STOP
Manual Starting Proce-
Electric Starting Proce-
ADD FLUIDS
Check oil and fuel levels
If needed, fill as shown below
GROUND GENERATOR
TO PREVENT ELECTRIC SHOCK
Install and connect 12V battery
Unplug all electrical loads
For Electric Start
Add fuel to within
1" of the rim of the tank
Note:
Use regular Unleaded 87 Octane gasoline.
E85 Ethanol blend will damage engine.
4.
PULL STARTER HANDLE
3.
TURN SWITCH TO START
FOR UP TO 5 SECONDS.
START
I
O
START
3.
TURN SWITCH TO ON
ON
I
O
START
2.
OPEN FUEL VALVE
1.
CLOSE CHOKE
2.
OPEN FUEL VALVE
1.
CLOSE CHOKE
4.
CHOKE SLOWLY TO RUN
5.
CHOKE SLOWLY TO RUN
5.
CHECK TOTAL WATTS
THEN PLUG IN PRODUCTS
6.
CHECK TOTAL WATTS
THEN PLUG IN PRODUCTS
BEFORE USING:
Running
Watts
1,000
400
200
1,200
Total Running W
atts
(must be less than 3,200)
4,200
Largest
Additional Start-up W
atts
1,200
Total Startup W
atts needed for all loads
(must be less than 4,000)
5,400
Must be
Less than
8,750
Must be
Less than
7,000
Running
Watts
1,000
400
200
1,200
Total Running W
atts
(must be less than 3,200)
4,200
Largest
Additional Start-up W
atts
1,200
Total Startup W
atts needed for all loads
(must be less than 4,000)
5,400
Must be
Less than
8,750
Must be
Less than
7,000
Add oil to engine crankcase
WITHOUT OIL
GENERATOR WILL
NOT START
Wheel Kit sold separately
(Item 68531)