background image

6333V103-IN

 

5

Electrical specifications

Specifications range:
-40°C to +60°C
Common specifications:
Supply voltage, DC 

 

Standard...............................................  8...35 VDC

 

ATEX Ex ................................................  8...30 VDC

Internal consumption ..................................  0.19...0.8 W

Voltage drop ................................................  8 VDC

Isolation voltage, channel 1 / channel 2: 

 

Standard...............................................  3.75 kVAC

 

ATEX Ex ................................................  1500 VAC

Warm-up time ..............................................  5 min.

Communications interface ..........................  Loop Link

Signal / noise ratio ......................................  Min. 60 dB 

Response time (programmable) ..................  0.33...60 s

Signal dynamics, input ................................  19 bit

Signal dynamics, output..............................  16 bit

Calibration temperature...............................  20...28°C

Accuracy, the greater of general and basic values:

Order: 6333

General values

 

Input type

Absolute 

accuracy

Temperature 

coefficient

All

 ±0.1% of span

≤ 

±0.01% of span / °C 

Type

Version

Galvanic 

isolation

Channels

6333 Standard 

: A 

ATEX Ex 

: B 

None 

: 1 Single 

: A 

Double 

: B

CONTENTS

CONTENTS

Summary of Contents for PRetrans 6333

Page 1: ...S I G N A L S T H E B E S T 6 3 3 3 DK UK FR DE ES RU 2 W i r e P r o g r a m m a b l e T r a n s m i t t e r N o 6 3 3 3 V 1 0 3 I N F r o m s e r n o 0 8 0 6 2 9 0 5 2 ...

Page 2: ... electronics A S offre une large gamme de produits pour le traite ment des signaux analogiques et numériques dans tous les domaines industriels La gamme de produits s étend des transmetteurs de température aux afficheurs des isolateurs aux interfaces SI jusqu aux modules universels Vous pouvez compter sur nos produits même dans les conditions d utilisation sévères p ex bruit électrique vibrations ...

Page 3: ...eclaration of conformity 2 Application 3 Technical characteristics 3 Mounting installation 3 Applications 4 Order 6333 5 Electrical specifications 5 Connections 8 Block diagram 9 Programming 10 Appendix 11 ATEX Installation Drawing 6333A 12 ATEX Installation Drawing 6333B 13 ...

Page 4: ...1326 1 2006 For specification of the acceptable EMC performance level refer to the electrical specifications for the module The ATEX Directive 94 9 EC and later amendments EN 60079 0 2006 EN 60079 11 2007 EN 60079 15 2005 and EN 60079 26 2007 ATEX certificate KEMA 10ATEX0007 X 6333A ATEX certificate KEMA 09ATEX0147 6333B Notified body KEMA Quality B V 0344 Utrechtseweg 310 6812 AR Arnhem P O Box 5...

Page 5: ...ignal for instance from valves or Ohmic level sensors Technical characteristics Within a few seconds the user can program PR6333 to measure temperatures within all RTD ranges defined by the norms The RTD and resistance inputs have cable compensation for 3 wire connection A limit can be programmed on the output signal Mounting installation Mounted vertically or horizontally on a DIN rail Using the ...

Page 6: ...4 6333V103 IN Applications V mA V mA 2 wire installation in control room 2 wire installation in control room RTD to 4 20 mA Resistance to 4 20 mA CONTENTS CONTENTS ...

Page 7: ...rm up time 5 min Communications interface Loop Link Signal noise ratio Min 60 dB Response time programmable 0 33 60 s Signal dynamics input 19 bit Signal dynamics output 16 bit Calibration temperature 20 28 C Accuracy the greater of general and basic values Order 6333 General values Input type Absolute accuracy Temperature coefficient All 0 1 of span 0 01 of span C Type Version Galvanic isolation ...

Page 8: ...ire 0 002 Ω Ω Sensor error detection Yes Outputs Current outputs Signal range 4 20 mA Min signal range 16 mA Updating time 135 ms Load resistance Vsupply 8 0 023 Ω Load stability 0 01 of span 100 Ω Sensor error detection Programmable 3 5 23 mA Namur NE43 Upscale 23 mA Namur NE43 Downscale 3 5 mA Of span Of the presently selected range RTD type Min value Max value Min span Standard Pt100 Ni100 Lin ...

Page 9: ...S approval 6333B KEMA 09ATEX0147 II 1 G Ex ia IIC T6 T5 Max amb temperature for T6 40 C Max amb temperature for T5 60 C ATEX applicable in zone 0 1 or 2 ATEX Installation Drawing No 6333QA01 GOST R approval VNIIM VNIIFTRI Cert no See www prelectronics com Observed authority requirements Standard EMC 2004 108 EC EN 61326 1 ATEX 94 9 EC EN 60079 0 EN 60079 11 EN 60079 15 EN 60079 26 CONTENTS CONTENT...

Page 10: ... 53 41 42 44 43 41 42 44 43 51 52 54 53 mA mA 23 21 22 11 12 13 Channel 1 Channel 2 Channel 2 Inputs Channel 1 RTD 2 wire RTD 2 wire RTD 3 wire RTD 3 wire Resistance 3 wire Resistance 2 wire Resistance 3 wire Resistance 2 wire Outputs 2 wire installation 2 wire installation CONTENTS ...

Page 11: ... Comp Supply Comm 44 13 23 11 21 43 42 41 53 54 51 52 CH 1 CH 2 0 16 mA mA MUX 4 mA PGA D A A D CPU EEPROM DC DC 6333 6333 Supply 4 20 mA Ex circuit only 6333B Input RTD Input Lin R Comp Supply Comm 44 13 23 11 21 43 42 41 53 54 51 52 CH 1 CH 2 0 1 6 m A m A M U X 4 m A PGA D A A D C P U E E P R O M DC DC 6333 6333 Supply 4 20 mA Ex circuit only 6333B Input RTD Input Lin R Comp Supply Comm CONTENT...

Page 12: ...s Loop Link is not approved for communication with modules installed in hazard ous Ex area Order Loop Link PRetrans 6333 13 23 11 21 Loop Link 5909 USB 5905 RS232 File Product Input Output Communication Language Option 08 30 00 PRetop 5331 Date 2004 8 10 043201594 PRelectronics Analog input Analog output Serial no Input type Output type 4 20mA Upscale Sensor error Pt100 DIN IEC 0 00 50 00 C 3 wire...

Page 13: ...6333V103 IN 11 Appendix ATEX Installation Drawing 6333A ATEX Installation Drawing 6333B CONTENTS CONTENTS ...

Page 14: ...007X Marking Standards EN 60079 0 2006 EN 60079 11 2007 EN 60079 15 2005 Special conditions for safe use For use in a potentially explosive atmosphere of flammable gasses vapours or mists the transmitter shall be mounted in an enclosure providing a degree of protection of at least IP54 in accordance to EN60529 II 3 G Ex nA nL IIC T6 T5 II 3 G Ex nL IIC T6 T5 II 3 G Ex nA ic IIC T6 T5 II 3 G Ex ic ...

Page 15: ...first two digits in the serial number ATEX Certificate KEMA 09ATEX 0147 Marking Standards EN 60079 0 2006 EN 60079 11 2007 EN 60079 26 2007 Installation notes The instructions provided with the equipment shall be followed in detail in order to assure safe operation Non Hazardous Area Hazardous area Zone 0 1 2 II 1 G Ex ia IIC T6 T5 Terminal 41 42 43 Uo 27 VDC Io 7 mA Po 45 mW Lo 35 mH Co 90 nF Ter...

Page 16: ...lvanic isolators for analogue and digital signals as well as HART signals A wide product range with both loop powered and universal isolators featuring linearisation inversion and scaling of output signals Isolation Interfaces for analogue and digital signals as well as HART signals between sensors I P converters frequency signals and control systems in Ex zone 0 1 2 and for some modules in zone 2...

Page 17: ...ax 45 86 37 30 85 www prelectronics fr sales prelectronics fr www prelectronics de sales prelectronics de www prelectronics es sales prelectronics es www prelectronics it sales prelectronics it www prelectronics se sales prelectronics se www prelectronics co uk sales prelectronics co uk www prelectronics com sales prelectronics com ...

Reviews: