Model PD603 Process Meter Instruction Manual
Connections
All connections are made to removable screw terminal connectors
located at the rear of the meter.
!
Use copper wire with 60°C or 60/75°C insulation
for all line voltage connections. Observe all safety
regulations. Electrical wiring should be performed
in accordance with all applicable national, state,
and local codes to prevent damage to the meter
and ensure personnel safety.
Connector Labeling
The connectors label, affixed to the meter, shows the location of the
connectors available with requested configuration.
24V OUT
DW1911
POWER
X
X
V+
mA+
COM
Factory
Use
Only
3
4
1
2
5
2
1
2
1
P+
P-
+
-
SIGNAL
Figure 2. Connector Labeling - Meter with 24 V Supply
Power Connections
Power connections are made to a two-terminal connector labeled
POWER on Figure 2. The meter will operate regardless of DC polarity
connection. The + and - symbols are only a suggested wiring convention.
1
2
AC or DC
POWER
Required External Fuse:
5 A max, Slow Blow
POWER CONNECTOR
+
-
Figure 3. Power Connections