PD2-7000
Helios Large Display Temperature Meter Instruction Manual
23
Display Functions & Messages
The meter displays various functions and messages during setup, programming, and operation. The
following table shows the main menu functions and messages in the order they appear in the menu.
Display
Parameter
Action/Setting Description
setup
Setup
Enter
Setup
menu
Input
Input
Enter
Input
selection menu
tc
TC
Set meter for thermocouple input (J, K, T, E, R, S, B, N, C)
Rtd
RTD
Set meter for RTD input (100Pt, 1000Pt, 10Cu, 120Ni)
A385
A385
Set meter for 0.00385 curve
A392
A392
Set meter for 0.00392 curve
F or C
F or C
Press Enter to select degrees F or C
units
Units
Select the display units/tags
Dec pt
Decimal point
Set decimal point (
dddd
,
dddd
.
d
,
dddd
°
F
,
dddd
.
dF
)
dsplay
Display
Enter the
Display
menu
Line 1
Display Line 1
Press Enter to assign the display line 1 parameter
(default: PV - temperature)
Line 2
Display Line 2
Press Enter to assign the display line 2 parameter
(default: engineering units)
d-Inty
Display intensity
Set display intensity level from 1 to 8
RELaY
Relay
Enter the
Relay
menu
RLY 1
Relay 1
Relay 1 setup
Act 1
Action 1
Set relay 1 action
Auto
Automatic
Set relay for automatic reset
A-nman
Auto-manual
Set relay for automatic & manual reset any time
LatCH
Latching
Set relay for latching operation
Lt-CLr
Latching-cleared
Set relay for latching operation with manual reset only after alarm
condition has cleared
Altern
Alternate
Set relay for pump alternation control
Sanmpl
Sampling
Set relay for sampling operation
OFF
Off
Disable relay and front panel status LED
(Select Off to enable Interlock feature)
Set 1
Set 1
Program set point 1
RSt 1
Reset 1
Program reset point 1
RLY 2
Relay 2
Relays 2-4 setup
FaiLSF
Fail-safe
Enter
Fail-safe
menu
FLS 1
Fail-safe 1
Set relay 1 fail-safe operation
on
On
Enable fail-safe operation
off
Off
Disable fail-safe operation
FLS 2
Fail-safe 2
Set relays 2-4 fail-safe operation
DeLAY
Delay
Enter relay
Time Delay
menu
DLY 1
Delay 1
Enter relay 1 time delay setup
On 1
On 1
Set relay 1 On time delay
OFF 1
Off 1
Set relay 1 Off time delay
DLY 2
Delay 2
Enter relays 2-4 time delay setup
break
Loop break
Set relay condition if loop break detected
www.
.com
1.800.561.8187