PD865 Snooper Modbus
Serial Input Meter
Instruction Manual
64
Factory Defaults & User Settings
The following table shows the factory setting for most of the
programmable parameters on the meter. Next to the factory setting, the
user may record the new setting for the particular application. Note that
all settings are loaded with a default value, even though some settings
may not be used. For example, the Slave mode is the default setting,
but all of the Master mode settings have their default values loaded.
Model: ______________ S/N: _______________
Date: _________
Parameter
Display
Default Setting
User Setting
Mode
nmode
Master
Function Code
FunCode
03
Number of PVs
Pv.nbr
1
Slave ID PV1
Id-Pv1
247
Register
Number PV1
Reg.Pv1
40001
(5 digit)
Data Type
Data.1
Short integer
(Binary & Signed)
Byte Order
1234
Big-endian
Polling Time
t-poll
2.0 second
Slave Response
Timeout
t-resp
5.0 second
Baud
baud
2400
Parity
parity
Even
Byte-to-byte
timeout*
t-byte
0.01 second
Display decimal
point
dddd.dd
2 places
Input 1
inp 1
-199999
Display 1
dis 1
-1999.99
Input 2
inp 2
999999
Display 2
dis 2
9999.99