SDI-JC-13D2 rev 8-22-22
page 6 of 14
Wiring (continued):
INPUT TYPE = '5V’ or 10V'
34
33
A/D
0-5 or 0-10 Vdc Signal
100.0k
0.1%
+
-
Note: 100k resistor is not supplied with the JC-10D2.
Order separately: p/n 25100-2B25-4/10F
10.0k
0.1%
JC-10D2
INPUT TYPE = '2.3V'
34
33
0.000 - 2.330 Vdc
A/D
Potentiometer
1k – 10k ohm
32 +2.5Vref
JC-10D2
INPUT TYPE = '2.3V'
34
33
0.000 - 2.330 Vdc
A/D
0 - 2.3 Vdc Signal
+
-
Power
Supply
JC-10D2
INPUT TYPE = 'mA'
4 Wire 4-20 mA Xmtr
+
-
Power
Supply
34
33
A/D
Thermistor
Fuse
JC-10D2
31
34
33
A/D
2 Wire 4-20 mA Xmtr
+
-
INPUT TYPE = 'mA'
Thermistor
Fuse
+24V
JC-10D2
Thermocouple and Thermistor Field Wiring Notes:
* Do not run in conduits with AC wiring.
* Do not run in conduits with Ignition xfmr or VFD motor wiring.
* Can run in conduits with thermocouples, thermistors
pots, 4-20 mA, and other 'quiet' DC wiring; but not with
pulser or solenoid wiring).
* Un-Shielded Cable can be used if run in metallic conduit.
32
34
33
+2.500 Vdc
10.0k
ohms
A/D
Thermistor
No Polarity
10k@25C
817.2@100C
INPUT TYPE = 'Thermistor'
JC-10D2
INPUT TYPE = 'J TC' or 'K TC'
+
-
A/D
34
33
red
white = type J
yellow = type K
Thermocouple
Extension Wire
red
+
-
Thermocouple
(Types J or K)
JC-10D2