Pramac Industries
SERVICE BULLETIN
TSB1001
Page 3 of 3
Follow the steps below to remove the ground to neutral jumper wire.
Tools required: Phillips head screwdriver, 10mm Socket or wrench.
Make certain that the generator is not running before beginning.
Read the instructions completely
before beginning work.
1. Remove the bolts around the perimeter of the control panel using the 10mm socket or wrench
and rotate the panel down.
2. Locate the ground to neutral jumper. It should be a
green
wire connected from a
ground(green wires) point to a neutral(white wires) point. Reference Figure 3 below for the
typical position, circled in red. Note that the jumper could possibly be on any of the
receptacles but should be as shown below.
3. Loosen the
green
screw on the receptacle where one end of the jumper is connected and
remove the jumper from that position. Re-tighten the screw.
4. Loosen the
silver
screw on the receptacle at the other end of the jumper wire. Remove the
jumper from that position. Re-tighten the screw making sure that the white wire remains
connected. Discard the jumper wire.
5. Reinstall the control panel.
6. Make certain that all GFCI receptacles are reset by pushing the reset buttons on the front of
the receptacles.