Preferred Instruments - Feedwater Center Model JC-FWC-ND-OIT

 

MAIN MENU

> 1. TUNING - 

  2. TUNING - TRANSFER

  3. UTILITIES

  4. 

  5. PAGER SETUP

  6. I/O

  7. INITIAL SETUP PARAMETERS 

QUICK START QUIDE

INITIAL PARAMETER SETUP

The Preferred Instruments Feedwater Center - Transfer Pump/

Surge Tank Control is designed to be field adjustable for multiple 

applications.  In order to customize to your installation some pre-

liminary settings must be entered.   

After initial powerup, the homepage should be displayed. To set 

initial parameters, Press the MAIN MENU button, and then “7” for 

Initial Parameter Menu

There is a detailed list of these parameter values found in the 

operation and instruction manual SDI-JC-FWC that provides an 

area to record each setting for future use in case the unit must 

be replaced.  

FACTORY 

VALUE

DESCRIPTION

HELP/COMMENTS

NOT USED

SURGE TANK LEVEL

If the system being set up has a Level sensor on the Surge 

Tank, turn the ‘NOT USED’ to ‘INSTAL’D’

NOT USED

TRANSFER PUMP DISCH      

PRESSURE

If the system being set up has a Pressure sensor on the 

Transfer Pump Header, turn the ‘NOT USED’ to ‘INSTAL’D’

NOT USED

MAKE UP FLOW

If the system being set up has a Flow sensor on the Make 

Up water line going into the Surge tank, turn the ‘NOT 

USED’ to ‘INSTAL’D’ 

NOT USED

MAKE UP PRESSURE

If the system being set up has a Pressure sensor on the 

Make Up water line going into the Surge tank, turn the 

‘NOT USED’ to ‘INSTAL’D’ 

NOT USED

SURGE TANK TEMPERATURE

If the system being set up has a temperature sensor in the 

Surge tank, turn the ‘NOT USED’ to ‘INSTAL’D’ by using 

the UP and DOWN arrow keys and highlighting the ‘NOT 

USED’ and pressing enter.

NOT USED

COND RTN FLOW

If the system being set up has a Flow sensor on the Con-

densate return line, turn the ‘NOT USED’ to ‘INSTAL’D’ 

NOT USED

COND RTN TEMP

If the system being set up has a Temperature sensor 

on the Condensate return line, turn the ‘NOT USED’ to 

‘INSTAL’D’ 

NOT USED

BACKUP PUMP HEADER PSI

If the system being set up has a Pressure sensor in the 

Transfer Pump Header, turn the ‘NOT USED’ to ‘INSTAL’D’ 

PARAMETER SETTINGS

                                      

> 1. PARAMETERS - SETUP 1

  2. PARAMETERS - SETUP 2

  3. SETUP EGUS

  

  

PARAMETER - SETUP 1 deals with the installed devices.  Set each sensor to INSTAL’D if it is included in this applica-

tion.  

PARAMETERS - INSTALLED DEVICES

 PARAMETER SETUP - 1

SENSORS:

 SURGE TANK LEVEL  (AI 0.1):    INSTAL’D

 PUMP DISCH PRESS  (AI 0.2):    INSTAL’D

 MAKE UP FLOW      (AI 6.1):    INSTAL’D

 MAKE UP PRESSURE  (AI 6.2):    INSTAL’D

 SURGE TANK TEMP   (AI 6.3):    INSTAL’D

 COND RTN BLOW     (AI 6.4):    INSTAL’D

 COND RTN TEMP     (AI 6.5):    INSTAL’D

                   (AI 6.6):    NOT USED

                   (AI 6.7):    NOT USED

 BU DUMP DISCH PSI (AI 6.8):    INSTAL’D

  

QUANTITY OF PUMPS

 TRANSFER PUMPS          :        4

 TRANSFER LEAD ALWAYS ON :      YES

Summary of Contents for JC-FWC-ND

Page 1: ...Preferred Instruments Danbury CT USA http www PreferredInstruments com Feedwater Center Model JC FWC ND OIT JC FWC ND Quick Start Guide...

Page 2: ...evision 0 0 02 13 2019 INTRODUCTION This guide is designed to simplify the commissioning process by detailing the initial parameters required to properly setup a Preferred Instruments Feedwater Cen te...

Page 3: ...n the NOT USED to INSTAL D NOT USED MAKE UP PRESSURE If the system being set up has a Pressure sensor on the Make Up water line going into the Surge tank turn the NOT USED to INSTAL D NOT USED SURGE T...

Page 4: ...ge NOT USED to INSTAL D This enables the Level Control Valve output PARAMETER SETUP 2 deals with the scope and type of control being used A description of the effect of each pa rameter are provided PA...

Page 5: ...t Editor please reference the Operation and Installation manual SDI JC FWC ND OIT ID NAME VALUE 0 VALUE100 DECPT HELP COMMENTS A1 A2 ST LVL 0 0 1000 1 Surge Tank Level in WC A3 A4 STF 50 300 0 Surge T...

Page 6: ...anual SDI JC FWC ND OIT MODBUS The following information applies to JC FWC ND OIT Feedwater Center Transfer Pump Surge Tank Control Default Options Device Address 1 1 31 Baud 19200 1200 2400 4800 9600...

Page 7: ...40021 Surge Tank Low Low Level Alarm Delay Y 100 0 secs 40022 40023 40024 40025 40026 40027 40028 40029 40030 40031 40032 40033 40034 40035 40036 Surge Tank Level for 100 MU Valve Y 100 0 40037 Surge...

Page 8: ...dd l Start Lag Delay Y 0 100 secs 40059 Transfer Pump Add l Stop Lag Delay Y 0 100 secs 40060 Transfer Pump Quantity Y 0 100 secs 40061 Transfer Pump Rotate Runtime Hours Y 0 100 40062 Transfer Pump 1...

Page 9: ...0 GPM 40095 Surge Tank Pump 1 Elapsed Time 0 10000 Hrs 2 40096 Surge Tank Pump 2 Elapsed Time 0 10000 Hrs 2 40097 Surge Tank Pump 3 Elapsed Time 0 10000 Hrs 2 40098 40099 40100 40101 40102 40103 40104...

Page 10: ...018 Has Makeup Water Flow Y NOT USED INSTAL D 00019 Has Makeup Water Pressure Y NOT USED INSTAL D 00020 Has Condensate Return Temperature Y NOT USED INSTAL D 00021 Has Condensate Return Flow Y NOT USE...

Page 11: ...061 Surge Tank Low Level Alarm Alarm Normal 00062 Surge Tank Low Low Level Alarm Alarm Normal 00063 Surge Tank High Level Alarm Alarm Normal 00064 00065 00066 00067 00068 00069 Transfer Pump 1 Active...

Page 12: ...99 00100 00101 Surge Tank MU Valve in Auto Auto On or Off 00102 00103 Spare Yes No 00104 Spare Yes No 00105 Transfer Pump 1 Speed in Auto Auto On or Off 00106 Transfer Pump 2 Speed in Auto Auto On or...

Page 13: ...2 627 DIN 1 DI 1 13 628 DIN 1 DI 1 14 629 DIN 1 DI 1 15 Disable All BAS Contact 630 HOA ROUT 2 HO 2 1 Transfer Pump 1 Start Circuit 631 HOA ROUT 2 HO 2 2 Transfer Pump 2 Start Circuit 632 HOA ROUT 2 H...

Page 14: ...677 A M AOUT 5 AM 5 3 Transfer Pump 3 Speed 678 A M AOUT 5 AM 5 4 Transfer Pump 4 Speed 679 A M AOUT 5 AM 5 5 Transfer Make Up Water Valve 690 AIN 6 AI 6 1 Make Up Water Flow 691 AIN 6 AI 6 2 Make Up...

Page 15: ...15 Preferred Instruments Feedwater Center Model JC FWC ND OIT NOTES...

Page 16: ...Preferred Instruments Feedwater Center Model JC FWC ND OIT 16 REVISION HISTORY REV 0 0 FIRST ISSUE 02 13 2019 Description SDI FWC ND OIT QS Revision 0 0 02 13 2019...

Page 17: ...A Division of Preferred Utilities Manufacturing Corp 31 35 South St Danbury CT 06810 www Preferred MFG com Phone 203 743 6741 Email info preferred mfg com...

Reviews: