
t
Off.N.C.
On.N.C.
On.N.C.
10
10
20
20
30
30
40
40
50
50
60
60
70
70
80
80
90
90
100
100
0
Off.N.O.
Off.N.O.
On.N.O.
t
10
10
20
20
30
30
40
40
50
50
60
60
70
70
80
80
90
90
100
100
0
Off.N.O.
Off.N.O.
On.N.O.
Off.N.C.
On.N.C.
On.N.C.
42
43
Configuration / oPerating the
funCtion Keys
Documentation.for.routing.diagram.
in general:
When.configuring.the.display.you.are.guided.through.all.parameters,.you.can.
choose.the.settings.which.fit.the.application..For.each.menu.there.is.a.scrol-
ling.help.text.which.is.automatically.shown.in.the.display,.this.starts.after.5.
seconds.if.no.key.has.been.activated..
Configuration.is.carried.out.by.using.the.3.function.keys.
1
.
will.increase.the.numerical.value.or.choose.the.next.parameter.
2
will.decrease.the.numerical.value.or.choose.the.previous.parameter.
3
.
will.accept.the.chosen.value.and.end.the.menu..
If.a.function.does.not.exist.in.the.display.all.parameters.are.skipped.to.make.
the.configuration.as.simple.as.possible.
Once.the.configuration.has.been.entered.the.display.will.show.“----”..
Pressing.and.holding.
3
.will.return.to.the.previous.menu.or.return.to.the.default.
state.(1.0).without.saving.the.changed.values.or.parameters..
If.no.key.is.activated.for.2.minutes,.the.display.will.return.to.the.default.state.
(1.0).without.saving.the.changed.values.or.parameters..
further explanations:
fast setpoint adjustment and relay test:
.These.menus.allow.you.to.change.
the.set.point.quickly.and.to.check.the.operation.of.the.relays.
Pressing.
1
.and.
2
.at.the.same.time.will.change.the.state.of.the.relay.–.this.change
is.indicated.by.the.diodes.on.the.display..Pressing.
3
.will.save.the.set.point.
change.
Holding.down.
3
.for.more.than.0.5.seconds.will.return.the.unit.to.the.default.
state.without.changing.the.set.point.
Password protection:
Using.a.password.will.stop.access.to.the.menu.and.parameters..There.are.two.
levels.of.password.protection..Passwords.between.0000…4999.allow.access.
to.the.fast.set.point.adjustment.and.relay.test..(Using.this.password.stops.
access.to.all.other.parts.of.the.menu)..Passwords.between.5000…9999.stop.
access.to.all.parts.of.the.menu,.fast.set.point.and.relay.test..(Current.set.
point.is.still.shown)..By.using.the.master.password.2008,.all.configuration.
menus.are.available.
graphic depiction of the relay function setpoint
:
Relay.units
Relay.units
Setpoint.=.50
Hysteresis.=.10
Hysteresis.=.10
Setpoint.=.50
relay action: increasing
relay action: Decreasing