CSA Installation drawing 6331QC01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
Revision date:
2014-10-20
Version Revision
V1R0
Page:
1/2
Installation notes.
The Transmitter must be installed in a suitable enclosure to meet installation codes stipulated in The
Canadian Electrical Code (CEC).
Substitution of components may impair intrinsic safety.
Non Hazardous Location
Hazardous (Classified ) Location
IS,Class I, Division 1, Group A,B,C,D T4..T6
Ex ia IIC T4..T6 Ga
Class I, Zone 0, AEx ia IIC T4..T6 Ga
Terminal:
11,13
Ui: 30 VDC
Ii: 120 mA
Pi: 0.84 W
Li: 10μH
Ci: 1.0nF
Co(Ca) >
∑
(Ci+Ccable)
Lo(La) >
∑
(Li+Lcable)
T6: -40 ≤ Ta ≤ 60ºC
T4: -40 ≤ Ta ≤ 85ºC
13
12
44
43
42
41
+
-
Barrier
6331B2A
CH1
11
Terminal: 41,42,43,44
Connect to passive or
non-energy storing
devices such as RTD’s
Resistors and
Thermocouples only.
CSA Installation Drawing - 6331B
18 6331V106-DE