46
Packaged and Split Rooftop Ventilator
© 2021 Mitsubishi Electric US, Inc.
Premi
Sys
Part Name
Checking Points
Liquid pipe thermistor
(TH22)
Gas pipe thermistor
(TH23)
Reheat pipe thermistor
(TH25)
Disconnect the connector then measure the resistance between terminals with a tester.
(Surrounding temperature 10ºC~30ºC [50ºF~86ºF].
Normal
Abnormal
4.3kΩ~9.6kΩ
Open or short
<Thermistor characteristic graph>
Liquid thermistor (TH22)
Gas pipe thermistor (TH23)
Reheat pipe thermistor (TH25)
Thermistor R
10
= 15kΩ ± 3%
Fixed number of B = 3460kΩ ± 2%
Rt = 15exp {3465 (
1
⁄
273+t
-
1
⁄
273
)}
0ºC
32ºF
15kΩ
10ºC
50ºF
9.7kΩ
20ºC
68ºF
6.4kΩ
25ºC
77ºF
5.3kΩ
30ºC
86ºF
4.3kΩ
40ºC
104ºF
3.1kΩ
Linear Expansion Valve
1
2
3
4
5
6
LEV
White
Yellow
Orange
Blue
Red
Brown
CN60, CNLEV2
Disconnect the connector then measure the resistance between terminals with a tester.
Normal
Abnormal
1-5
White-Red
2-6
Yellow-Brown
3-5
Orange-Red
4-6
Blue-Brown
Open or short
200 kΩ ± 10%
Solenoid valve coil
SV10, SV11
Measure the resistance between the terminals with a tester.
(Surrounding temperature 20ºC [68ºF]
Normal
Abnormal
1183Ω ± 100%
Open or short
(Refer to the <Thermistor
characteristic graph>)
0
10
20
30
40
50
-20 -10 0 10 20 30 40 50
Temperature
(˚C)
-4 14 32 50 68 86 104122
[˚F]
Resistance (KΩ
)
Troubleshooting – Split DX Refrigeration Circuit