9107 - Product version 9107-002
23
9107QA01
LERBAKKEN 10, 8410 RØNDE DENMARK
Revision date:
2013-09-11
Version Revision
V3 R0
Prepared by:
PB
Page:
1/2
ATEX Installation drawing
For safe installation of 9107B the following must be observed. The module shall only be
installed by qualified personnel who are familiar with the national and international laws,
directives and standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
For Installation in Zone 2 the following must be observed.
The 4501 programming module is to be used solely with PRelectronics modules. It is
important that the module is undamaged and has not been altered or modified in any way.
Only 4501 modules free of dust and moisture shall be installed.
9107BA:
1 channel
HART
-transparent driver
9107BB:
2 channel
HART
-transparent driver
ATEX Certificate
: ………………………………………………..…. DEKRA 11 ATEX0247X
Marking
Standards
EN 60079-0 : 2012, EN 60079-11 : 2012, EN 60079-15 : 2010
EN 60079-26 : 2007
Installation notes:
Install in pollution degree 2, overvoltage category II as defined in EN 60664-1
Do not separate connectors when energized and an explosive gas mixture is present.
Do not mount or remove modules from the Power Rail when an explosive gas mixture is present.
Disconnect power before servicing.
The wiring of unused terminals is not allowed.
In type of protection [Ex ia Da] the parameters for intrinsic safety for gas group IIB are applicable.
For installation in Zone 2, the module shall be installed in an enclosure in type of protection Ex n or
Ex e, providing a degree of protection of at least IP54. Cable entry devices and blanking elements
shall fulfill the same requirements.
For installation on Power Rail in Zone 2, only Power Rail type 9400 supplied by Power Control Unit
type 9410 (Type Examination Certificate KEMA 07ATEX0152 X) is allowed.
II (1) G [Ex ia Ga] IIC/IIB/IIA
II 3 G Ex nA nC IIC T4 Gc
II (1) D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I
Status Relay.
terminal (33,34)
Zone 2 Installation
Voltage max:
125 VAC / 110 VDC
32 VAC / 32 VDC
Power max:
62.5 VA / 32 W
16 VA / 32 W
Current max:
0.5 A AC / 0.3 ADC
0.5 A AC / 1ADC
Supply terminal
(31,32)
Voltage :
19.2 – 31.2 VDC
ATEX Installation Drawing