CSA Installation drawing 6333QC02-V2R0
For safe installation of the single channel 6333A1A or the two channel 6333A1B
the following must be observed. The module shall only be Installed by qualified
personnel who are familiar with the national and international laws, directives
and standards that apply to this area.
T4: -40ºC to 85 ºC
T6: -40ºC to 60 ºC
Terminal: 41,42,43,44
Uo: 5 VDC
Io: 4 mA
Po: 20 mW
Lo: 900 mH
Co: 1000
μ
F
13
11
44
43
42
41
+
-
23
21
54
53
52
51
+
-
CH2
CH1
Terminal:
11-13
Functional Ratings:
U nominal
≤
35 VDC;
I nominal
≤
3.5 - 23 mA
Marking
Class I, Division 2, Group A,B,C,D T6…T4
Ex nA[ic] IIC T6…T4
Class I Zone 2 AEx nA[ic] IIC T6…T4
Hazardous Area
CL I, Div 2, GP ABCD
CL I, Zone 2, IIC
Terminal:
21-23
Functional Ratings:
U nominal
≤
35 VDC;
I nominal
≤
3.5 - 23 mA
Terminal:
51,52,53,54
Uo: 5 VDC
Io: 4 mA
Po: 20 mW
Lo: 900 mH
Co: 1000
μ
F
NI Installation instructions
The transmitter must be installed in an enclosure providing a degree of protection of at
least IP54 according to IEC60529 that is suitable for the application and is correctly
installed. Cable entry devices and blanking elements shall fulfill the same requirements.
If the enclosure is made of non-metallic materials or of painted metal, electrostatic
charging shall be avoided.
Use supply wires with a rating of at least 5 K above the ambient temperature.
Supply from a Class 2 Power Supply with Transient protection or equivalent.
WARNING: Substitution of components may impair suitability for Class I, Division 2
AVERTISSEMENT: la substitution de composants peut nuire à l'aptitude à la Classe I,
Division 2.
WARNING: Do not disconnect equipment unless power has been switched off or the
area is known to be safe.
AVERTISSEMENT: Ne débranchez pas l'équipement sauf si l'alimentation a été
coupée ou si la zone est connue pour être sûre.
Non Incendive field wiring installation
The non incendive field Wiring Circuit concept allows interconnection of Nonincendive
Field wiring Apparatus with Associated Nonincendive Field Wiring Apparatus or
Assosicated Intrinsically Safe Apparatus or Associated Apparatus not specially
examined in combination as a syatem using any of the wiring methods permitted for
unclassified locations,
Voc < Vmax, Ca
≥
Ci + Ccable , La
≥
Li + Lcable.
FM Installation drawing 6333QF01-V1R0
Installation notes
For installation in Class I the Transmitter must be installed in a suitable enclosure to
meet installation codes stipulated in The National Electrical Code (ANSI-NFPA 70).
Equipment that is FM-approved for intrinsic safety may be connected to barriers based
on the Entity Concept. This concept permits interconnection of approved transmitters,
meters and other devices in combinations, which have not been specifically examined
by FM, provided that the agency's criteria are met. The combination is then intrinsically
safe, if the entity concept is acceptable to the authority having jurisdiction over the
installation.
The entity concept criteria are as follows: The intrinsically safe devices, other than
barriers, must not be a source of power. The maximum voltage Ui(VMAX) and current
Ii(IMAX), and maximum power Pi(Pmax), which the device can receive and remain
intrinsically safe, must be equal to or greater than the voltage (Uo or VOC or Vt) and
current (Io or ISC or It) and the power Po which can be delivered by the barrier. The
sum of the maximum unprotected capacitance (Ci) for each intrinsically device and the
interconnecting wiring must be less than the capacitance (Ca) which can be safely
connected to the barrier. The sum of the maximum unprotected inductance (Li) for each
intrinsically device and the interconnecting wiring must be less than the inductance (La)
which can be safely connected to the barrier. The entity parameters Uo, VOC or Vt and
Io, ISC or It, and Ca and La for barriers are provided by the barrier manufacturer.
Non Hazardous Location
Hazardous (Classified ) Location
Class I, Division 1, Group A,B,C,D T4..T6
Class I, Zone 0, AEx ia IIC T4..T6
T6: -40 ≤ Ta ≤ 60ºC
T4: -40 ≤ Ta ≤ 85ºC
13
12
43
42
41
+
-
Barrier
23
22
53
52
51
+
-
Barrier
6333B1A : one channel
6333B1B : two channel
CH2
CH1
11
21
Installation notes
The Transmitter must be installed in a suitable enclosure to meet installation codes
stipulated in The National Electrical Code (ANSI-NFPA 70).
To assure a Non-Incendive system the transmitter and associated apparatus must be
wired in accordance with the associated apparatus manufacturers field wiring
instructions and the circuit diagram shown above.
Non Hazardous Location
Hazardous (Classified ) Location
Class I, Division 2, Group A,B,C,D T4..T6
Class I, Zone 2, IIC T4..T6
T6: -40 ≤ Ta ≤ 60ºC
T4: -40 ≤ Ta ≤ 85ºC
13
12
43
42
41
+
-
23
22
53
52
51
+
-
Associated
apparatus
6333A1A: one channel
6333A1B: two channel
CH2
CH1
11
21
Associated
apparatus
CSA Installation drawing 6333QC01-V1R0
Installation notes
The Transmitter must be installed in a suitable enclosure to meet installation
codes stipulated in The Canadian Electrical Code (CEC).
Substitution of components may impair intrinsic safety.
Non Hazardous Location
Hazardous (Classified ) Location
IS,Class I, Division 1, Group A,B,C,D T4..T6
Ex ia IIC T4..T6 Ga
Class I, Zone 0, AEx ia IIC T4..T6 Ga
Terminal:
11,13
Ui: 30 VDC
Ii: 120 mA
Pi: 0.84 W
Li: 10μH
Ci: 6.2nF
Co(Ca) > ∑(Ci+Ccable)
Lo(La) > ∑ (Li+Lcable)
T6: -40 ≤ Ta ≤ 60ºC
T4: -40 ≤ Ta ≤ 85ºC
13
11
43
42
41
+
-
Barrier
6333B1A
CH1
Terminal: 41,42,43
Connect to passive
or non-energy
storing devices
such as RTD’s
Resistors and
Thermocouples
only.
Installation notes
The Transmitter must be installed in a suitable enclosure to meet installation
codes stipulated in The Canadian Electrical Code (CEC).
Channel 1 and Channel 2 are separate channels and therefore separate
shielded cables shall be used for each channel.
Substitution of components may impair intrinsic safety.
Non Hazardous Location
Hazardous (Classified ) Location
IS,Class I, Division 1, Group A,B,C,D T4..T6
Ex ia IIC T4..T6 Ga
Class I, Zone 0, AEx ia IIC T4..T6 Ga
Terminal:
11, 13 and
21, 23
Ui: 30 VDC
Ii: 120 mA
Pi: 0.84 W
Li: 10μH
Ci: 6.2nF
Co(Ca) > ∑(Ci+Ccable)
Lo(La) > ∑ (Li+Lcable)
T6: -40 ≤ Ta ≤ 60ºC
T4: -40 ≤ Ta ≤ 85ºC
13
11
43
42
41
+
-
Barrier
23
21
53
52
51
+
-
Barrier
6333B1B
CH2
CH1
Terminal: 41,42,43
51,52,53
Connect to passive or
non-energy storing
devices such as
RTD’s Resistors and
Thermocouples only.
ATEX-installation drawing 6333QA01-V3R0
For safe installation of 6333Bxx the following must be observed.
The module shall only be installed by qualified personnel who are
familiar with the national and international laws, directives and
standards that apply to this area. Year of manufacture can be taken
from the first two digits in the serial number.
ATEX Certificate DEKRA 20ATEX 0105X
Marking
Standards
EN IEC 60079-0: 2018, EN 60079-11: 2012
Non Hazardous Area
Hazardous area
Zone 0, 1, 2, 21, 22
II 1 G Ex ia IIC T6...T4 Ga
II 2 D Ex ia IIIC Db
I M1 Ex ia I Ma
Terminal:
11,13 and
21,23
Ui: 30 VDC
Ii: 120 mA
Pi: 0.84 W or
Pi: 0.75 W
Li: 10
μ
H
Ci: 6.2 nF
Terminal:
41,42,43
Uo: 30 VDC
Io: 8 mA
Po: 60 mW
Lo: 35 mH
Co: 60.8 nF
Terminal:
51,52,53
Uo: 30 VDC
Io: 8 mA
Po: 60 mW
Lo: 35 mH
Co: 60.8 nF
13
11
43
42
41
+
-
Barrier
23
21
53
52
51
+
-
Barrier
6333
CH2
CH1
Temperature
Class
Ambient temperature range
Pi: 0.84 W
Pi: 0.75 W
T6
-40°C to +40°C
-40°C to +45°C
T5
-40°C to +55°C
-40°C to +60°C
T4
-40°C to +85°C
-40°C to +85°C
Installation notes
If the enclosure is made of non-metallic plastic materials, electrostatic
charges on the transmitter enclosure shall be avoided.
If the transmitter is installed in an explosive atmosphere requiring the use of
equipment protection level Ga, the transmitter shall be mounted in an
enclosure that provides a degree of protection of at least IP20 according to
EN 60529, and that is suitable for the application and correctly installed.
If the transmitter is installed in an explosive atmosphere requiring the use of
equipment protection level Ga or Ma, and if the enclosure is made of
aluminum, it must be installed such, that ignition sources due to impact and
friction sparks are excluded.
If the transmitter is installed in an explosive atmosphere requiring the use of
equipment protection level Db, the transmitter shall be mounted in a
separately certified enclosure that provides a degree of protection of at least
IP5X according to EN 60079-0, and that is suitable for the application and
correctly installed.
If the transmitter is installed in an explosive atmosphere requiring the use of
equipment protection level Ma, the transmitter shall be mounted in an
enclosure that provides a degree of protection of at least IP54 according to
EN 60529, and that is suitable for the application and correctly installed.
Cable entries and blanking elements shall be used that are suitable for the
application and correctly installed.
For an ambient temperature
≥
60ºC, heat resistant cables shall be used with
a rating of at least 20 K above the ambient temperature.
ATEX-installation drawing 6333QA02-V3R0
For safe installation of 6333A the following must be observed. The module
shall only be installed by qualified personnel who are familiar with the national
and international laws, directives and standards that apply to this area. Year of
manufacture can be taken from the first two digits in the serial number.
Certificate DEKRA 20ATEX0106 X
Marking
Standards
EN 60079-0: 2018, EN 60079-11: 2012,
EN 60079-15: 2010, EN 60079-7:2015+A1: 2018
Terminal
41,42,43
51,52,53
Terminal
11,12,13
21,22,23
Terminal
11,12,13
21,22,23
Terminal
11,12,13
21,22,23
Ex ic IIC,Ex ic IIIC Ex ic IIC,Ex ic IIIC Ex ic IIC,Ex ic IIIC Ex nA, Ex ec
Uo: 5 V
Io: 4 mA
Po: 20 mW
Lo: 900 mH
Co: 1000
μF
Ui = 35 V
Ii = 110 mA
Ci = 6.2 nF
Li = 1
0 μH
Ui = 24 V
Ii = 260 mA
Ci = 6.2 nF
Li = 1
0 μH
Umax ≤ 35 V
DC
or
Umax ≤ 24 VDC
Ex ic IIC, Ex ic IIIC
Temperature
Class
Ambient temperature range
Ui=35 V
Ui=24 V
T6
-40°C to +54°C
-40°C to +63°C
T5
-40°C to +69°C
-40°C to +78°C
T4
-40°C to +85°C
-40°C to +85°C
Ex ec, Ex nA
Temperature
Class
Ambient temperature range
Vmax=35 V
Vmax=24 V
T6
-40°C to +43°C
-40°C to +55°C
T5
-40°C to +85°C
-40°C to +85°C
T4
-40°C to +85°C
-40°C to +85°C
II 3 G Ex nA [ic] IIC T6 … T4 Gc
II 3 G Ex ec [ic] IIC T6 … T4 Gc
II 3 G Ex ic IIC T6 … T4 Gc
II 3 D Ex ic IIIC Dc
PR electronics A/S
• Lerbakken 10 • DK-8410 Rønde •
T
+45 86 37 26 77 • [email protected] • www.prelectronics.com
F20.1/2022-03-28/HGA
EU DECLARATION OF CONFORMITY
(6333DoC_103)
As manufacturer
PR electronics A/S, Lerbakken 10, DK-8410 Rønde
hereby declares that the following product:
Type: 6333
Name:
2-wire programmable transmitter
is in conformity with the following directives and standards:
The EMC Directive 2014/30/EU and later amendments
EN 61326-1 : 2013
Immunity test requirements for equipment intended to be used in an industrial electromagnetic
environment. For specification of the acceptable EMC performance level, refer to the electrical
specifications for the device.
The ATEX Directive 2014/34/EU and later amendments
EN IEC 60079-0 : 2018, EN 60079-7 : 2015 + A1 : 2018, EN 60079-11 : 2012
and EN 60079-15 : 2010
ATEX certificate: DEKRA 20ATEX0106 X (6333A)
ATEX certificate: DEKRA 20ATEX0105 X (6333B)
ATEX notified body (type approval)
DEKRA Certification B.V.
Meander 1051, 6825 MJ Arnhem
P.O. Box 5185, 6802 ED Arnhem
The Netherlands
The RoHS2 Directive 2011/65/EU and later amendments
EN IEC 63000 : 2018
Notified body 0344
DEKRA Certification B.V.
Meander 1051, 6825 MJ Arnhem
P.O. Box 5185, 6802 ED Arnhem
The Netherlands
Rønde, 22 April 2022
Stig Lindemann, CTO
Manufacturer’s signature
Installation notes
If the enclosure is made of non-metallic plastic materials, electrostatic
charges on the transmitter enclosure shall be avoided.
If the transmitter is installed in an explosive atmosphere requiring the use of
equipment protection level Gc and applied in type of protection Ex ic, the
transmitter shall be mounted in an enclosure that provides a degree of
protection of at least IP20 according to EN 60529, and that is suitable for the
application and correctly installed.
If the transmitter is installed in an explosive atmosphere requiring the use of
equipment protection level Dc, the transmitter shall be mounted in a
separately certified enclosure that provides a degree of protection of at least
IP5X according to EN 60079-0, and that is suitable for the application and
correctly installed. The surface temperature of the outer enclosure is +20 K
above the ambient temperature, determined without a dust layer.
Ambient temperature range: -40°C to +85°C.
If the transmitter is installed in an explosive atmosphere requiring the use of
equipment protection level Gc and applied in type of protection Ex nA or Ex
ec, the transmitter shall be mounted in a separately certified enclosure that
provides a degree of protection of at least IP54 according to EN 60079-0,
and that is suitable for the application and correctly installed.
If the transmitter is installed in an explosive atmosphere requiring the use of
equipment protection level Gc and applied in type of protection Ex nA or Ex
ec, the equipment shall only be used in an area of not more than pollution
degree 2, as defined in EN 60664-1.
IECEx-installation drawing 6333QI01-V2R0
For safe installation of 6333Bxx the following must be observed.
The module shall only be installed by qualified personnel who are
familiar with the national and international laws, directives and
standards that apply to this area. Year of manufacture can be taken
from the first two digits in the serial number.
Certificate
IECEx DEK 20.0062X
Marking
Standards
IEC 60079-0: 2017, IEC 60079-11: 2011
Non Hazardous Area
Hazardous area
Zone 0, 1, 2, 21, 22
Ex ia IIC T6...T4 Ga
Ex ia IIIC Db
Ex ia I Ma
Terminal:
11,13 and
21,23
Ui: 30 VDC
Ii: 120 mA
Pi: 0.84 W or
Pi: 0.75 W
Li: 10
μ
H
Ci: 6.2 nF
Terminal:
41,42,43
Uo: 30 VDC
Io: 8 mA
Po: 60 mW
Lo: 35 mH
Co: 60.8 nF
Terminal:
51,52,53
Uo: 30 VDC
Io: 8 mA
Po: 60 mW
Lo: 35 mH
Co: 60.8 nF
13
11
43
42
41
+
-
23
21
53
52
51
+
-
6333
CH2
CH1
Temperature
Class
Ambient temperature range
Pi: 0.84 W
Pi: 0.75 W
T6
-40°C to +40°C
-40°C to +45°C
T5
-40°C to +55°C
-40°C to +60°C
T4
-40°C to +85°C
-40°C to +85°C
Installation notes
If the enclosure is made of non-metallic plastic materials, electrostatic
charges on the transmitter enclosure shall be avoided.
If the transmitter is installed in an explosive atmosphere requiring the use of
equipment protection level Ga, the transmitter shall be mounted in an
enclosure that provides a degree of protection of at least IP20 according to
IEC 60529, and that is suitable for the application and correctly installed.
If the transmitter is installed in an explosive atmosphere requiring the use of
equipment protection level Ga or Ma, and if the enclosure is made of
aluminum, it must be installed such, that ignition sources due to impact and
friction sparks are excluded.
If the transmitter is installed in an explosive atmosphere requiring the use of
equipment protection level Db, the transmitter shall be mounted in a
separately certified enclosure that provides a degree of protection of at least
IP5X according to IEC 60079-0, and that is suitable for the application and
correctly installed. The surface temperature of the outer enclosure is +20 K
above the ambient temperature, determined without a dust layer.
Ambient temperature range: -40°C to +85°C.
If the transmitter is installed in an explosive atmosphere requiring the use of
equipment protection level Ma, the transmitter shall be mounted in an
enclosure that provides a degree of protection of at least IP54 according to
IEC 60529, and that is suitable for the application and correctly installed.
Ambient temperature range: -40°C to +85°C.
Cable entries and blanking elements shall be used that are suitable for the
application and correctly installed.
For an ambient temperature
≥
60ºC, heat resistant cables shall be used with
a rating of at least 20 K above the ambient temperature.
IECEx-installation drawing 6333QI02-V2R0
For safe installation of 6333A the following must be observed. The module
shall only be installed by qualified personnel who are familiar with the national
and international laws, directives and standards that apply to this area. Year of
manufacture can be taken from the first two digits in the serial number.
Certificate IECEx DEK 20.0062X
Marking
Standards
IEC 60079-0: 2017, IEC 60079-11: 2011,
IEC 60079-15: 2010, IEC 60079-7: 2017
Terminal
41,42,43
51,52,53
Terminal
11,12,13
21,22,23
Terminal
11,12,13
21,22,23
Terminal
11,12,13
21,22,23
Ex ic IIC,Ex ic IIIC Ex ic IIC,Ex ic IIIC Ex ic IIC,Ex ic IIIC Ex nA, Ex ec
Uo: 5 V
Io: 4 mA
Po: 20 mW
Lo: 900 mH
Co: 1000
μF
Ui = 35 V
Ii = 110 mA
Ci = 6.2 nF
Li = 1
0 μH
Ui = 24 V
Ii = 260 mA
Ci = 6.2 nF
Li = 1
0 μH
Umax ≤ 35 V
DC
or
Umax ≤ 24 V
DC
Ex ic IIC, Ex ic IIIC
Temperature
Class
Ambient temperature range
Ui=35 V
Ui=24 V
T6
-40°C to +54°C
-40°C to +63°C
T5
-40°C to +69°C
-40°C to +78°C
T4
-40°C to +85°C
-40°C to +85°C
Ex ec, Ex nA
Temperature
Class
Ambient temperature range
Vmax=35 V
Vmax=24 V
T6
-40°C to +43°C
-40°C to +55°C
T5
-40°C to +85°C
-40°C to +85°C
T4
-40°C to +85°C
-40°C to +85°C
Ex nA [ic] IIC T6 … T4 Gc
Ex ec [ic] IIC T6 … T4 Gc
Ex ic IIC T6 … T4 Gc
Ex ic IIIC Dc
Terminal: 1,2
Ex ic
Ui = 35 VDC
Ii = 110 mA
Li = 10
μ
H
Ci = 1.0 nF
Installation notes
If the enclosure is made of non-metallic plastic materials, electrostatic
charges on the transmitter enclosure shall be avoided.
If the transmitter is installed in an explosive atmosphere requiring the use of
equipment protection level Gc and applied in type of protection Ex ic, the
transmitter shall be mounted in an enclosure that provides a degree of
protection of at least IP20 according to IEC 60529, and that is suitable for the
application and correctly installed.
If the transmitter is installed in an explosive atmosphere requiring the use of
equipment protection level Dc, the transmitter shall be mounted in a
separately certified enclosure that provides a degree of protection of at least
IP5X according to IEC 60079-0, and that is suitable for the application and
correctly installed. The surface temperature of the outer enclosure is +20 K
above the ambient temperature, determined without a dust layer.
Ambient temperature range: -40°C to +85°C.
If the transmitter is installed in an explosive atmosphere requiring the use of
equipment protection level Gc and applied in type of protection Ex nA or Ex
ec, the transmitter shall be mounted in a separately certified enclosure that
provides a degree of protection of at least IP54 according to IEC 60079-0,
and that is suitable for the application and correctly installed.
If the transmitter is installed in an explosive atmosphere requiring the use of
equipment protection level Gc and applied in type of protection Ex nA or Ex
ec, the equipment shall only be used in an area of not more than pollution
degree 2, as defined in IEC 60664-1.