Product manual  

5725

Programmable frequency indicator

TEMPER ATURE  |  I.S. INTERFACES  |  COMMUNIC ATION INTERFACES  |  MULTIFUNC TIONAL  |  ISOL ATION  |  DISPL AY

No. 5725V104-UK
From serial no.: 191059001

Summary of Contents for 5700 Series

Page 1: ...ERFORMANCE MADE SMARTER Product manual 5725 Programmable frequency indicator TEMPERATURE I S INTERFACES COMMUNICATION INTERFACES MULTIFUNCTIONAL ISOLATION DISPLAY No 5725V104 UK From serial no 191059001 ...

Page 2: ...achable have a built in display for readout of process values and diagnostics and can be configured via push buttons Product specific functionality includes communication via Modbus and Bluetooth and remote access using our PR Process Supervisor PPS application available for iOS and Android Our unique range of single devices covering multiple applications is easily deployable as your site standard...

Page 3: ... 9 Accessories 9 Electrical specifications 9 Sensor error indication inside and outside range 12 Connections 13 Block diagram 14 Configuration operating the function keys 15 Additional features from s n 121435001 15 Additional features from s n 181101000 16 Routing diagram for 5725A 17 Routing diagram for 5725D 19 Help text overview 21 Graphic depiction of the relay function setpoint 23 Installati...

Page 4: ...rning Until the device is fixed do not connect hazardous voltages to the device The following operations should only be carried out on a disconnected device and under ESD safe conditions Troubleshooting the device Repair of the device and replacement of circuit breakers must be done by PR electronics A S only Symbol identification Triangle with an exclamation mark Read the manual before installati...

Page 5: ... connection of the device should comply with national legislation for mounting of electric materials i e wire cross section protective fuse and location Stranded wire should be installed with an insulation stripping length of 5 mm or via a suitable insulated terminal such as a bootlace ferrule Descriptions of Input Output and supply connections are shown in the block diagram and side label The fol...

Page 6: ...6 5725V104 UK Front and back layout Picture 1 Front of 5725 Picture 2 Back of 5725 ...

Page 7: ... additional protection is provided by the optional 8335 splash proof cover Technical characteristics 4 digit display w 13 8 mm high 14 segment LED digits and adjustable decimal point Indicator is scalable from 1999 to 9999 Scrolling help text makes programming easy Built in excitation source for measuring NPN PNP NAMUR and SO sensors Fast response time of 1 cycle 100 ms and excellent accuracy of b...

Page 8: ...1 12 11 1 1 2 2 8 5725V104 UK Applications 21 6 253 VAC or 19 2 300 VDC Supply Output signals Input signals Supply 5 17 V Contact NPN Special trig current voltage Relay 1 Relay 2 Input Tacho Input gnd TTL S0 NAMUR PNP NPN Tacho Analog 0 4 20 mA Supply Supply ...

Page 9: ...ring cage Vibration IEC 60068 2 6 2 13 2 Hz 1 mm 13 2 100 Hz 0 7 g Common electrical specifications Supply voltage universal 21 6 253 VAC 50 60 Hz or 19 2 300 VDC Max required power 5725A 5725D 2 8 W 3 6 W Isolation voltage test operation 2 3 kVAC 250 VAC Signal noise ratio 60 dB Input specifications Frequency range f I conversion function 0 001 Hz to 50 kHz Low cut off frequency default value 0 0...

Page 10: ...in 44 programmable 5 17 V 20 mA S0 input acc to DIN 43864 Trig level LOW 2 2 mA Trig level HIGH 9 0 mA Input impedance 758 Ω 1 5 nF Sensor supply pin 44 fixed 17 V Special voltage input User programmable trig levels 0 05 6 50 V Hysteresis min 50 mV Input impedance selectable High Z 100 kΩ 1 5 nF Pull up and pull down 3 48 kΩ 1 5 nF Sensor supply pin 44 programmable 5 17 V 20 mA Special current inp...

Page 11: ...display counts 0 100 0 9999 On and Off delay 0 3600 s Power On delay 0 0 60 0 s Sensor error action Make Break Hold Max voltage 250 VAC VDC Max AC current 2 A Max AC power 500 VA Max DC current resistive load Urelay 30 VDC 2 ADC Urelay 30 VDC 1380 x U 2 relay x 1 0085 Urelay ADC Graphic depiction of 1380 x U 2 relay x 1 0085 Urelay Observed authority requirements EMC 2014 30 EU UK SI 2016 1091 LVD...

Page 12: ...8 min 31 sec Low cut off time IN HI flashing 19 8 µs IN LO flashing Sensor error indication inside and outside range Display out of range Indication Valid display value range Out of range limit Display readout 1999 to 9999 1999 1 9 9 9 flashing 9999 9 9 9 9 flashing Hardware error indication Error explanation Error cause Display readout Error in internal communication SPI etc Permanent error in in...

Page 13: ...43 41 42 44 45 46 43 31 32 41 42 44 45 46 43 41 42 44 45 46 43 41 42 44 45 46 43 11 12 21 22 24 25 26 23 R1 R2 Output Input Special current Special voltage Tacho PNP Supply NPN Contact NPN Current S0 TTL NAMUR Relays S0 TTL supply 8 3 V supply 17 V supply 5 17 V supply 5 17 V supply 5 17 V supply 5 17 V supply supply ...

Page 14: ...5725A D 1 1 2 2 3 3 4 4 44 46 45 43 42 41 R1 R2 mA VREG 5 17 V fin 14 5725V104 UK Block diagram I Output Common Relay 1 N O Relay 1 N C Common Relay 2 N O Relay 2 N C Supply Supply 21 6 253 VAC or 19 2 300 VDC Option D Gnd Option D Freq detector ...

Page 15: ...ating 1 and 2 simultaneously a relay test will be initiated and the relay will change state The setpoint adjustment will be saved by a quick press of 3 Holding down 3 for more that 0 5 seconds will return the display to the default state Monitor without changing the setpoint Password protection Using a password will block access to the menu and parameters If the configured password is not known pl...

Page 16: ... 181101000 Programmable display response time The response time of the 5725 display readout can be configured independently of the analog output response time This feature ensures a stable and easy readout of unstable or jittering input signals ...

Page 17: ... 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 2 5725V104 UK 17 Routing diagram for 5725A If no key is activated for 2 minutes the display will return to the default state Monitor without saving configuration changes 1 Increase value choose next parameter 2 Decrease value choose previous parameter 3 Save the chosen value and proceed to the next menu Hold 3 Back to previous menu return to default state Monitor wit...

Page 18: ...A 0 0 60 0 3 18 5725V104 UK 1 Only displayed if password is enabled E PASS YES 5 Only visible if max IN LO IN HI value is 50 Hz f I or 20 ms period time Default if visible YES else deactivated 10 Out of range limit is 0 0009 Hz 18 min 31 sec when L COF NO Out of range limit is 0 5 Hz 2 sec when L COF YES Start Start 4 Displays either Hz kHz or s ms for 1 sec before actual value is displayed When v...

Page 19: ...XT 57 1999 9999 ACT1 TXT 58 59 INCR DECR HYS1 T 60 0 9999 3 3 3 1 2 1 2 RELU TXT 52 53 PERC DISP REL1 TXT 54 56 TXT 67 69 SKIP 3 3 If RELU PERC If RELU DISP OFF SET 3 3 2 7 6 3 5725V104 UK 19 Routing diagram for 5725D If no key is activated for 2 minutes the display will return to the default state Monitor without saving configuration changes 1 Increase value choose next parameter 2 Decrease value...

Page 20: ...nly displayed if password is enabled E PASS YES 5 Only visible if max IN LO IN HI value is 50 Hz f I or 20 ms period time Default if visible YES else deactivated 10 Out of range limit is 0 0009 Hz 18 min 31 sec when L COF NO Out of range limit is 0 5 Hz 2 sec when L COF YES 4 Displays either Hz kHz or s ms for 1 sec before actual value is displayed When value hits digit limit while scrolling eithe...

Page 21: ... INPUT 23 TTL TTL SENSOR INPUT 24 NAMU NAMUR SENSOR INPUT 25 S0 S0 SENSOR INPUT 26 TACH TACHO SENSOR INPUT 27 Top line Scrolling text TXT NO XmA SPECIAL CURRENT SENSOR INPUT 28 XV SPECIAL VOLTAGE SENSOR INPUT 29 TR LO when special voltage input is selected xxxx SET LOW TRIGGER LEVEL IN VOLT 30 TR LO when special current input is selected xxxx SET LOW TRIGGER LEVEL IN mA 31 TR HI when special volta...

Page 22: ...Y OFF DELAY IN SECONDS 66 REL2 OFF RELAY 2 DISABLED 67 SETP ENTER RELAY 2 SETUP 68 SKIP SKIP RELAY 2 SETUP 69 Top line Scrolling text TXT NO SETP xxxx RELAY SETPOINT 57 ACT2 INCR ACTIVATE AT INCREASING SIGNAL 58 DECR ACTIVATE AT DECREASING SIGNAL 59 HYS2 xxxx RELAY HYSTERESIS 60 ERR2 HOLD HOLD RELAY AT ERROR 61 ACTI ACTIVATE RELAY AT ERROR 62 DEAC DEACTIVATE RELAY AT ERROR 63 NONE UNDEFINED STATUS...

Page 23: ...ff N C 100 90 80 70 60 50 40 30 20 10 0 10 20 30 40 50 60 70 80 90 100 t Off N O Off N O On N O On N C On N C Off N C 5725V104 UK 23 Graphic depiction of the relay function setpoint Relay units Relay units Setpoint 50 Hysteresis 10 Setpoint 50 Relay action Increasing Relay action Decreasing Hysteresis 10 ...

Page 24: ...enclosure Use 60 75 C copper conducters only Enclosure rating face only acc to UL50E Type 4X Max ambient temperature 60 C Max wire size pins 41 46 AWG 30 16 Max wire size others AWG 30 12 UL file number E248256 Relay outputs Max voltage 250 VRMS Max current 2 A AC Max AC power 500 VA Max current at 24 VDC 1 A ...

Page 25: ...nal technical support and guidance day to day delivery repair without charge within the warranty period and easily accessible documentation We are headquartered in Denmark and have offices and authorized partners the world over We are a local business with a global reach This means that we are always nearby and know your local markets well We are committed to your satisfaction and provide PERFORMA...

Page 26: ...andards for products communicating monitoring and connecting our customers process measurement points to their process control systems Our innovative patented technologies are derived from our extensive R D facilities and from having a great understanding of our customers needs and processes We are guided by principles of simplicity focus courage and excellence enabling some of the world s greates...