4
5335V116-UK
Electrical specifications
Specifications range:
-40°C to +85°C
Common specifications:
Supply voltage, DC
Standard ............................................................. 8.0...35 V
CSA, FM, ATEX, IECEx & INMETRO ........... 8.0...30 V
Isolation voltage, test / operation .................... 1.5 kVAC / 50 VAC
Warm-up time
............................................................ 30 s
Communications interface ...................................
HART
®
and Loop Link
Signal / noise ratio .................................................. Min. 60 dB
Response time (programmable) ......................... 1...60 s
EEprom error check ................................................. < 10 s
Signal dynamics, input ........................................... 22 bit
Signal dynamics, output ....................................... 16 bit
Calibration temperature ........................................ 20...28°C
Accuracy, the greater of general and basic values:
Order: 5335
Type
Version
5335
Standard
: A
CSA, FM, ATEX, IECEx & INMETRO
: D
General values
Input type
Absolute
accuracy
Temperature
coefficient
All
≤
±0.05% of span
≤
±0.005% of span / °C
5909 = Loop Link USB interface and PReset Software
8421 = DIN rail clip
Accessories