CONDENSATE DRAIN
In the wall version of the ventilation system the condensate
is removed naturally to the outside, in the lower part of the
housing through the air intake, when installing the unit at an
angle of 2-3° inclination towards the street;
In the wall version of the ventilation system should be
equipped with a «mini-heater» option to protect the heat
exchanger from frosting and effective condensate removal;
In the combined version of the ventilation system
condensate removal is carried out similarly to the wall
version.
In the internal version of the ventilation system the
condensate is drained at the bottom of the unit using a 10
mm diameter nozzle.
The unit is mounted in such a way that the recuperator
side with the condensate drain pipe is in the lower part.
The ventilating system is mounted horizontally without
any inclination. Condensate drainage into the existing
sewage system. Condensate drainage pipes should have at
least 3 cm per 1 meter of downward slope.
The condensate shall be drained into the sewage system
via a siphon.
The condensate drain system shall not be operated in rooms
where the temperature is below 0 °C! If the temperature is
below 0 °C, the condensate drain system must be insulated
with thermal insulation or equipped with heating.