PRESSURE RELIEF VALVE 

THIS VALVE IS A SAFETY COMPONENT AND MUST 

NOT BE REMOVED FOR ANY REASON OTHER 

THAN REPLACEMENT. 

This water heater is equipped 

with a pressure relief valve that complies with the standard 

for Relief Valves and Automatic Gas Shutoff Devices for 

Hot Water Systems, ANSI Z21.22 / CSA 4.4. 

This valve protects against excessive water expansion only. 

This water heater has separate and dedicated protection for 

excessive heat. 

If you use a discharge line, do not use a reducing coupling or 

other restriction smaller than the outlet of the relief valve. 

Allow complete drainage of both valve and line. 

FOR REPLACEMENT PARTS: 

DO NOT install anything less than a pressure relief 

valve certified by a nationally recognized testing 

laboratory that maintains periodic inspection of 

product of listed equipment or materials, as meeting 

requirements for Relief Valves and Automatic Gas 

Shutoff Devices of Hot Water Supply Systems, 

ANSI Z21.22 / CSA 4.4. Valve must have 

maximum set pressure

 not to exceed 100 psi. 

Install replacement valve into opening provided and 

designated for this purpose on water heater. 

Installation must conform with local codes or in the 

absence of local codes, Standard on Recreational 

Vehicles, ANSI A119.2 or CAN/CSA-Z240RV. 

 

 

 

 

 

 

 

  

CAUTION ELECTRICAL DAMAGE

Label all wires prior to disconnection when servicing controls. 

Wiring errors can cause improper and dangerous operation. 

Verify proper operation after servicing.

WIRING INSTRUCTIONS

Heater must be connected to fully rectified 
12 VDC current, taking care to assure 

RED 

lead is connected to +12 VDC (positive)

 

supply and

 green wire connected to -12VDC 

(negative) 

connections. Reversing polarity 

or connecting to AC power will damage the 
equipment which is not covered by 
warranty.

The appliance, when installed, must be 
electrically grounded in accordance with 
local codes or, in the absence of local 
codes, with the 

National Electrical Code, 

ANSI/NFPA 70 

and/or the 

CSA C22.1, 

Canadian Electrical Code.

The appliance must be disconnected from the gas 
supply piping system during any pressure testing of the 
system at test pressures in excess of 

½

 psi. The 

appliance must be isolated from the gas piping system 
during any pressure testing at test pressures equal to or 
less than 

½

 psi. Pressure inlet to valve, 13” W.C. 

maximum, 11” W.C. minimum. Pressure at outlet of 
valve is factory set at 10”. Burner manifold pressure is 
W.C. 8.9” W.C. +/- .2” at tap on burner manifold.

Flow

Meter

WIRING DIAGRAM

CONTROL BOARD

IGNITION BOARD

GAS 

VALVE

MODULATING VALVE

T- OUT

THERMISTER

T- MID

THERMISTER

RD-24

RD_18

BR-18

BR-18

T- IN

THERMISTER

BL-24

BR-18

Pressure

Switch

GR-18

RV-550 EC

Summary of Contents for cIAPMO-T RV-550-EC

Page 1: ...r to the current standards of Local codes or in the absence of local codes the National Fuel Gas Code ANSI Z223 1 NFPA 54 and or CSA B149 1 Natural Gas and Propane Installation Code Local codes or in...

Page 2: ...he case holes with no gaps or openings where the line passes through the case All connections must be made using TWO 2 wrenches to avoid twisting and damaging lines Damage voids the Warranty 5 Cut the...

Page 3: ...al Vehicles ANSI A119 2 or CAN CSA Z240RV CAUTION ELECTRICAL DAMAGE Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Verify prope...

Page 4: ...he showerhead button wastes water Each time this is done the showerhead trickles filling the hot water line with cold water This cold water has to be purged from the line each time the showerhead is t...

Page 5: ...er 8 Flue Hood 9 Flue Pipe 10 T In Thermistor 11 T Mid Thermistor 12 T Out Thermistor 13 165 F ECO 14 100 PSI Pressure Relief Valve 15 Gas Modulation Valve NOT PICTURED 16 12 VDC Relay 17 Control Boar...

Page 6: ...ions is in the off position An open valve can also permit water to bypass heater causing it not to fire There Is No Ignition When Water Is On Power vent is running 1 Be sure the gas valve at the tank...

Page 7: ...purchase PrecisionTemp will replace the complete water heater if the heat exchanger leaks due to corrosion This warranty includes reasonable labor charges required to replace the complete water heater...

Page 8: ...8...

Reviews: