™ PD6262 Dual Analog Input Rate/Totalizer
Instruction Manual
42
Noise Filter (
filter
)
The noise filter is available for unusually noisy signals
that cause an unstable process variable display. The
noise filter averages the input signal over a certain
period. The filter level determines the length of time
over which the signal is averaged. The filter level can
be set between 2 and 199. The higher the filter level,
the longer the averaging time and so the longer it
takes the display to settle to its final value. Setting the
filter level to zero disables the filter function.
Noise Filter Bypass (
bypass
)
The noise filter bypass changes the behavior of the
meter so that small variations in the signal are filtered
out but large abrupt changes in the input signal are
displayed immediately. The bypass value determines
the minimum amount of signal change to be displayed
immediately. All signal changes smaller than the
bypass value are filtered or averaged by the meter.
The noise filter bypass may be set between 0.1 and
99.9% of full scale.
Rounding Feature (
round
)
The rounding feature is used to give the user a
steadier display with fluctuating signals. Rounding is
used in addition to the filter function.
Rounding causes the display to round to the nearest
value according to the rounding selected. This setting
affects the last two digits, regardless of decimal point
position.
Rounding
Selection
Actual
Value
Display
Value
Actual
Value
Display
Value
1
12.022
12.022
12.023
12.023
5
12.022
12.020
12.023
12.025
10
12.024
12.020
12.025
12.030
Modbus RTU Serial
Communications (
serial
)
The meter is equipped with serial communications
capability as a standard feature using Modbus RTU
Serial Communication Protocol.
The meter may be connected to a PC for initial
configuration via the onboard micro USB connection.
For ongoing digital communications with a computer
or other data terminal equipment, an RS-232, or RS-
485 option is required; see
•
DO NOT
connect any equipment other than
Precision Digital’s expansion modules, cables, or
meters to the RJ45 M LINK connector. Otherwise
damage will occur to the equipment and the
meter.
Note: More detailed instructions are provided with
each optional serial communications adapter.
Note: Refer to the ProVu Modbus Register Tables
located at www.predig.com for details.
When using more than one meter in a multi-drop
mode, each meter must be provided with its own
unique address. The meter address (Slave ID) may
be programmed between 1 and 247. The transmit
delay may be set between 0 and 199 ms. The parity
can be set to even, odd, or none with 1 or 2 stop bits.
Changes made to the Serial menu are initialized after
the MENU key is pressed or after navigating through
the t-byte parameter.