Preferred JC-13D2 Installation & Operation Instructions Download Page 10

 

SDI-JC-13D2   rev 8-22-22

 

 

page 10  of  14 

Configure / Setup     Alarms 

Parameter  Default 

Max. 

Min. 

Goto: Menu > Configure/Setup > Ch.x Setup > Alarm Setup 

16 

100.0 

999999  -999999 

Alarm 1 Setpoint 

 

 

17 

3600 

Alarm 1 Delay Sec 

 

18 

1.0 

99999 

Alarm 1 Deadband

 

 

19 

0.0 

999999  -999999 

Alarm 2 Setpoint 

 

 

20 

3600 

Alarm 2 Delay Sec 

 

21 

1.0 

99999 

Alarm 2 Deadband

 

 

 
 

Configure / Setup     Alarm Types 

Parameter  Default 

Max. 

Min. 

Goto: Menu > Configure/Setup > Ch.x Setup > Alarm Setup > Alarm Types 

22 

Disabled 

HiHi 

Disabled 

Alarm 1 Type

 

Disabled, LoLo, Lo, Hi, HiHi

  

23 

Auto 

Manual 

Auto 

Alarm 1 Reset Type 

Auto, Manual 

24 

Disabled 

HiHi 

Disabled 

Alarm 2 Type

 

Disabled, LoLo, Lo, Hi, HiHi  

25 

Auto 

Manual 

Auto 

Alarm 2 Reset Type 

Auto, Manual

 

 

 

Configure / Setup     Totalizer Setup 

 

Parameter  Default 

Max. 

Min. 

Goto: Menu > Configure/Setup > Analog Input Setup > mA/Vdc Scaling > Totalizer Setup 

NOTE:

 None of these Parameters are used for T/C and Thermistor Input Types

 

26 

Disabled  Enabled  Disabled 

Totalizer Option 

 

27 

Disabled  Enabled  Disabled 

Zero Button Option 

Totalized values can be reset to zero when User presses this button. 

28 

/Hour 

/Day 

/Minute 

Rate Time Base

 

/Minute, /Hour, /Day    Examples: gpm, use /Minute \ gph, use /Hour \ gal/day, use /Day 

29 

x1 

x1000000 

x1 

Rate Multiplier   

x1 x10,x100,x1000,x10000,x100000,x1000000  Example: 0-5 kscf/hr & x1000, 1 count = 1scf  

 

TotUnits 

 

 

Totalized Units

 

User entered text, 8 character max, space permitting, use Upper and Lower case letters 

30 

0.0 

99999.0 

0.0 

Low Flow Cutoff

 

Input Rates below this value will not be totalized. 
Typically used to prevent false totalization due to Xmtr Zero Calibration drift. 

 

 
Configure / Setup    4-20 mA Output 

Parameter  Default 

Max.  Min. 

Goto: Menu > Configure/Setup > Optional I/O > 4-20 Output 

31 

AOUT 0-1 Channel   

 Choose which AIN channel is associated with this output 

32 

0.0 

99999.9  -99999.9 

AOUT 0-1 4 mA =      

This is the scaled Input value for  4 mA output.

 

33 

100.0 

99999.9  -99999.9 

AOUT 0-1 20 mA = 

This is the scaled Input value for 20 mA output.

 

34 

AOUT 0-2 Channel   

 Choose which AIN channel is associated with this output 

35 

0.0 

99999.9  -99999.9 

AOUT 0-2 4 mA =      

This is the scaled Input value for  4 mA output.

 

36 

100.0 

99999.9  -99999.9 

AOUT 0-2 20 mA = 

This is the scaled Input value for 20 mA output.

 

 

 

 

Summary of Contents for JC-13D2

Page 1: ...sensor Units totalizer Units 50 pt Alarm Event History Time Date Stamped Only 4 7 8 deep fits in most existing burner control cabinets Plug in field wiring terminals Modbus TCP Ethernet Modbus RTU RS...

Page 2: ...ntinuously indicate the AIN Process Variable PV value The alarm setpoints are indicated on the bargraph with tic marks If the PV exceeds a Hi or HiHi Setpoint for more than 30 seconds adjustable the b...

Page 3: ...ms Alarms will not be displayed on the Main and Menu screens All active Alarms are displayed on this screen High Alarm High High Alarm etc The PV and time date shown occurred when the Alarm time delay...

Page 4: ...elds only where shown insulate all other shields to prevent accidental grounding Ignition transformer and motor VFD wiring are particularly electrically noisy and should be kept away from the thermoco...

Page 5: ...ts 45 47 49 RS485 RS485 Common Ethernet 43 24 Vdc 7 ACDIN 1 8 ACDIN 2 37 24V 32 2 5Vref 38 AIN 3 39 DC 44 DCDIN 1 46 DCDIN 2 DC 24 Vdc 120 Vac 1 2 3 Relay 1 6 5 4 Relay 2 Channel 3 35 24V 32 2 5Vref 3...

Page 6: ...r Fuse JC 10D2 31 34 33 A D 2 Wire 4 20 mA Xmtr INPUT TYPE mA Thermistor Fuse 24V JC 10D2 Thermocouple and Thermistor Field Wiring Notes Do not run in conduits with AC wiring Do not run in conduits wi...

Page 7: ...nction DC DIN 2 Function Discrete Outputs ROUT 1 Function ROUT 2 Function DOUT 1 Function DOUT 2 Function 4 20 mA Outputs AOUT 0 1 Channel AOUT 0 1 4 mA AOUT 0 1 20 mA AOUT 0 2 Channel AOUT 0 2 4 mA A...

Page 8: ...ow Cutoff Alarm 1 2 Types Alarm 1 Type Alarm 1 Reset Type Alarm 2 Type Alarm 2 Reset Type Bargraph Setup Tick Decimal Places Bargraph Top Bargraph Bottom Analog Input Setup Input Name Input Type Smoot...

Page 9: ...t Types 6 0 0 15 0 15 0 Temperature Adjust degrees The displayed value is offset from the measured value by this amount for all temperatures Used to calibrate out minor temperature differences due to...

Page 10: ...ion Totalized values can be reset to zero when User presses this button 28 Hour Day Minute Rate Time Base Minute Hour Day Examples gpm use Minute gph use Hour gal day use Day 29 x1 x1000000 x1 Rate Mu...

Page 11: ...ed AIN Error Disabled DOUT 2 Function Disabled Alarm 1 Alarm 2 Common Alarm Horn AIN Error NOTE Horn is Off after Alarm s are silenced AIN Error means mA Vdc Out of Range T C Open Thermistor Shorted o...

Page 12: ...H 2 Alarm 2 Setpoint 40117 RO UINT8 Enumeration CH 2 Alarm 2 Type 0 Disabled 1 LoLo 2 Lo 3 Hi 4 HiHi 40118 RO UINT32 CH 2 Totalizer Count 40120 RO FLOAT CH 3 Process Variable 40122 RO FLOAT CH 3 Alarm...

Page 13: ...EL D4B Adapter Plate Panel Cutout 8 00 X 10 75 Specifications Mechanical Enclosure Nema 12 Faceplate Indoor Locations Bezel 3 7 8 w x 8 h x 1 d Rear Case 3 1 2 w x 7 9 16 h x 4 7 8 d Panel Cutout 3 6...

Page 14: ...SDI JC 13D2 rev 8 22 22 page 14 of 14 Preferred Utilities Mfg Corp Preferred Instruments div 31 35 South Street Danbury CT 06810 203 743 6741 www preferred mfg com...

Reviews: