Installation and Operation Manual JC-22-PL2-1006      rev. 6    6-5-17  

 Page 5 of 12 

 

A. DESCRIPTION 

 

 
The JC-22-PL2-1006 is a state-of-the-art microcomputer based linear actuator that is used as a 
draft controller,  with a solid state pressure sensor. The JC-22-PL2-1006 interfaces to any 
commercialized flame safeguard in the industry or any dedicated burner management system. 
The actuator travel range is 6” and travel time 60 seconds. The actuator has 150 lbs thrust 
force. 
The JC-22-PL2-1006 actuator provides automatic modulation for any balanced negative or 
positive furnace pressure application. 
 
The pressure sensing element is  a linear solid state pressure transducer that is temperature 
compensated that generates a low drift signal. The sensor has two inlets: one for positive 
pressure and the other for negative pressure. The pressure is sampled via a ¼” NPT female 
fitting through a 1/8” flexible tube connected to one of the transducer port. 
There are also four  miniature dials for adjusting the set point, proportional band, damping and   
dead band. Base on the inputs, the microcomputer activates two solid state relays, one for 
opening the damper and the other for closing the damper. 
 
The actuator is equipped with a relay module that includes a toggle switch for selecting between 
Automatic and Fully open operations. The Open Mode allows soot-blowing operation without 
firing interruption and also allows the burner to fire in the “Open” damper mode under 
emergency conditions. 
 
Open and Closed end switches shut off the power to the motor whenever the arm is fully 
extended or fully retracted. There is a third auxiliary switch that indicates when the damper is 
fully open. This auxiliary switch is used  as High Fire Switch Indicator.  
 
The actuator is self-locked when power is lost. 
 
A 10-point terminal strip is used for external connections. See Wiring section. 
 
The draft controller is provided in a single compact enclosure with a removable cover and is 
offered as a direct replacement for Hays Cleveland model 9502-1012-B-12, facilitating field 
removal/installation. 
 
Preferred  offers a Draft Cut Off Switch model JC22-HDPCO-8 that is a direct replacement to 
Hays AFS-952-55 for forced draft burners. Model JC-22-LDPCO-8 is for natural draft burners.  
 
 
 
 

 

Summary of Contents for JC-22-PL2-1006

Page 1: ...u uf f fa a ac c ct t tu u ur r ri iin n ng g g C C Co o or r rp p po o or r ra a at t ti iio o on n n J J JC C C 2 2 22 2 2 P P PL L L2 2 2 1 1 10 0 00 0 06 6 6 D D DR R RA A AF F FT T T R R RE E EG...

Page 2: ...turing Corp Phone 203 743 6741 Fax 203 798 7313 www preferredinstruments com Installation and Operation Manual JC 22 PL2 1006 rev 6 6 5 17 Page 2 of 12 Table of Contents A Description 5 B Specificatio...

Page 3: ...he burner and all applicable burner boiler safety codes should install configure and commission the JC 22 PL2 1006 Incorrect installation can result in equipment damage injury or death Note All rights...

Page 4: ...erred Instruments Div of Preferred Utilities Manufacturing Corp Phone 203 743 6741 Fax 203 798 7313 www preferredinstruments com Installation and Operation Manual JC 22 PL2 1006 rev 6 6 5 17 Page 4 of...

Page 5: ...ur miniature dials for adjusting the set point proportional band damping and dead band Base on the inputs the microcomputer activates two solid state relays one for opening the damper and the other fo...

Page 6: ...table from 0 100 corresponds to 0 to 2 0 w c or 0 to 2 0 w c see pg 12 to change Dampening Adjustable from 0 100 corresponds to 1 5 to 15 seconds For 90 response to a step change Dead Band Adjustable...

Page 7: ...ice panel not intermediate sub panels to the damper controller The ground path needs to be low impedance less than 1 ohm to the equipment frame which in turn needs low impedance to earth ground For a...

Page 8: ...Operating Limit switch type Burner Flame Safeguard Typical Wiring Diagram for JC 22 PL2 1006 Draft Controller with JC 22 xDPCO 8 Draft Cutout NOTE Burner Boiler wiring diagrams vary significantly fro...

Page 9: ...n dry contact Contacts make when damper is fully open Consult burner mfg for proper flame safeguard interface connection Typically wired in series with flame safeguard Start Ignition interlocks D Oper...

Page 10: ...The factory set range 0 to 2 or 0 to 2 is indicated on the label near the adjustment pots The range can be changed by following the directions on page 12 2 Damping Turn clockwise to reduce actuator hu...

Page 11: ...erredinstruments com Installation and Operation Manual JC 22 PL2 1006 rev 6 6 5 17 Page 11 of 12 LED Indicators INCREASE yellow The ram tube is extending which opens the damper DECREASE yellow The ram...

Page 12: ...le disconnects many be required 2 Disconnect the external sample line 3 Remove the two mounting screws next to sample line connection 4 Remove the Controller and un plug the cable connected to the boa...