8 4512V100-UK
4512 - configuration / operating the function keys
Documentation for routing diagram.
In general
When using the PR 4512 for configuration of a PR 4000 or PR 9000 device, you will be guided through all parameters and can
choose the settings which fit the application. For each menu there is a scrolling help text which is automatically shown in line
3 on the display.
Configuration is carried out by use of the 3 function keys:
1
will increase the numerical value or choose the next parameter
2
will decrease the numerical value or choose the previous parameter
3
will save the chosen value and proceed to the next menu
When configuration is completed, the display will return to the default state 1.0. Pressing and holding
3
will return to the
previous menu or return to the default state (1.0) without saving the changed values or parameters.
If no key is activated for 1 minute, the display will return to the default state (1.0) without saving the changed values or
parameters.
For device-specific programming menus, please refer to the user manual for each device, e.g. PR 4116.
4512 functions
The PR 4512 gives access to a number of functions which can be reached by answering “Yes” to the menu point “ADV.SET”
(see “4512 settings - routing diagram” on page 10).
Two factor authentication
When pairing the PPS device with PR 4512, a physical acknowledgement on the 4512 unit is required to complete pairing
(activation of the
3
button). Two factor authentication is enabled by default.
Log functionality
By selecting the “LOG.INT” menu item, it is possible to set the log interval in seconds. Valid selections are 1...9999 s.
You can also choose to reset the stored log in the menu item “LOG. DEL”.
The logging function exits automatically, if the PR 4512 is detached. If the PR 4512 is placed back on the same device, the
logging will continue. In the event of a power outage, logging will resume when power is restored.
Error Scenarios and help texts
Conditions
Scrolling help text Solution
4512 has been without
power until the battery is
fully discharged.
The RTC now needs to be
synchronized.
RTC
synchronization
required.
Connect a smart device to the 4512 and synchronize.
The error message will disappear when the synchronization is OK.
4512 has a log in progress
and is moved to a new
host.
New host detected,
move 4512 back to
previous host or
press OK to stop
log.
Move the 4512 back to the previous host or press OK.
Both actions will remove the error message.
The log will still be available in the memory of the 4512, but the device will
not continue logging.
Use PR 4590 or the PPS app to read out the log, before moving 4512 to a
new host.
4512 has a log in progress
and the user changes the
host configuration.
Configuration
change detected,
log has been
stopped.
If the configuration is changed while logging, the log is stopped
immediately.
Press OK to acknowledge that the log has been stopped in order to remove
the error message.
The log will still be available in the memory of the 4512, until a new log is
started.
Use PR 4590 or the PPS app to read out the log, before starting a new log.