CSA Installation drawing 6333QC02-V2R0 

 

For safe installation of the single channel 6333A1A or the two channel 6333A1B 

the following must be observed. The module shall only be Installed by qualified 

personnel who are familiar with the national and international laws, directives 

and standards that apply to this area.  

 

 

 

 

 

 

     

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

                      

 

 

 

 

 

 

 

T4: -40ºC to 85 ºC 

T6: -40ºC to 60 ºC 

Terminal: 41,42,43,44  

Uo: 5 VDC 

Io:   4 mA 

Po:  20 mW 

Lo:  900 mH 

Co:  1000 

μ

13

11

44

43

42
41

+

-

23

21

54

53

52

51

+

-

CH2

CH1

Terminal:  

11-13  

 

Functional Ratings: 

U nominal 

 35 VDC;  

I nominal   

 3.5 - 23 mA

 

Marking 

Class I, Division 2, Group A,B,C,D T6…T4 

Ex nA[ic] IIC T6…T4  

Class I Zone 2 AEx nA[ic] IIC T6…T4 

Hazardous Area 

CL I, Div 2, GP ABCD 

CL I, Zone 2, IIC  

 

Terminal:  

21-23 

 

Functional Ratings: 

U nominal 

 35 VDC;  

I nominal   

 3.5 - 23 mA

 

Terminal:  

51,52,53,54 

Uo: 5 VDC 

Io:   4 mA 

Po:  20 mW 

Lo:  900 mH 

Co:  1000

μ

   

 

NI Installation instructions 

 

The transmitter must be installed in an enclosure providing a degree of protection of at 

least IP54 according to IEC60529 that is suitable for the application and is correctly 

installed. Cable entry devices and blanking elements shall fulfill the same requirements. 

If the enclosure is made of non-metallic materials or of painted metal, electrostatic 

charging shall be avoided. 

Use supply wires with a rating of at least 5 K above the ambient temperature. 

Supply from a Class 2 Power Supply with Transient protection or equivalent. 

 

WARNING: Substitution of components may impair suitability for Class I, Division 2 

AVERTISSEMENT: la substitution de composants peut nuire à l'aptitude à la Classe I, 

Division 2. 

 

WARNING: Do not disconnect equipment unless power has been switched off or the 

area is known to be safe. 

AVERTISSEMENT: Ne débranchez pas l'équipement sauf si l'alimentation a été 

coupée ou si la zone est connue pour être sûre. 

 

Non Incendive field wiring installation 

The non incendive field Wiring Circuit concept allows interconnection of Nonincendive 

Field wiring Apparatus with Associated Nonincendive Field Wiring Apparatus or 

Assosicated Intrinsically Safe Apparatus or Associated Apparatus not specially 

examined in combination as a syatem using any of the wiring methods permitted for 

unclassified locations,  

Voc < Vmax, Ca 

 Ci + Ccable , La 

 Li + Lcable. 

FM Installation drawing 6333QF01-V1R0 

 
 

 

 

 

 

 

 

 

 

 

  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Installation notes 

For installation in Class I the Transmitter must be installed in a suitable enclosure to 

meet installation codes stipulated in The National Electrical Code (ANSI-NFPA 70).  

Equipment that is FM-approved for intrinsic safety may be connected to barriers based 

on the Entity Concept. This concept permits interconnection of approved transmitters, 

meters and other devices in combinations, which have not been specifically examined 

by FM, provided that the agency's criteria are met. The combination is then intrinsically 

safe, if the entity concept is acceptable to the authority having jurisdiction over the 

installation. 

 

The entity concept criteria are as follows: The intrinsically safe devices, other than 

barriers, must not be a source of power. The maximum voltage Ui(VMAX) and current 

Ii(IMAX), and maximum power Pi(Pmax), which the device can receive and remain 

intrinsically safe, must be equal to or greater than the voltage (Uo or VOC or Vt) and 

current (Io or ISC or It) and the power Po which can be delivered by the barrier. The 

sum of the maximum unprotected capacitance (Ci) for each intrinsically device and the 

interconnecting wiring must be less than the capacitance (Ca) which can be safely 

connected to the barrier. The sum of the maximum unprotected inductance (Li) for each 

intrinsically device and the interconnecting wiring must be less than the inductance (La) 

which can be safely connected to the barrier. The entity parameters Uo, VOC or Vt and 

Io, ISC or It, and Ca and La for barriers are provided by the barrier manufacturer. 

 

Non Hazardous Location

 

Hazardous (Classified ) Location 

Class I, Division 1, Group A,B,C,D T4..T6 

Class I, Zone 0, AEx ia IIC T4..T6 

T6:  -40 ≤ Ta ≤ 60ºC  

T4:  -40 ≤ Ta ≤ 85ºC  

13
12

43

42

41

+

-

Barrier

23

22

53

52

51

+

-

Barrier

6333B1A : one channel 

6333B1B : two channel

CH2

CH1

11

21

 

 

 

 

 

 

 

 

  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Installation notes 

The Transmitter must be installed in a suitable enclosure to meet installation codes 

stipulated in The National Electrical Code (ANSI-NFPA 70).  

 

To assure a Non-Incendive system the transmitter and associated apparatus must be 

wired in accordance with the associated apparatus manufacturers field wiring 

instructions and the circuit diagram shown above. 

Non Hazardous Location

 

Hazardous (Classified ) Location 

Class I, Division 2, Group A,B,C,D T4..T6 

Class I, Zone 2, IIC T4..T6 

T6:  -40 ≤ Ta ≤ 60ºC  

T4:  -40 ≤ Ta ≤ 85ºC  

13
12

43

42

41

+

-

23

22

53

52

51

+

-

Associated 

apparatus

6333A1A: one channel

6333A1B: two channel

CH2

CH1

11

21

Associated 

apparatus

CSA Installation drawing 6333QC01-V1R0 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Installation notes 

The Transmitter must be installed in a suitable enclosure to meet installation 

codes stipulated in The Canadian Electrical Code (CEC).  
 
Substitution of components may impair intrinsic safety. 

Non Hazardous Location

 

Hazardous (Classified ) Location 

IS,Class I, Division 1, Group A,B,C,D T4..T6 

Ex ia IIC T4..T6 Ga 

Class I, Zone 0, AEx ia IIC T4..T6 Ga 

Terminal:  

11,13 

Ui: 30 VDC 

Ii:   120 mA 

Pi:  0.84 W 

Li:  10μH 

Ci:  6.2nF 

 

Co(Ca) > ∑(Ci+Ccable) 

Lo(La)  > ∑ (Li+Lcable) 

T6:  -40 ≤ Ta ≤ 60ºC 

T4:  -40 ≤ Ta ≤ 85ºC 

13

11

43

42
41

+

-

Barrier

6333B1A

CH1

Terminal: 41,42,43 

Connect to passive 

or non-energy 

storing devices 

such as RTD’s 

Resistors and 

Thermocouples 

only. 

 

 

 

 

 

 

 

 

 

 

  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
 
 
 
 
 
 
 
 
 

Installation notes 

The Transmitter must be installed in a suitable enclosure to meet installation 

codes stipulated in The Canadian Electrical Code (CEC).  
 
Channel 1 and Channel 2 are separate channels and therefore separate 

shielded cables shall be used for each channel. 
 
Substitution of components may impair intrinsic safety. 

Non Hazardous Location

 

Hazardous (Classified ) Location 

IS,Class I, Division 1, Group A,B,C,D T4..T6 

Ex ia IIC T4..T6 Ga 

Class I, Zone 0, AEx ia IIC T4..T6 Ga 

Terminal:  

11, 13 and  

21, 23 

Ui: 30 VDC 

Ii:   120 mA 

Pi:  0.84 W 

Li:  10μH 

Ci:  6.2nF 

 

Co(Ca) > ∑(Ci+Ccable) 

Lo(La)  > ∑ (Li+Lcable) 

T6:  -40 ≤ Ta ≤ 60ºC 

T4:  -40 ≤ Ta ≤ 85ºC  

13

11

43

42

41

+

-

Barrier

23

21

53

52

51

+

-

Barrier

6333B1B

CH2

CH1

Terminal: 41,42,43 

                 51,52,53 

Connect to passive or 

non-energy storing 

devices such as 

RTD’s Resistors and 

Thermocouples only. 

 

 

ATEX-installation drawing 6333QA01-V3R0 

 

For safe installation of 6333Bxx the following must be observed. 

The module shall only be installed by qualified personnel who are 

familiar with the national and international laws, directives and 

standards that apply to this area. Year of manufacture can be taken 

from the first two digits in the serial number. 

 

 

ATEX Certificate        DEKRA 20ATEX 0105X 

 

Marking 

 

 

 

   

 

Standards 

EN IEC 60079-0: 2018, EN 60079-11: 2012 

 

 

 

 

 

 

 

  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Non Hazardous Area

 

 

Hazardous area 

Zone 0, 1, 2, 21, 22 

 

II 1 G Ex ia IIC T6...T4 Ga  

II 2 D Ex ia IIIC Db 

I M1 Ex ia I Ma 

Terminal:  

11,13 and  

21,23 

Ui: 30 VDC 

Ii:   120 mA 

Pi:  0.84 W or  

Pi:  0.75 W 

Li:  10 

μ

Ci:  6.2 nF 

Terminal: 

41,42,43 

Uo: 30 VDC 

Io:   8 mA 

Po:  60 mW 

Lo:  35 mH 

Co:  60.8 nF 

Terminal: 

51,52,53 

Uo: 30 VDC 

Io:   8 mA 

Po:  60 mW 

Lo:  35 mH 

Co:  60.8 nF 

 

13

11

43

42
41

+

-

Barrier

23

21

53

52

51

+

-

Barrier

6333

CH2

CH1

 

 

 

Temperature  

Class 

Ambient temperature range 

Pi: 0.84 W 

Pi: 0.75 W 

T6 

-40°C to +40°C

 

-40°C to +45°C

 

T5 

-40°C to +55°C

 

-40°C to +60°C

 

T4 

-40°C to +85°C

 

-40°C to +85°C

 

 

Installation notes 

 

If the enclosure is made of non-metallic plastic materials, electrostatic 

charges on the transmitter enclosure shall be avoided. 

 

If the transmitter is installed in an explosive atmosphere requiring the use of 

equipment protection level Ga, the transmitter shall be mounted in an 

enclosure that provides a degree of protection of at least IP20 according to  

EN 60529, and that is suitable for the application and correctly installed. 

 

If the transmitter is installed in an explosive atmosphere requiring the use of 

equipment protection level Ga or Ma, and if the enclosure is made of 

aluminum, it must be installed such, that ignition sources due to impact and 

friction sparks are excluded. 

 

If the transmitter is installed in an explosive atmosphere requiring the use of 

equipment protection level Db, the transmitter shall be mounted in a 

separately certified enclosure that provides a degree of protection of at least 

IP5X according to EN 60079-0, and that is suitable for the application and 

correctly installed. 

 

If the transmitter is installed in an explosive atmosphere requiring the use of 

equipment protection level Ma, the transmitter shall be mounted in an 

enclosure that provides a degree of protection of at least IP54 according to  

EN 60529, and that is suitable for the application and correctly installed. 

 

Cable entries and blanking elements shall be used that are suitable for the 

application and correctly installed. 

 

For an ambient temperature 

 60ºC, heat resistant cables shall be used with 

a rating of at least 20 K above the ambient temperature. 

 

ATEX-installation drawing 6333QA02-V3R0 

 

For safe installation of 6333A the following must be observed. The module 

shall only be installed by qualified personnel who are familiar with the national 

and international laws, directives and standards that apply to this area. Year of 

manufacture can be taken from the first two digits in the serial number. 

 

Certificate                  DEKRA 20ATEX0106 X 

 

Marking 

 

 

 

 

Standards 

EN 60079-0: 2018, EN 60079-11: 2012,  

 

 

EN 60079-15: 2010, EN 60079-7:2015+A1: 2018 

 

Terminal  

41,42,43 

51,52,53 

Terminal  

11,12,13 

21,22,23 

Terminal 

11,12,13 

21,22,23 

Terminal 

11,12,13 

21,22,23 

Ex ic IIC,Ex ic IIIC   Ex ic IIC,Ex ic IIIC  Ex ic IIC,Ex ic IIIC  Ex nA, Ex ec 
Uo:  5 V 

Io:   4 mA 

Po:  20 mW 

Lo:  900 mH 

Co: 1000 

μF

 

Ui = 35 V 

Ii = 110 mA 

Ci = 6.2 nF 

Li = 1

0 μH

 

 

Ui = 24 V 

Ii = 260 mA 

Ci = 6.2 nF 

Li = 1

0 μH

 

Umax ≤ 35 V

DC 

or 

Umax ≤ 24 VDC

 

 

Ex ic IIC, Ex ic IIIC 

Temperature  

Class 

Ambient temperature range 

Ui=35 V 

Ui=24 V 

T6 

-40°C to +54°C

 

-40°C to +63°C

 

T5 

-40°C to +69°C

 

-40°C to +78°C

 

T4 

-40°C to +85°C

 

-40°C to +85°C

 

 

Ex ec, Ex nA 

Temperature  

Class 

Ambient temperature range 

Vmax=35 V 

Vmax=24 V 

T6 

-40°C to +43°C

 

-40°C to +55°C

 

T5 

-40°C to +85°C

 

-40°C to +85°C

 

T4 

-40°C to +85°C

 

-40°C to +85°C

 

 

II 3 G  Ex nA [ic] IIC T6 … T4 Gc 

II 3 G  Ex ec [ic] IIC T6 … T4 Gc 

II 3 G  Ex ic IIC T6 … T4 Gc 

II 3 D  Ex ic IIIC Dc 

   

     

 

     

 

      

        

      

 

PR electronics A/S

 • Lerbakken 10 • DK-8410 Rønde • 

T

 +45 86 37 26 77 • [email protected] • www.prelectronics.com

F20.1/2022-03-28/HGA

EU DECLARATION OF CONFORMITY

(6333DoC_103)

As manufacturer

PR electronics A/S, Lerbakken 10, DK-8410 Rønde

hereby declares that the following product:

Type: 6333 

Name: 

2-wire programmable transmitter 

is in conformity with the following directives and standards:

The EMC Directive 2014/30/EU and later amendments

EN 61326-1 : 2013

  Immunity test requirements for equipment intended to be used in an industrial electromagnetic 

environment. For specification of the acceptable EMC performance level, refer to the electrical 
specifications for the device.

The ATEX Directive 2014/34/EU and later amendments

EN IEC 60079-0 : 2018, EN 60079-7 : 2015 + A1 : 2018, EN 60079-11 : 2012
and EN 60079-15 : 2010
ATEX certificate: DEKRA 20ATEX0106 X (6333A)
ATEX certificate: DEKRA 20ATEX0105 X (6333B)

ATEX notified body (type approval)

DEKRA Certification B.V. 

Meander 1051, 6825 MJ Arnhem 

P.O. Box 5185, 6802 ED Arnhem 

The Netherlands

The RoHS2 Directive 2011/65/EU and later amendments

EN IEC 63000 : 2018

Notified body 0344

DEKRA Certification B.V.  

Meander 1051, 6825 MJ Arnhem 

P.O. Box 5185, 6802 ED Arnhem 

The Netherlands

Rønde, 22 April 2022 

Stig Lindemann, CTO

 

Manufacturer’s signature

Installation notes 

If the enclosure is made of non-metallic plastic materials, electrostatic 

charges on the transmitter enclosure shall be avoided. 

 

If the transmitter is installed in an explosive atmosphere requiring the use of 

equipment protection level Gc and applied in type of protection Ex ic, the 

transmitter shall be mounted in an enclosure that provides a degree of 

protection of at least IP20 according to EN 60529, and that is suitable for the 

application and correctly installed. 

 

If the transmitter is installed in an explosive atmosphere requiring the use of 

equipment protection level Dc, the transmitter shall be mounted in a 

separately certified enclosure that provides a degree of protection of at least 

IP5X according to EN 60079-0, and that is suitable for the application and 

correctly installed. The surface temperature of the outer enclosure is +20 K 

above the ambient temperature, determined without a dust layer. 

Ambient temperature range: -40°C to +85°C. 

 

If the transmitter is installed in an explosive atmosphere requiring the use of 

equipment protection level Gc and applied in type of protection Ex nA or Ex 

ec, the transmitter shall be mounted in a separately certified enclosure that 

provides a degree of protection of at least IP54 according to EN 60079-0, 

and that is suitable for the application and correctly installed. 

 

If the transmitter is installed in an explosive atmosphere requiring the use of 

equipment protection level Gc and applied in type of protection Ex nA or Ex 

ec, the equipment shall only be used in an area of not more than pollution 

degree 2, as defined in EN 60664-1. 

 

 

IECEx-installation drawing 6333QI01-V2R0 

 

For safe installation of 6333Bxx the following must be observed. 

The module shall only be installed by qualified personnel who are 

familiar with the national and international laws, directives and 

standards that apply to this area. Year of manufacture can be taken 

from the first two digits in the serial number. 

 

 

Certificate        

 IECEx DEK 20.0062X 

 

Marking 

 

 

 

   

 

Standards 

 IEC 60079-0: 2017, IEC 60079-11: 2011 

 

 

 

 

 

 

 

  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Non Hazardous Area

 

 

Hazardous area 

Zone 0, 1, 2, 21, 22 

 

Ex ia IIC T6...T4 Ga  

Ex ia IIIC Db 

Ex ia I Ma 

Terminal:  

11,13 and  

21,23 

Ui: 30 VDC 

Ii:   120 mA 

Pi:  0.84 W or  

Pi:  0.75 W 

Li:  10 

μ

Ci:  6.2 nF 

Terminal: 

41,42,43 

Uo: 30 VDC 

Io:   8 mA 

Po:  60 mW 

Lo:  35 mH 

Co: 60.8 nF 

Terminal: 

51,52,53 

Uo: 30 VDC 

Io:   8 mA 

Po:  60 mW 

Lo:  35 mH 

Co: 60.8 nF 

13

11

43

42
41

+

-

23

21

53

52

51

+

-

6333

CH2

CH1

 

 

Temperature  

Class 

Ambient temperature range 

Pi: 0.84 W 

Pi: 0.75 W 

T6 

-40°C to +40°C

 

-40°C to +45°C

 

T5 

-40°C to +55°C

 

-40°C to +60°C

 

T4 

-40°C to +85°C

 

-40°C to +85°C

 

 

Installation notes 

 

If the enclosure is made of non-metallic plastic materials, electrostatic 

charges on the transmitter enclosure shall be avoided. 

 

If the transmitter is installed in an explosive atmosphere requiring the use of 

equipment protection level Ga, the transmitter shall be mounted in an 

enclosure that provides a degree of protection of at least IP20 according to 

IEC 60529, and that is suitable for the application and correctly installed. 

 

If the transmitter is installed in an explosive atmosphere requiring the use of 

equipment protection level Ga or Ma, and if the enclosure is made of 

aluminum, it must be installed such, that ignition sources due to impact and 

friction sparks are excluded. 

 

If the transmitter is installed in an explosive atmosphere requiring the use of 

equipment protection level Db, the transmitter shall be mounted in a 

separately certified enclosure that provides a degree of protection of at least 

IP5X according to IEC 60079-0, and that is suitable for the application and 

correctly installed. The surface temperature of the outer enclosure is +20 K 

above the ambient temperature, determined without a dust layer. 

Ambient temperature range: -40°C to +85°C. 

 

If the transmitter is installed in an explosive atmosphere requiring the use of 

equipment protection level Ma, the transmitter shall be mounted in an 

enclosure that provides a degree of protection of at least IP54 according to 

IEC 60529, and that is suitable for the application and correctly installed. 

Ambient temperature range: -40°C to +85°C. 

 

Cable entries and blanking elements shall be used that are suitable for the 

application and correctly installed. 

 

For an ambient temperature 

 60ºC, heat resistant cables shall be used with 

a rating of at least 20 K above the ambient temperature. 

 

 

 

IECEx-installation drawing 6333QI02-V2R0 

 

For safe installation of 6333A the following must be observed. The module 

shall only be installed by qualified personnel who are familiar with the national 

and international laws, directives and standards that apply to this area. Year of 

manufacture can be taken from the first two digits in the serial number. 

 

Certificate                  IECEx DEK 20.0062X 

 

Marking 

 

 

 

 

Standards 

IEC 60079-0: 2017, IEC 60079-11: 2011,  

 

 

IEC 60079-15: 2010, IEC 60079-7: 2017 

 

Terminal  

41,42,43 

51,52,53 

Terminal  

11,12,13 

21,22,23 

Terminal 

11,12,13 

21,22,23 

Terminal 

11,12,13 

21,22,23 

Ex ic IIC,Ex ic IIIC   Ex ic IIC,Ex ic IIIC  Ex ic IIC,Ex ic IIIC  Ex nA, Ex ec 
Uo: 5 V 

Io:  4 mA 

Po: 20 mW 

Lo:  900 mH 

Co: 1000 

μF

 

Ui = 35 V 

Ii = 110 mA 

Ci = 6.2 nF 

Li = 1

0 μH

 

 

Ui = 24 V 

Ii = 260 mA 

Ci = 6.2 nF 

Li = 1

0 μH

 

Umax ≤ 35 V

DC 

or 

Umax ≤ 24 V

DC 

 

Ex ic IIC, Ex ic IIIC 

Temperature  

Class 

Ambient temperature range 

Ui=35 V 

Ui=24 V 

T6 

-40°C to +54°C

 

-40°C to +63°C

 

T5 

-40°C to +69°C

 

-40°C to +78°C

 

T4 

-40°C to +85°C

 

-40°C to +85°C

 

 

Ex ec, Ex nA 

Temperature  

Class 

Ambient temperature range 

Vmax=35 V 

Vmax=24 V 

T6 

-40°C to +43°C

 

-40°C to +55°C

 

T5 

-40°C to +85°C

 

-40°C to +85°C

 

T4 

-40°C to +85°C

 

-40°C to +85°C

 

 

Ex nA [ic] IIC T6 … T4 Gc

 

Ex ec [ic] IIC T6 … T4 Gc

 

Ex ic IIC T6 … T4 Gc

 

Ex ic IIIC Dc 

Terminal: 1,2 

 Ex ic 

 

Ui = 35 VDC 

Ii = 110 mA 

Li  = 10 

μ

Ci = 1.0 nF 

 

 

 

Installation notes 

If the enclosure is made of non-metallic plastic materials, electrostatic 

charges on the transmitter enclosure shall be avoided. 

 

If the transmitter is installed in an explosive atmosphere requiring the use of 

equipment protection level Gc and applied in type of protection Ex ic, the 

transmitter shall be mounted in an enclosure that provides a degree of 

protection of at least IP20 according to IEC 60529, and that is suitable for the 

application and correctly installed. 

 

If the transmitter is installed in an explosive atmosphere requiring the use of 

equipment protection level Dc, the transmitter shall be mounted in a 

separately certified enclosure that provides a degree of protection of at least 

IP5X according to IEC 60079-0, and that is suitable for the application and 

correctly installed. The surface temperature of the outer enclosure is +20 K 

above the ambient temperature, determined without a dust layer. 

Ambient temperature range: -40°C to +85°C. 

 

If the transmitter is installed in an explosive atmosphere requiring the use of 

equipment protection level Gc and applied in type of protection Ex nA or Ex 

ec, the transmitter shall be mounted in a separately certified enclosure that 

provides a degree of protection of at least IP54 according to IEC 60079-0, 

and that is suitable for the application and correctly installed. 

 

If the transmitter is installed in an explosive atmosphere requiring the use of 

equipment protection level Gc and applied in type of protection Ex nA or Ex 

ec, the equipment shall only be used in an area of not more than pollution 

degree 2, as defined in IEC 60664-1. 