Setting up the Rate/Totalizer Meter (
setup
)
The
Setup
menu is used to select:
1. Enable or disable totalizer features
2. Units for Rate, Total, and Grand
Total
3. Decimal point position
4. Input Calibration
5. Display parameter and intensity
6. Relay operation
7. 4-20 mA analog output scaling
Press the Enter button to access any menu
or press Up arrow button to scroll through
choices. Press the Menu button to exit at
any time.
Setting the Input Signal (
Input
)
There is a switch, located to the right of the
input connector, which must be configured
according to the input level and type.
Jumper J4 located inside the meter, behind
the input signal connector, is used to select
the excitation voltage (24 V*, 10 V or 5 V)
which is supplied to the P+ and P- wiring
terminals.
Enter the Input menu to enable or disable
the totalizer features.
*
Default setting
Setting the Totalizer Features (
total
)
Enable or disable the totalizer features by selecting “
Yes
” or “
no
” after the input type has been set up. If
the totalizer features are disabled, most totalizer features and functions are hidden from the menus.
Note: The totalizer continues working in the background.