10 2204V104-UK
PROGRAMMING
INPUT
PROGRAMING
DP1 (10-pole)
SW 1, 2, 3, 4, 5
SW ON
SW OFF
0...0.5 mA
0...20 mA
0...1 V
0...2.5 V
0...10 V
1, 3
1, 4
2, 3
2, 4
2, 3, 4
2, 4, 5
2, 3, 5
1, 4, 5
1, 3, 5
1, 5
For 20% offset on input,
set DP1 SW5 ON
e.g. input 4...20 mA
1, 4, 5
2, 3
OUTPUT
PROGRAMING
DP2 (4-pole)
SW 1 - 4
DP1 (10-pole)
SW 6, 7, 8, 9, 10
SW ON
SW OFF
ON
OFF
0...5 mA
0...20 mA
0...5 mA / 0...250 mV
0...20 mA / 0...1 V
0...5 mA / 0...2.5 V
0...20 mA / 0...10 V
4
3
1, 4
1, 3
2, 4
2, 3
1, 2, 3
1, 2, 4
2, 3
2, 4
1, 3
1, 4
7
8
6
6, 7
6, 8
6, 7, 8
6, 8, 9, 10
6, 7, 9, 10
7, 8, 9, 10
8, 9, 10
7, 9, 10
9, 10
For 20% offset on output,
set DP1 SW9 ON
e.g. output 4...20 mA
3
1, 2, 4
8, 9
6, 7, 10
For reversed output set DP1,
SW10 ON
e.g. output 20...4 mA
3
1, 2, 4
8, 9, 10
6, 7
Note:
At other spans than the above-mentioned, DP1 and DP2 have a different
setting which applies to the delivered special range.