (Calibration)

DIP Switch 2

Dip Switch 3

Learn Button

Sensor auto calibrates every 8 days

ON

OFF

N/A

Sensor uses factory calibration level (500ppm)

OFF

OFF

N/A

Sensor uses recalibrated background level on completion

OFF

ON

Pressed

3. Connection of battery

Battery

Unit Status

Dip Switch 4

Not connected

Solar powered only

OFF

Connected

Solar + battery powered

ON

4. Commissioning

There are 2 ways in which the unit can be commissioned.

Automatic Registration. 

To commission the unit, depress and release the “Learn” button. The LED will blink once. The unit now 
transmits a learn telegram.

Manual registration.

Alternatively, the unit can be commissioned onto your EnOcean

®

 network manually. To do this you will need 

the unique EnOcean

®

 ID of the Pressac Sensing CO

2

 Sensor and also its EnOcean

®

 Equipment Profi le. The 

EnOcean

®

 ID and the EEP are printed on the product label on the Pressac Sensing CO

2

 Sensor.

Product Operation

Light Status

Energy Supply

Sampling

DIP Switch 1

Ambient light good

(Powered from solar)

Fixed (15 mins)

ON

Ambient light poor

(Powered from stored energy)

Fixed (15 mins)

ON

Ambient light poor 

(Powered from battery)

Fixed (15 mins)

ON

Ambient light good

(Powered from solar)

Dynamic (5 mins)

OFF

Ambient light poor

(Powered from stored energy)

Dynamic (5 mins)

OFF

Ambient light poor 

(Powered from battery) 

Dynamic (15 mins)

OFF

Battery

DIP Switches

Learn Button

LED

EnOcean

®

 EEP

Module/Device ID

Solar Panel

Bottom Screw

Top Vent

Bottom Vent