Helios PD2-6262 Dual Analog Input Rate/Totalizer
Instruction Manual
47
Advanced Features Menu & Display Messages
Display
Parameter
Action/Setting
Ch-b
Channel B
Set low-flow cutoff for
Channel B
Count
Count
Set total count direction
Ch-A
Channel A
Set total count direction for
Channel A
Ch-b
Channel B
Set total count direction for
Channel B
Tot C
Total count
Set direction of total count
Gtot C
Grand total
count
Set direction of grand total
count
up
Count up
Count up
Douwn
Count down
Count down
C
strt
Count start
Enter count down start
value
AoutPr
Analog output
programming
Program analog output
parameters
Aout*
Analog output
Program analog output
parameters
Source
Source
Select source for the
4-20 mA output
break
Loop break
Set analog output value if
input loop break is detected
Calib
Calibrate
Calibrate 4-20 mA output
(internal reference source
used for scaling the output)
4 nmA
4 mA output
Enter mA output value read
by milliamp meter with at
least 0.001 mA resolution
20 nmA
20 mA output
Enter mA output value read
by milliamp meter with at
least 0.001 mA resolution
O-rang
Overrange
Program mA output for
display overrange
u-rang
Underrange
Program mA output for
display underrange
nmAx
Maximum
Program maximum mA
output allowed
nmin
Minimum
Program minimum mA
output allowed
User
User I/O
Assign function keys and
digital I/O
F1*
F1* function key
Assign F1 function key
(*F1/F2/F3)
F4
F4 digital input
Assign F4 function (digital
input)
dI I
Digital input 1
Assign digital input 1
– 4
dO 1
Digital output 1
Assign digital output 1
– 4
ICal
Internal
calibration
Enter internal calibration
(used for recalibrating the
meter with a calibrated
signal source)
Ch-A
Channel A
Perform calibration on
channel A
Advanced Features Menu & Display Messages
Display
Parameter
Action/Setting
Ch-b
Channel B
Perform calibration on
channel B
C CAL
Current
calibration
Calibrate 4-20 mA current
input (internal reference
source used for scaling the
input)
C lo
Current low
Calibrate low current input
(e.g. 4 mA)
C Hi
Current high
Calibrate high current input
(e.g. 20 mA)
V CAL
Voltage
calibration
Calibrate voltage input
V Lo
Voltage low
Calibrate low voltage input
(e.g. 0 V)
V Hi
Voltage high
Calibrate high voltage input
(e.g. 10 V)
Diag
Diagnostics
Display parameter settings
LED t
LED test
Test all LEDs
Info
Information
Display software number
and version
erase
Erase
Erase MeterView Pro
software stored in meter’s
memory