28
29
Electrical specifications:
Specifications range:
-20°C to +60°C
Common specifications:
Supply voltage, universal ............................ 24...230 VAC ±10%
50...60
Hz
24...250
VDC
±20%
Internal consumption ..................................
≤
2 W
Max. consumption ......................................
≤
3 W
Fuse ............................................................. 400 mA SB / 250 VAC
Isolation voltage, test / operation ............... 3.75 kVAC / 250 VAC
Communications interface .......................... Loop Link
Signal / noise ratio ...................................... Min. 60 dB (0...100 kHz)
Updating time:
Temperature input .................................... 115 ms
mA / V / mV input .................................... 75 ms
Response time (0...90%, 100...10%), programmable:
Temperature input .................................... 400 ms to 60 s
mA / V / mV input .................................... 250 ms to 60 s
Signal dynamics, input ................................ 22 bit
Signal dynamics, output ............................. 16 bit
Calibration temperature .............................. 20...28°C
29
5116
Type
Version
Order: 5116
Standard :
A
ATEX Ex approved : B
*NB!
Please remember to order CJC connectors
type 5910 / 5910EEx for TC inputs with internal CJC.
28
RTD and lin. resistance
2-wire transmitter
mA, VDC or potmeter
TC
Output
Output
Output
Output
2 relays
2 relays
2 relays
2 relays
Supply
Supply
Supply
Supply