TROUBLESHOOTING

Most problems are easily remedied by consulting 
the trouble-shooting guide. If problems still persist, 
contact PrecisionTemp or an authorized service 
center. Only a qualified technician should do any 
work involving the gas system.

A periodic visual check of the burner flames should 
be done by observing the flame through the “peep 
hole” in the heat exchanger. There should be blue 
flame with minimum or no yellow tipping. There 
should be nothing obstructing the flow of 
combustion and ventilation air.

Burner maintenance should be performed by a 
PrecisionTemp Authorized Service Technician.

NOTE:  The heater is dormant until it senses 
water flow.  When a water tap is turned on to at 
least .4 GPM the burner will fire until water flow 
is turned off and the heater again goes 
dormant.

Heater Does Not Come On When The Water is 
turned on.  (Power vent not running)

1. Be sure power is on and panel breaker is not 

tripped.

2. Check electrical contacts. Be sure the connector 

is plugged into board. Using a voltmeter, check 
for 12Volts on this connector.

3. Be sure all electrical connectors are secure and 

the polarity is correct. (Red wire to positive 
terminal).

4. Fuse in power wire might be blown. Replace 

fuse.

5. Locate the ECO, high temperature switch (red 
and purple wires) at the upper left hand of the heat 
exchanger. Check for open circuit condition. The 
ECO should be reset by pushing the reset button 
when temperature drops below 160 degrees.
 6. Be sure there is a battery in the system. Never 
connect the heater directly to a power converter. 
Some converters have circuits that are not pure 
DC.  This can cause malfunctions or damage to 
the heater and is not covered by warranty.
7. Be sure that no water-mixing valve has been left 
in the on position, using the showerhead as a shut 
off. This will permit water to bypass the water 
heater and bleed cold water into the hot water 
system. Always turn off both hot and cold water 
valves after using. 
8. Be sure that the bypass valve at the water 
plumbing connections is in the "off" position.  An 
open valve can also permit water to bypass heater, 
causing it not to fire.

There Is No Ignition When Water Is On (Power 
vent is running)

1. Be sure the gas valve at the tank is “On”, there 
is gas in the tank and the gas line is purged of all 
air.
2. Be sure that water flow is at least 0.5 gallon/
minute.
3. Check that the ignition wire is plugged into the 
spark tower on the ignition control and is not 
touching anything else.
4. Check flame site hole to see if igniter is sparking 
from the probe to the burner. Contact 

PrecisionTemp

 or your nearest authorized service 

representative.
5. Check that there are no cuts or breaks in the 
wire. Align it so that it is not in contact with 
anything but the terminal.
6. Be sure that the power vent fan has 12 volts to it 
when there is water flowing and there are no 
obstructions in the flue pipe. 
7. Safety pressure switch may be out of 
adjustment.  Contact PrecisionTemp or your 
nearest authorized service representative.

No Water Flows From Tap When Tap is 
Turned on.

1. Be sure that water supply is turned on and 
that there are no obstructions.
2. Hot and cold water lines connected to 
heater are reversed.  Correct by reversing their 
positions.

Burner Turns On But Temperature Fluctuates 
Erratically.

1. May be caused by excessive restriction at the 
water outlets, showerheads, aerators or water 
strainers. These should be cleaned and  any 
showerhead flow restrictor removed.
2. If temperature fluctuates as the pump cycles, a 
pressure accumulator tank is needed in the water 
system. If you have an accumulator tank, check to 
see if it has become filled with water. If it has, drain 
it so that it contains air only.

Heater Comes On But Rapidly Cycles On And 
Off.

1. 

Water flow is too low. Increase flow at a tap. Clean 

all aerators and shower head screens to assure at 
least .4 GPM of water flow
2. Water pump is not functioning properly. Repair or 
replace pump.
3. If the heater cycles as the pump cycles, a pressure 
accumulator tank is needed in the water system. If 
you have an accumulator tank, check to see if it has 
become filled with water. If it has, drain it so that it 
contains air only.
4. Air is in the water line. Bleed air by turning on all 
water taps.

6

Summary of Contents for cIAPMO-T RV-550-EC

Page 1: ...r to the current standards of Local codes or in the absence of local codes the National Fuel Gas Code ANSI Z223 1 NFPA 54 and or CSA B149 1 Natural Gas and Propane Installation Code Local codes or in...

Page 2: ...he case holes with no gaps or openings where the line passes through the case All connections must be made using TWO 2 wrenches to avoid twisting and damaging lines Damage voids the Warranty 5 Cut the...

Page 3: ...al Vehicles ANSI A119 2 or CAN CSA Z240RV CAUTION ELECTRICAL DAMAGE Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Verify prope...

Page 4: ...he showerhead button wastes water Each time this is done the showerhead trickles filling the hot water line with cold water This cold water has to be purged from the line each time the showerhead is t...

Page 5: ...er 8 Flue Hood 9 Flue Pipe 10 T In Thermistor 11 T Mid Thermistor 12 T Out Thermistor 13 165 F ECO 14 100 PSI Pressure Relief Valve 15 Gas Modulation Valve NOT PICTURED 16 12 VDC Relay 17 Control Boar...

Page 6: ...ions is in the off position An open valve can also permit water to bypass heater causing it not to fire There Is No Ignition When Water Is On Power vent is running 1 Be sure the gas valve at the tank...

Page 7: ...purchase PrecisionTemp will replace the complete water heater if the heat exchanger leaks due to corrosion This warranty includes reasonable labor charges required to replace the complete water heater...

Page 8: ...8...

Reviews: