Ex data for 5115B, all types:
Terminal 31, 32 and 33
Um............................................................... : 250 V
Ex data for 5115 B1 (input 1 for 5115 B3):
Terminal 41, 42, 44 to 43 (51, 52, 54 to 53)
Uo................................................................ : 7.5 VDC
Io.................................................................. : 6.0 mADC
Po ................................................................ : 11.25 mW
Lo ................................................................ : 200 mH
Co................................................................ : 6.0
µ
F
Ex data for 5115 B2 (input 2 for 5115 B3):
Terminal 44 to 41 (54 to 51)
Uo................................................................ : 28 VDC
Io.................................................................. : 87 mADC
Po ................................................................ : 0.62 W
Lo ................................................................ : 4.2 mH
Co................................................................ : 0.08
µ
F
Terminal 42, 43 to 41 (52, 53 to 51)
Uo................................................................ : 7.5 VDC
Io.................................................................. : 6.0 mADC
Po ................................................................ : 11.25 mW
Lo ................................................................ : 200 mH
Co................................................................ : 6.0
µ
F
EEx approval CENELEC:
DEMKO 00 .................................................. ATEX 128567
ATEX ............................................................ 0539 II (1) G
[EEx ia] IIC
Applicable in............................................... Zone 0, 1, or 2
Observed authority requirements: Standard:
EMC 89/336/EEC, Emission ....................... EN 50 081-1, EN 50 081-2
Immunity ....................... EN 50 082-2, EN 50 082-1
Emission and immunity ....................... EN 61 326
LVD 73/23/EEC............................................ EN 61 010-1
PELV/SELV................................................... IEC 364-4-41,
and EN 60 742
ATEX 94/9/EC.............................................. EN 50 014 and EN 50 020
35
Electrical specifications, mA / V / mV input:
Max. offset .................................................. 50% of selec. max. value
Current input:
Measurement range .................................... 0...100 mA
Min. measurement range (span) ................. 4 mA
Input resistance:
Supplied unit ............................................... nom. 10
Ω
+ PTC 10
Ω
Non-supplied unit........................................ R
SHUNT
=
∞
, V
DROP
< 6 V
Voltage input:
Measurement range .................................... 0...250 VDC
Min. measurement range (span) ................. 5 mVDC
Max. offset .................................................. 50% of selec. max. value
Input resistance
≤
2.5 VDC ......................... nom. 10 M
Ω
> 2.5 VDC ........................ nom. 5 M
Ω
Electrical specifications - OUTPUT:
Current output:
Signal range (span)...................................... 0...20 mA
Min. signal range (span) .............................. 10 mA
Load (max.).................................................. 20 mA / 600
Ω
/ 12 VDC
Load stability ...............................................
≤
0.01% of span / 100
Ω
Current limit.................................................
≤
28 mA
Voltage output:
Signal range (span)...................................... 0...10 VDC
Min. signal range (span) .............................. 500 mV
Load (min.)................................................... 500 k
Ω
2-wire 4...20 mA output:
Signal range ................................................ 4...20 mA
Load stability ...............................................
≤
0.01% of span / 100
Ω
Load resistance ...........................................
≤
(Vsupply
-3.5) / 0.023 A [
Ω
]
Max. external 2-wire supply........................ 29 VDC
Effect of external 2-wire supply
voltage change............................................ < 0.005% of span / V
Sensor error detection:
Programmable ............................................. 0...23 mA
NAMUR NE43 Upscale ............................... 23 mA
NAMUR NE43 Downscale........................... 3.5 mA
Of span = Of the presently selected range