Precaution on Installation
MLCAC-UTSM-2011-02
Installation
50
1. Precaution on Installation
1). Measure the necessary length of the connecting pipe, and make it by the following way.
a. Connect the indoor unit at first, then the outdoor unit.
Bend the tubing in proper way. Do not harm them.
Specially Notice the pipe length/height/dimension of each capacity.
Maximum pipe length
Model
Max. Length
Max. Elevation
18,000Btu/h ~24,000Btu/h
30m
10m
30,000Btu/h ~60,000Btu/h
30m
20m
Piping sizes
Model
Liquid(mm)
Gas(mm)
18,000Btu/h
Φ
6..35
Φ
12.7
24,000Btu/h
Φ
9.52
Φ
16
36,000Btu/h ~60,000Btu/h
Φ
9.52
Φ
19
CAUTIONS
Daub the surfaces of the flare pipe and the joint nuts with frozen oil, and wrench it for 3~4 rounds
With hands before fasten the flare nuts.
Be sure to use two wrenches simultaneously when you connect or disconnect the pipes.
Pipe gauge
Tightening torque
Flare dimension A
Min (mm) Max
Flare shape
Φ
6.35
15
~
16N.m
(153
~
163kgf.cm)
8.3
8.7
Φ
9.52
25
~
26N.m
(255
~
265kgf.cm)
12.0
12.4
Φ
12.7
35
~
36N.m
(357
~
367kgf.cm)
15.4
15.8
Φ
16
45
~
47N.m
(459
~
480kgf.cm )
18.6
19.1
Φ
19
65
~
67N.m
(663
~
684kgf.cm)
22.9
23.3
b. The stop value of the outdoor unit should be closed absolutely (as original state). Every time you connect it, first loosen the nuts at the part
of stop value, then connect the flare pipe immediately (in 5 minutes). If the nuts have been loosened for a long time, dusts and other
impurities may enter the pipe system and may cause malfunction later. So please expel the air out of the pipe with refrigerant before
connection.
c.
Expel the air after connecting the refrigerant pipe with the indoor unit and the outdoor unit. Then fasten the nuts at the repair-points.
2) Locate The Pipe
a. Drill a hole in the wall (suitable just for the size of the wall conduit), then set on the fittings such as the wall conduit and its cover.
b. Bind the connecting pipe and the cables together tightly with binding tapes. Do not let air in, which will cause water leakage by
condensation.
c.
Pass the bound connecting pipe through the wall conduit from outside. Be careful of the pipe allocation to do no damage to the tubing.
3) Connect the pipes.
4) Then, open the stem of stop values of the outdoor unit to make the refrigerant pipe connecting the indoor unit with the outdoor unit in
fluent flow.
5) Be sure of no leakage by checking it with leak detector or soap water.
6) Cover the joint of the connecting pipe to the indoor unit with the soundproof / insulating sheath (fittings), and bind it well with the tapes to
prevent leakage.
Summary of Contents for PAC247C-I
Page 5: ......
Page 9: ......
Page 15: ...MLCAC UTSM 2011 02 Wiring Diagrams Four way Cassette 13 4 Wiring Diagrams PAC247C I PAC367C I ...
Page 16: ...Wiring Diagrams MLCAC UTSM 2011 02 14 Four way Cassette PAC487C I ...
Page 25: ...MLCAC UTSM 2011 02 Service Space Ceiling Floor Type 23 3 Service Space ...
Page 26: ...Wiring Diagrams MLCAC UTSM 2011 02 24 Ceiling Floor Type 4 Wiring Diagrams PAC366FC I ...
Page 27: ...MLCAC UTSM 2011 02 Wiring Diagrams Ceiling Floor Type 25 PAC486FC I PAC606FC I ...
Page 35: ...MLCAC UTSM 2011 02 Features Outdoor Units 33 2 Service Space ...
Page 37: ...MLCAC UTSM 2011 02 Features Outdoor Units 35 4 Wiring Diagrams PAC247C O ...
Page 38: ...Features MLCAC UTSM 2011 02 36 Outdoor Units PAC367C O PAC366FC O ...
Page 39: ...MLCAC UTSM 2011 02 Features Outdoor Units 37 PAC487C O PAC486FC O ...
Page 40: ...Features MLCAC UTSM 2011 02 38 Outdoor Units PAC606FC O ...