ModeL pd684 & pd689 Loop-powered rate/totaLizers

3

Programmable Exponent 

The programmable exponent function is used to linearize the level 
signal in open channel flow applications using weirs and flumes 
and display flow rate & total in engineering units. 

Totalizer Conversion Factor

The totalizer conversion factor is a number which is multiplied by 
the rate to compute total. For example, if the rate display is gallons 
per hour and total is desired in liters, a factor of 3.7843 should be 
used.  If  the  rate  display  is  gallons  per  hour  and  total  is  desired  in 
gallons, a factor of 1 should be used.

Total & Overflow Display

KEY:

= Screens Toggle

TOTAL

OVERFLOW

GAL

T

GAL

T

Alarm Condition

HI

ALARM TRIPS 

ALARM SCREEN

ACKNOWLEDGED

ACK

(Display Flashes)

Press ACK button

to acknowledge

ACK

4-20 mA output 

setUp & prograMMing

Easy Setup

Even with all the features packed into these meters, they’re still easy 
to setup and get running. Everything is programmed from the front 
panel  buttons  with  no  pots  or  jumpers  to  deal  with.  In  fact,  these 
meters can be scaled without a signal source for even quicker setup.

Main Menu

9.2846

GPS

s et up

pr oG

pas s

Run

Mode

Advanced Features Menu

To simplify the setup process, functions not needed for most applications 
are located in the Advanced Features menu. Press and hold the Menu 
button for five seconds to access the advanced features of the meter.

Isolated Open Collector Output

The open collector output may be assigned as a pulse or alarm output. 
As  a  pulse  output  this  feature  will  produce  one  pulse  output  per  a 
given number of counts (user select). For example, these meters can 
be programmed to produce one pulse for every 500 gallons totalized. 
This output can be sent to a PLC or a counter. As an alarm output this 
feature allows high or low rate indication or total setpoint indication.

instaLLation

There is no need to remove the meter from its case to complete the 
installation, wiring, and setup of the meter.

Mounting Dimensions                  

Units: Inch (mm)

3.61"

(92mm)

2.50"

(64mm)

4.68"

(119mm)

1.76"

(45mm)

0.59"

(15mm)

3.2"

(81mm)

2.45"

(62mm)

Notes:

1.  Panel cutout required: 3.622 x 1.772 (92 x 45) 
2  Panel thickness: 0.040 – 0.250 (1.0 – 6.4)
3.  Mounting brackets lock in place for easy mounting

This feature allows 
the PD684 & PD689 
to display total values 
up to eight digits. 
This sample shows a 
total of 68,923,684.

After an alarm  
has tripped simply 
press the ACK 
button for 3 seconds 
to acknowledge the 
alarm or wait for 
the alarm to reset 
automatically.

O+

O-

+

Alarm Indicator/

Pulse Counter

(e.g. PD693)

-

O+

O-

5-30 VDC

175 mA MAX

Relay output

connection

wiring

Pulse output

connection

wiring