MLCAC-UTSM-2011-02
The Specification of Power
Four-way Cassette
17
7. The Specification of Power
For 220V~230V 60Hz 1PH Outdoor unit type
Type
(
Cooling & Heating
)
18000
24000
36000
Phase
1- Phase
1- Phase
1- Phase
Indoor unit
Frequency and Voltage
220-230V~, 60Hz
220-230V~, 60Hz
220-230V~, 60Hz
Phase
1- Phase
1- Phase
1- Phase
Power
Outdoor unit
Frequency and Voltage
220V~, 60Hz
220V~, 60Hz
220V~, 60Hz
Indoor Circuit Breaker/ Fuse (A)
15/10
15/10
15/10
Outdoor Circuit Breaker/ Fuse (A)
30/25
30/25
35/30
Indoor Unit Power Wiring (mm
2
)
3x2.5
3x2.5
3x2.5
Ground Wiring
2.5
3.3
3.3
Outdoor
Unit
Power
Wiring
3x2.5
3x3.3
3x3.3
Indoor/Outdoor Connecting
Wiring (mm
2
)
Weak Electric Signal
4x1.0Z
4x1.0
4x1.0
Type
(
Cooling only
)
18000
24000
36000
Phase
1- Phase
1- Phase
1- Phase
Indoor unit
Frequency and Voltage
220-230V~, 60Hz
220-230V~, 60Hz
220-230V~, 60Hz
Phase
1- Phase
1- Phase
1- Phase
Power
Outdoor unit
Frequency and Voltage
220V~, 60Hz
220V~, 60Hz
220V~, 60Hz
Indoor Circuit Breaker/ Fuse (A)
15/10
15/10
15/10
Outdoor Circuit Breaker/ Fuse (A)
30/25
30/25
35/30
Indoor Unit Power Wiring (mm
2
)
3x2.5
3x2.5
3x2.5
Ground Wiring
2.5
3.3
3.3
Outdoor
Unit
Power
Wiring
3x2.5
3x3.3
3x3.3
Indoor/Outdoor Connecting
Wiring (mm
2
)
Weak Electric Signal
2x1.0
2x1.0
2x1.0
For 220V 60Hz 3PH Outdoor unit type
Type(Cooling only)
36000
48000
Phase
1- Phase
1- Phase
Indoor unit
Frequency and Voltage
220-230V~, 60Hz
220-230V~, 60Hz
Phase
3- Phase
3- Phase
Power
Outdoor unit
Frequency and Voltage
220V~, 60Hz
220V~, 60Hz
Indoor Circuit Breaker/ Fuse (A)
15/10
15/10
Outdoor Circuit Breaker/ Fuse (A)
35/30
40/35
Indoor Unit Power Wiring (mm
2
)
3x1.5
3x1.5
Ground Wiring
2.5
4.0
Outdoor Unit Power Wiring
3x2.5
3x4.0
Indoor/Outdoor
Connecting
Wiring (mm
2
)
Weak Electric Signal
2x1.0
2x1.0
Type(Cooling & Heating)
36000
48000
Phase
1- Phase
1- Phase
Indoor unit
Frequency and Voltage
220-230V~, 60Hz
220-230V~, 60Hz
Phase
3- Phase
3- Phase
Power
Outdoor unit
Frequency and Voltage
220V~, 60Hz
220V~, 60Hz
Indoor Circuit Breaker/ Fuse (A)
15/10
15/10
Outdoor Circuit Breaker/ Fuse (A)
35/30
40/35
Indoor Unit Power Wiring (mm
2
)
3x1.5
3x1.5
Ground Wiring
2.5
4.0
Outdoor Unit Power Wiring
3x2.5
3x4.0
Indoor/Outdoor
Connecting
Wiring (mm
2
)
Weak Electric Signal
4x1.0
4x1.0
Summary of Contents for PAC247C-I
Page 5: ......
Page 9: ......
Page 15: ...MLCAC UTSM 2011 02 Wiring Diagrams Four way Cassette 13 4 Wiring Diagrams PAC247C I PAC367C I ...
Page 16: ...Wiring Diagrams MLCAC UTSM 2011 02 14 Four way Cassette PAC487C I ...
Page 25: ...MLCAC UTSM 2011 02 Service Space Ceiling Floor Type 23 3 Service Space ...
Page 26: ...Wiring Diagrams MLCAC UTSM 2011 02 24 Ceiling Floor Type 4 Wiring Diagrams PAC366FC I ...
Page 27: ...MLCAC UTSM 2011 02 Wiring Diagrams Ceiling Floor Type 25 PAC486FC I PAC606FC I ...
Page 35: ...MLCAC UTSM 2011 02 Features Outdoor Units 33 2 Service Space ...
Page 37: ...MLCAC UTSM 2011 02 Features Outdoor Units 35 4 Wiring Diagrams PAC247C O ...
Page 38: ...Features MLCAC UTSM 2011 02 36 Outdoor Units PAC367C O PAC366FC O ...
Page 39: ...MLCAC UTSM 2011 02 Features Outdoor Units 37 PAC487C O PAC486FC O ...
Page 40: ...Features MLCAC UTSM 2011 02 38 Outdoor Units PAC606FC O ...